Description
Core Product Summary
The ICS Triplex T8431 is a Trusted TMR 24 Vdc Analog Input Module with 40 input channels for sourcing field devices. It acts as a current sink for each connected device and provides triplicated measurement paths for each analog input within the Trusted automation architecture.
The module supports 0–22 mA input current, selectable per-channel line monitoring for open-circuit and short-circuit field wiring faults, configurable thresholds, and onboard Sequence of Events reporting with 1 ms resolution. It provides 2500 V impulse-withstand opto/galvanic isolation, front-panel channel status LEDs, and hot-replacement operation through Companion Slot or SmartSlot configurations. The T8431 is TÜV certified to IEC 61508 SIL 3.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | ICS Triplex |
| Exact model | T8431 |
| Product type | Trusted TMR 24 Vdc Analog Input Module |
| Product family | ICS Triplex Trusted |
| Number of input channels | 40 |
| Input architecture | Triple Modular Redundant (TMR), one measurement path per channel per slice |
| Field device type | Sourcing field input devices |
| Module input role | Current sink |
| Input current range | 0–22 mA |
| Standard process signal | 4–20 mA |
| System supply voltage range | 20–32 Vdc |
| Isolation | 2500 V impulse-withstand opto/galvanic isolation barrier |
| Line monitoring | Selectable per channel for open-circuit and short-circuit field wiring faults |
| Thresholds | Four user-programmable thresholds plus fixed minimum and maximum thresholds |
| Sequence of Events | Onboard SOE reporting, 1 ms resolution |
| Hot replacement | Companion Slot or SmartSlot configurations |
| Front-panel indication | Per-channel input status LEDs; module health, Active/Standby, and Educated status LEDs |
| Dimensions | 266 mm H × 31 mm W × 303 mm D |
| Weight | 1.149 kg |
| Certification | TÜV certified IEC 61508 SIL 3 |
Engineering Selection Highlights
- The T8431 provides 40 TMR analog input channels, making it suitable for Trusted systems that require multiple 4–20 mA process measurements with triplicated input processing.
- It interfaces to sourcing field devices and operates as a current sink, so the field loop architecture must match this input configuration.
- The 0–22 mA input range covers the standard 4–20 mA process signal while allowing diagnostic and fault-state measurements beyond the normal operating range.
- Selectable line monitoring detects open-circuit and short-circuit field wiring faults on a per-channel basis, supporting wiring-fault identification without affecting every channel.
- The module’s four user-programmable thresholds and hysteresis allow channel states and SOE events to be configured around the specific field signal range.
- Its 1 ms SOE resolution is relevant where time-ordered input changes must be recorded in the Trusted system event log.
- Hot replacement through Companion Slot or SmartSlot configurations should be matched to the installed Trusted I/O cabling and spare-slot strategy.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Trusted system family | ICS Triplex Trusted | The T8431 is a Trusted TMR I/O module. |
| System communication | Inter-Module Bus (IMB) | The module communicates with the Trusted TMR Processor through the IMB. |
| Chassis installation | Trusted Controller Chassis or Trusted Expander Chassis | Controller Chassis I/O slots are numbered 1–8; Expander Chassis I/O slots are numbered 1–12. |
| Field connection | Field I/O Cable Assembly and FTA or VFTA | The module’s rear field connector mates with the chassis field cable assembly. |
| Field signal type | Sourcing devices; module acts as current sink | Confirm the transmitter loop configuration before wiring. |
| Standard analog range | 4–20 mA using a 250 Ω resistor on a standard FTA | The module reports field voltage as 1024 counts per volt. |
| Engineering configuration | IEC 61131 TOOLSET and Trusted System Configuration Manager | Module variables, chassis/slot definitions, thresholds, filtering, and LED modes are configured in the engineering workstation tools. |
| Redundant module operation | Companion Slot or SmartSlot configuration | Active and Standby modules coordinate through the SmartSlot link. |
| Certification | TÜV certified IEC 61508 SIL 3 | Certification applies to the T8431 as specified in the manufacturer’s product documentation. |

T8431

T8431
Dimensions, Mounting & Connection Notes
The ICS Triplex T8431 measures 266 mm high, 31 mm wide, and 303 mm deep, and weighs 1.149 kg. It installs in an I/O slot of a Trusted Controller Chassis or Trusted Expander Chassis.
Before installation, the field cable assembly must be installed and correctly located. The module is inserted with its ejector tabs fully open, pushed fully home, and secured by closing the ejectors until they lock. The module and its associated field cable are keyed to prevent insertion into the wrong position; for the T8431, keying pins 1, 4, and 5 are removed from the cable.
The module uses a rear field connector for the 40 analog input channels, field returns, and SmartSlot links. Its front panel provides per-channel input status LEDs and module status LEDs for health and operating mode. The module contains static-sensitive components, so static-handling precautions apply and the module housing should not be removed.
Detailed Product Overview
The ICS Triplex T8431 is a 40-channel Trusted TMR 24 Vdc Analog Input Module. It connects to sourcing field devices, acts as a current sink for each input, and provides triplicated analog measurement for every channel. The module is part of the Trusted I/O range and communicates with the Trusted TMR Processor through the Inter-Module Bus.
Each input channel is measured by three independent Field Interface Unit slices. Each slice contains an analog-to-digital converter for the 40 field inputs, and the resulting values are processed through the module’s TMR architecture. This arrangement isolates faults to individual slices or channels rather than allowing a single analog-path failure to affect a wider group of inputs.
The module supports an input current range of 0–22 mA. With a standard field termination assembly using a 250 Ω resistor, the 4–20 mA process range corresponds to 1–5 V at the module input. The module reports voltage in engineering units at 1024 counts per volt, allowing the application to use the value directly or scale it through the IEC 61131 TOOLSET conversion tables.
Line monitoring can be enabled independently for each channel. The module compares the measured field voltage with configurable thresholds and detects open-circuit, short-circuit, and indeterminate wiring conditions. Four user-programmable thresholds, plus fixed minimum and maximum thresholds, define the input states; hysteresis is provided through separate rising and falling threshold values.
The T8431 includes onboard Sequence of Events reporting with 1 ms resolution. When an input changes state, the module records the change with a real-time clock value. The Trusted TMR Processor retrieves this information and writes configured events into the system SOE log. Input status and line-fault status variables can be configured for automatic SOE logging.
The module is configured through the IEC 61131 TOOLSET and Trusted System Configuration Manager. Configuration includes defining I/O variables, assigning the module’s chassis and slot location, connecting variables to input channels, and setting thresholds, noise filtering, and LED indicator modes. The TMR Processor automatically configures the module after the application is downloaded and during Active/Standby changeover.
For maintenance, the T8431 supports hot replacement using a dedicated Companion Slot or a SmartSlot configuration. The front panel provides channel-level status indication as well as module health, Active/Standby, and Educated indicators, supporting fault identification and module replacement procedures.
Applications & System Role
In a Trusted automation architecture, the ICS Triplex T8431 acquires 4–20 mA analog field signals and presents triplicated input data to the Trusted TMR Processor through the Inter-Module Bus. Each of its 40 channels is processed through three independent module slices, with the resulting input state and engineering-unit value made available to the Trusted application.
The module is intended for Trusted systems that require analog process measurements with channel-level diagnostics, configurable threshold-based state detection, and time-stamped event reporting. Its line-monitoring and diagnostic functions support identification of field-wiring faults and module-channel faults within the Trusted I/O architecture.
FAQ
What is the ICS Triplex T8431?
The ICS Triplex T8431 is a Trusted TMR 24 Vdc Analog Input Module with 40 input channels for sourcing field devices.
What input signal range does the T8431 support?
It supports 0–22 mA input current and is commonly used for 4–20 mA analog process signals.
How many input channels does the T8431 provide?
It provides 40 Triple Modular Redundant analog input channels.
What type of field devices does it interface to?
It interfaces to sourcing field input devices and acts as a current sink for those devices.
Does the T8431 detect field-wiring faults?
Yes. Its selectable per-channel line monitoring detects open-circuit and short-circuit field wiring faults.
What Sequence of Events capability does it provide?
The module provides onboard SOE reporting with 1 ms resolution for configured input state changes.
Can the T8431 be replaced while the system is operating?
Yes. It can be hot-replaced online using Companion Slot or SmartSlot configurations.
What certification applies to the T8431?
The T8431 is TÜV certified to IEC 61508 SIL 3.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626