ICS Triplex T8461C Trusted CCoat TMR 24/48 Vdc 40-Channel Digital Output Module

Parameter Specification
Brand ICS Triplex
Exact model T8461C
Product type Trusted CCoat TMR 24/48 Vdc Digital Output Module
Product family ICS Triplex Trusted
Number of output channels 40
Output architecture Triple Modular Redundant (TMR)
Backplane (IMB) supply voltage 20–32 Vdc
Backplane power 26 W
Categories: , , , , SKU: T8461C Brand:

Description

Core Product Summary

The ICS Triplex T8461C is a conformal-coated Trusted TMR 24/48 Vdc Digital Output Module with 40 output channels for interfacing the Trusted automation platform to field devices. It uses a Triple Modular Redundant output architecture, with triplicated diagnostics and voltage and current measurement on each portion of the voted output channel.

The module provides automatic per-channel line monitoring for open-circuit and short-circuit field wiring or load faults, onboard Sequence of Events reporting with 1 ms resolution, 2500 V impulse-withstand opto/galvanic isolation, and automatic per-channel overcurrent protection. Its 40 outputs are powered in five isolated groups of eight channels. The T8461C supports hot replacement through Companion Slot or SmartSlot configurations and is TÜV certified to IEC 61508 SIL 3.

 

Key Technical Specifications

Parameter Specification
Brand ICS Triplex
Exact model T8461C
Product type Trusted CCoat TMR 24/48 Vdc Digital Output Module
Product family ICS Triplex Trusted
Number of output channels 40
Output architecture Triple Modular Redundant (TMR)
Backplane (IMB) supply voltage 20–32 Vdc
Backplane power 26 W
Field supply voltage 18–58 Vdc
Maximum field-supply current 30 A per module
Continuous output current 0.75 A per channel
Minimum on-state load current 25 mA
Output on-state resistance 1.6 Ω
Output off-state resistance 33 kΩ effective leakage
Maximum load capacitance 500 µF
Power groups 5 isolated groups of 8 outputs
Short-circuit protection Electronic, latching
Isolation 2500 V impulse-withstand opto/galvanic isolation barrier
Output turn-on/off delay 0.5 ms
Sample update time 0.5 ms
Sequence of Events resolution 1 ms
Self-test interval 2 minutes
Intrinsic safety External barrier required; not approved for direct hazardous-area connection
Dimensions 266 mm H × 31 mm W × 303 mm D
Weight 1.285 kg
Certification TÜV certified IEC 61508 SIL 3

 

Engineering Selection Highlights

  • The T8461C provides 40 TMR digital output channels, making it suitable for Trusted systems that require a high-density 24/48 Vdc output interface.
  • Its triplicated output structure uses three fully monitored, fail-safe switch channels per output, allowing the module to tolerate a single switch or slice failure while continuing to control the load.
  • Automatic per-channel line monitoring identifies open-circuit and short-circuit faults in field wiring or load devices, supporting fault isolation at the individual output point.
  • The module provides automatic per-channel overcurrent protection and a latching short-circuit fault state, eliminating the need for external channel fuses.
  • Outputs are divided into five isolated Power Groups of eight channels, so field supply grouping and load distribution must account for the power-group current limit.
  • The 1 ms SOE resolution is relevant where output state changes must be recorded with time-stamped event data.
  • Hot replacement through a dedicated Companion Slot or shared SmartSlot should be matched to the installed Trusted I/O cabling and spare-module strategy.
  • The module is not approved for direct connection to hazardous areas; intrinsic-safety barrier devices are required for such applications.
T8461C

T8461C

T8461C

T8461C

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Trusted system family ICS Triplex Trusted The T8461C is a Trusted TMR I/O module.
System communication Inter-Module Bus (IMB) The module communicates with the Trusted TMR Processor through the IMB.
Chassis installation Trusted Controller Chassis or Trusted Expander Chassis Controller Chassis I/O slots are numbered 1–8; Expander Chassis I/O slots are numbered 1–12.
Field connection Field I/O Cable Assembly and FTA or VFTA The module’s rear field connector connects to the chassis field cable assembly.
Field supply 18–58 Vdc The module monitors the external field I/O supply voltage.
Output grouping Five isolated Power Groups of eight outputs Each group has an isolated supply and return connection.
Engineering configuration IEC 61131 TOOLSET and Trusted System Configuration Manager I/O variables, chassis/slot location, LED modes, default/fail-safe states, and SOE settings are configured in the engineering tools.
Spare-module operation Companion Slot or SmartSlot configuration Active and Standby modules coordinate through the SmartSlot link during replacement.
Hazardous-area use External intrinsic-safety barriers required The module is not approved for direct hazardous-area connection.

 

Dimensions, Mounting & Connection Notes

The ICS Triplex T8461C measures 266 mm high, 31 mm wide, and 303 mm deep, and weighs 1.285 kg. It installs in an I/O slot of a Trusted Controller Chassis or Trusted Expander Chassis.

Before installation, confirm that the field cable assembly is installed and correctly located, then verify that module and cable keying match. For the T8461 module type, keying pins 1, 5, and 7 are removed from the associated field cable. Insert the module with its ejector tabs fully open, seat it fully in the slot, and close the ejectors until they lock. The module should insert with minimal resistance; do not force it if pins are bent or damaged.

The module contains static-sensitive components. Avoid touching exposed connector pins and do not remove the module housing. Its rear field connector carries the 40 output channels, five isolated power-group supplies and returns, and SmartSlot link connections. The front panel provides per-channel output status LEDs, module health LEDs, Active/Standby indication, and Educated status indication.

 

Detailed Product Overview

The ICS Triplex T8461C is a conformal-coated version of the Trusted TMR 24/48 Vdc Digital Output Module. It is a member of the Trusted I/O range and provides the interface between the Trusted TMR Processor and 24/48 Vdc field devices. The module communicates through the Inter-Module Bus and receives system power through the Trusted chassis backplane.

Each of the 40 output channels is implemented with a TMR switch topology. The load is driven by three fully monitored, fail-safe switch channels, with one channel physically resident in each of the module’s three Field Interface Unit slices. A single switch or an entire slice failure is designed to leave two of the three fail-safe switch channels operational, allowing the load to continue to be controlled.

The module performs extensive automatic diagnostics. It measures output voltage and current on each portion of the voted output channel, performs tests for stuck-on and stuck-off failures, and monitors onboard power supplies, reference voltages, current consumption, and board temperature. The TMR Processor periodically commands a Safety Layer Test, and the module uses CRC checks to verify variables and configuration stored in Flash memory.

Automatic line monitoring is provided for each output point. The module determines the output state from measured voltage and current and reports states including output energized, output de-energized, no field supply voltage, field open circuit, and field short circuit. Unused outputs should be commanded off and wired through a 10 kΩ, 0.5 W resistor to zero volts to avoid a no-load fault indication.

The T8461C provides onboard Sequence of Events reporting with 1 ms resolution. An output change of state creates an SOE entry, with the channel state and real-time clock value retrieved by the TMR Processor and written to the system SOE log when configured. Output voltage is reported in units of 1/500 V, while output current is reported in units of 1/1000 A.

Outputs are powered in five isolated Power Groups, each containing eight channels. Each channel provides automatic overcurrent protection, and a sustained overcurrent condition latches a short-circuit fault state and de-energizes the output. A non-replaceable fusible link provides absolute protection. Group Fail-Safe Switches provide a final means of de-energizing all outputs in a Power Group when two or more module faults prevent normal de-energization.

The module is configured through the IEC 61131 TOOLSET and Trusted System Configuration Manager. Configuration includes defining I/O variables, assigning the module’s chassis and slot location, connecting variables to output channels, and setting LED indicator modes, per-channel default or fail-safe states, and SOE behavior. The TMR Processor automatically configures the module after application download and during Active/Standby changeover.

 

Applications & System Role

Within a Trusted automation architecture, the ICS Triplex T8461C converts Trusted controller commands into 24/48 Vdc digital outputs for field devices. It provides 40 triplicated output channels and communicates with the Trusted TMR Processor through the Inter-Module Bus.

The module is intended for applications requiring digital output control with integrated diagnostics, line monitoring, fault containment, and time-stamped event reporting. Its isolated power groups and fail-safe switch structure support output-channel protection and controlled de-energization within the Trusted I/O architecture.

 

FAQ

What is the ICS Triplex T8461C?
The ICS Triplex T8461C is a conformal-coated Trusted TMR 24/48 Vdc Digital Output Module with 40 output channels for ICS Triplex Trusted automation systems.

How many output channels does the T8461C provide?
It provides 40 Triple Modular Redundant digital output channels.

What output voltage does the T8461C support?
It supports 24/48 Vdc field outputs, with an operational field supply voltage range of 18–58 Vdc.

What is the output current rating?
Each channel is rated for 0.75 A continuous output current.

Does the T8461C detect field-wiring faults?
Yes. It provides automatic per-channel line monitoring for open-circuit and short-circuit faults in field wiring or load devices.

Does the module require external fuses?
No. It provides automatic per-channel overcurrent protection, although it also includes a non-replaceable fusible link for absolute protection.

What Sequence of Events resolution does it provide?
The T8461C provides onboard SOE reporting with 1 ms resolution.

Can the T8461C be connected directly to hazardous areas?
No. The module is not approved for direct hazardous-area connection and should be used with intrinsic-safety barrier devices.