Sale!

ICS Triplex T8403 Trusted TMR 24 VDC Digital Input Module

Parameter Specification
Manufacturer & Series ICS Triplex / Rockwell Automation Trusted System
Model Number T8403
Module Type Trusted TMR 24 VDC Digital Input Module (40 Channels)
System Architecture Triple Modular Redundant (TMR) / Hardware Implemented Fault Tolerant (HIFT)
Safety Integrity Level TÜV Certified for IEC 61508 SIL 3 applications
Number of Inputs 40 discrete digital input channels
Nominal Input Voltage 24 VDC (Sink/Source depending on Field Termination Assembly)
Operating Voltage Range 20 VDC to 32 VDC

Description

Core Product Summary (Brand / Model / Key Attributes)

The ICS Triplex T8403 is a 40-channel Triple Modular Redundant (TMR) 24 VDC Digital Input Module for the Rockwell Automation ICS Triplex Trusted safety system. Installed within a Trusted controller or expander chassis, this high-integrity discrete input module interfaces directly with field safety switches, emergency pushbuttons, pressure switches, and digital process transmitters. Built on a Hardware Implemented Fault Tolerant (HIFT) 3-2-0 degraded mode architecture, the T8403 ensures continuous input monitoring and fault containment in high-availability, safety-critical environments.

Certified for IEC 61508 SIL 3 application loops, the T8403 provides 40 optically isolated input channels organized into groups for maximum electrical protection. Each channel contains onboard line monitoring capabilities to detect open-circuit field wiring and short-circuit faults when used with field termination assemblies. The unit offers integrated millisecond-level Sequence of Events (SOE) timestamping, dual-redundant 20 VDC to 32 VDC power feeds, and full online hot-swapping functionality, allowing live replacement of active or hot-standby modules without process disruption.

 

Key Technical Specifications

Parameter Specification
Manufacturer & Series ICS Triplex / Rockwell Automation Trusted System
Model Number T8403
Module Type Trusted TMR 24 VDC Digital Input Module (40 Channels)
System Architecture Triple Modular Redundant (TMR) / Hardware Implemented Fault Tolerant (HIFT)
Safety Integrity Level TÜV Certified for IEC 61508 SIL 3 applications
Number of Inputs 40 discrete digital input channels
Nominal Input Voltage 24 VDC (Sink/Source depending on Field Termination Assembly)
Operating Voltage Range 20 VDC to 32 VDC
Line Diagnostics Open-circuit and short-circuit wire fault detection (configured with FTA)
Sequence of Events (SOE) Integrated 1 ms resolution timestamping per channel
Isolation 1000 V galvanically isolated channels to backplane logic
Power Dissipation 25 W maximum heat dissipation
Operating Temperature -5 °C to 60 °C (23 °F to 140 °F)
Non-Operating Temperature -25 °C to 70 °C (-13 °F to 158 °F)
Relative Humidity 5% to 95%, non-condensing
Dimensions (H × W × D) 266 mm × 31 mm × 303 mm (10.5 in × 1.2 in × 11.9 in)
Module Weight 1.15 kg (2.53 lb)

 

Detailed Product Overview

The ICS Triplex T8403 TMR 24 VDC Digital Input Module provides the discrete signal acquisition engine for the Rockwell Automation Trusted safety chassis architecture. Applied extensively across industrial safety applications—including Emergency Shutdown (ESD), Fire and Gas (F&G) logic, Burner Management Systems (BMS), and high-integrity interlock monitoring—the module translates discrete field conditions into vote-validated safety variables for the main T8110-series processors.

Internally, the T8403 employs a triplicated processing path where each input channel signal is routed independently across three Fault Containment Regions (FCR A, B, and C). Signal states are hardware-voted prior to backplane transmission to guarantee 3-2-0 degraded mode capability. If a component fault occurs within a single channel slice, the fault is isolated and flagged in diagnostic buffers while the remaining two channels maintain continuous, uncompromised signal reading.

For advanced safety telemetry, the T8403 incorporates high-speed hardware latching to record Sequence of Events (SOE) state changes with 1 ms resolution. When coupled with line-monitored Field Termination Assemblies (FTAs), the module actively measures loop current thresholds to differentiate between normal contact open/close states, field cable breaks (open circuits), and field cable crushed/shorted conditions. Front-panel LEDs provide immediate visual status for module health, active/standby mode, and individual channel logic states.

T8403

T8403

T8403

T8403

Engineering Selection Highlights

  • High-Density 40-Channel Design: Provides 40 discrete 24 VDC safety input channels in a single 31 mm rack slot, maximizing cabinet space efficiency.
  • Triple Modular Redundancy: Hardware voting across triplicated channels eliminates single points of failure and supports 3-2-0 degraded mode operations.
  • Line-Monitored Input Capabilities: Detects open-circuit wiring and short-circuit faults directly at the field loop when paired with line-monitored FTAs.
  • 1 ms SOE Timestamping: Onboard hardware timestamping provides precise event reconstruction across critical safety trips.
  • Hot-Swap & Hot-Standby Support: Live insertion and removal capabilities enable module replacement without opening field loops or stopping logic execution.
  • IEC 61508 SIL 3 Certified: Full functional safety certification for critical safety-instrumented system deployments.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
System Chassis Trusted T8100 Controller / T8300 Expander Chassis Installs into standard I/O slots across primary or expanded racks.
Termination Assembly Trusted Field Termination Assembly (FTA) Connects via multi-core cable to line-monitored or non-line-monitored 24 VDC FTAs.
Companion Processor Trusted T8110B TMR Main Processor Routes scanned digital input arrays across inter-module bus to processor memory.
Software Toolset Trusted System Toolset Configures channel attributes, line monitoring thresholds, and SOE logging parameters.
Mechanical Polarization Connector Keying Pins Requires removal of specific connector keying pins on the rear interface to match I/O slot slotting.

 

Dimensions, Mounting & Connection Notes

  • Physical Dimensions: Height 266 mm (10.5 in), Width 31 mm (1.2 in), Depth 303 mm (11.9 in).
  • Weight: 1.15 kg (2.53 lb).
  • Mounting Method: Slide-in insertion into designated I/O card slots of the Trusted chassis; latched via top and bottom ejector levers.
  • Field Wiring Connection: Multi-pin rear connector attaches to pre-fabricated cables connecting directly to external Field Termination Assemblies (FTAs).
  • Thermal Management: Requires forced-air cabinet ventilation to maintain operating temperatures within the -5 °C to 60 °C (23 °F to 140 °F) specification.

 

FAQ

What is the ICS Triplex T8403?

The ICS Triplex T8403 is a 40-channel 24 VDC digital input module designed for the Rockwell Automation Trusted Triple Modular Redundant (TMR) safety platform.

How many channels does the T8403 support?

The module features 40 discrete digital input channels operating at 24 VDC nominal.

Can the T8403 detect field wiring faults?

Yes, when used with line-monitored Field Termination Assemblies (FTAs), the T8403 actively detects open-circuit wiring and short-circuit loop faults.

What is the SOE resolution on the T8403?

The module provides hardware-level Sequence of Events (SOE) timestamping with 1 ms time resolution per channel.

Can the T8403 be hot-swapped during live operation?

Yes, the T8403 supports full online hot-swapping and hot-standby pair configurations, enabling module replacement without interrupting safety operations.

What safety level is the T8403 certified for?

The module is TÜV certified for deployment in functional safety loops up to IEC 61508 SIL 3.

 

Verification & Troubleshooting Notes

  • Front Panel Indicators: Check the module state LEDs: Green indicates healthy operational status, Amber indicates a field line fault or degraded channel status, and Red/Off indicates an internal hardware fault or power loss.
  • Channel Status LEDs: Individual channel LEDs illuminate green when the input signal is in the logic HIGH state (24 V active).
  • Line Fault Diagnostics: If a field wiring fault is reported in software, check the corresponding FTA channel for damaged wiring, loose terminal screws, or missing line-monitoring resistors.
  • Ejector Handle Verification: Ensure both top and bottom ejector handles are fully closed and seated to prevent chassis status flags and unseated backplane contacts.
  • Grounding & Shielding: Ensure field cable shields are properly clamped to the cabinet earth bar at the FTA end to prevent field noise coupling onto discrete input channels.