The ICS Triplex T8480 is a Trusted TMR 4-20 mA analog output module providing 40 fault-tolerant output channels for the Rockwell Automation (ICS Triplex) Trusted Triple Modular Redundant safety platform. Each field output is driven through three fully monitored, fail-safe (6-element) driver channels — one driver stage resident on each of the module’s three slices — so the failure of any single driver or an entire slice still leaves two driver channels able to supply the commanded, regulated current to the load.

Categories: , , , , SKU: T8480 Brand:

Description

Core Product Summary

The ICS Triplex T8480 is a Trusted TMR 4-20 mA analog output module providing 40 fault-tolerant output channels for the Rockwell Automation (ICS Triplex) Trusted Triple Modular Redundant safety platform. Each field output is driven through three fully monitored, fail-safe (6-element) driver channels — one driver stage resident on each of the module’s three slices — so the failure of any single driver or an entire slice still leaves two driver channels able to supply the commanded, regulated current to the load.

Every channel is a closed current loop: the measured output current is compared against the commanded value and against the current reported by each independent slice, and the surviving slices compensate automatically if a discrepant slice is removed from service. Automatic per-channel line monitoring detects open circuits and loss of field loop power, outputs are powered in isolated groups of eight (Power Groups) with Group Fail-Safe Switches, and onboard Sequence of Events reporting resolves output state changes to 1 ms. The module supports online hot replacement via Companion Slot or SmartSlot configurations and is TÜV certified for non-interfering applications. It is not approved for direct connection to hazardous areas and must be used with Intrinsic Safety Barrier devices.

 

Key Technical Specifications

Parameter Value
Product type Trusted TMR 4-20 mA analog output module, 40 channel
Redundancy architecture Triple Modular Redundant (TMR), three slices (A, B, C) per module
Output channels 40 TMR analog output channels per module
Output signal 4-20 mA regulated current output per channel
Output driver structure Three fully monitored, fail-safe (6-element) driver channels per load, one per FIU slice
Current regulation Closed-loop control with ADC feedback and pulse-ratio-modulated gate drive (FPGA-based control logic)
Diagnostics Triplicated tests of current and voltage on each portion of the voted output channel; stuck-on and stuck-off testing; Safety Layer Test (SLT) and CRC verification of Flash-stored configuration
Line monitoring Automatic per channel; detects open circuit and loss of field loop power
Short-circuit behavior Not treated as a channel fault; the module is designed to drive 20 mA indefinitely into 0 Ω
Overcurrent protection Automatic, per channel; no external fuses required
Field supply grouping Outputs powered in isolated groups of eight (Power Groups) with Group Fail-Safe Switches (GFSS)
Isolation 2500 V impulse withstand opto/galvanic isolation barrier
Sequence of Events Onboard SOE reporting, 1 ms event resolution
Safety certification TÜV certified for non-interfering applications (see Trusted safety manual T8094)
Hazardous area use Not approved for direct connection; must be used with Intrinsic Safety Barrier devices
Online replacement Hot-replace via dedicated Companion (adjacent) Slot or SmartSlot
Front panel indication Per-channel output status LEDs; module status LEDs (Active, Standby, Educated, Slice Healthy)
Module construction Host Interface Unit (HIU), Field Interface Unit (FIU), Field Termination Unit (FTU), Front Panel Unit (FPU)

 

Detailed Product Overview

The T8480 occupies a specific role in a Trusted system: it is the analog path out of the safety controller, delivering commanded 4-20 mA currents to field loads. Its defining engineering problem differs from that of a digital output. A digital output must guarantee that a load can be dropped; an analog output must guarantee that the load receives exactly the commanded current even while faults develop inside the module. The T8480 addresses this with a TMR driver topology in which each load is driven by three fully monitored, fail-safe driver channels, one physically resident on each Field Interface Unit slice. Any single driver or entire slice failure leaves two of the three channels able to carry the load.

Current regulation is closed-loop at the channel level. A sense resistor feeds each slice’s ADC measurement of the actual output current, and FPGA control logic applies a pulse-ratio-modulated drive to the regulating FET to hold the loop at the commanded value. The integrity check is comparative: the measured channel current is continuously compared with the commanded current and with the current reported by each of the other slices. If a discrepancy exceeds what the control loop’s authority can overcome — in current or in the load voltage measured by each slice — the discrepant slice is disabled and the survivors compensate to maintain the commanded current without interruption.

The module’s stance on short circuits is a deliberate design decision worth noting during integration: because a 4-20 mA current loop into a short simply presents zero load resistance, a short circuit is not treated as a channel fault. The module is designed to drive 20 mA indefinitely into 0 Ω, and channel voltages are made available to the application so that a short can be inferred there if the engineering design requires it. What the module does flag per channel is an open circuit or loss of field loop power, each reported as a distinct line fault state alongside the numerical output state (energized, de-energized, no-load/open circuit, no field supply voltage). Unused outputs should be commanded off in the application and wired through a 10 kΩ 0.5 W resistor to zero volts so the drawn current exceeds the NO-LOAD threshold and prevents nuisance NO-LOAD faults.

Fail-safe behavior is organized around Power Groups. The 40 outputs are powered in isolated groups of eight, each group fed through a Group Fail-Safe Switch built from three parallel elements, one per slice. Any slice that observes an output failing to de-energize can command its own and the neighboring slices’ GFSS elements, and two or more faults within the module cause the Group Fail-Safe Switches to de-energize the entire group. The GFSS bias is generated by a charge pump driven from the slice comms clock, so a clock failure, a lost slice communication, or a watchdog timeout all collapse the bias and de-energize the group — a defense that does not depend on the module’s own logic remaining healthy.

T8480

T8480

T8480

T8480

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Host system Trusted TMR system; module communicates with the Trusted TMR Processor across the Inter-Module Bus (IMB) The IMB provides power; the HIU redundantly shares the dual 24 Vdc chassis supply
Field cabling Trusted I/O Companion Slot cables (ICSTT-RM311) or Trusted TMR I/O SmartSlot cables (ICSTT-RM313) The same publications detail the FTA / VFTA types usable with this module
Field termination Field Termination Assembly (FTA) or Versatile FTA (VFTA) Custom multi-core FTA cables: 0.5 mm², 40 Ω/km (50 m ≈ 4 Ω loop, ≈ 2 Vdc drop at 0.5 A)
Field supply wiring Power Group positive and return per group of eight outputs, per the field connector pinout Short-circuit status is not reported as a line fault; channel voltages are available to the application for fault inference
Module replacement topology Dedicated Companion (adjacent) Slot or SmartSlot (one spare slot for many modules) SmartSlot link coordinates Active/Standby changeover during online hot replacement
Configuration No configuration is performed on the physical module; all configurable characteristics are set with engineering workstation tools and loaded into the TMR Processor as part of the application or System.INI file The TMR Processor automatically configures the Output Module after application download and during Active/Standby changeover; the IEC 61131 TOOLSET provides the main configuration interface
SOE configuration Each output can be included in the system SOE log Full details in the Trusted Sequence of Events and Process Historian Package description (ICSTT-RM243)
Hazardous area integration Not approved for direct connection to hazardous areas Must be used with Intrinsic Safety Barrier devices
Safety documentation Trusted TMR Safety Manual T8094 TÜV certification applies to non-interfering applications; consult the safety manual for application constraints
Cable keying For this module (T8480), remove keying pins 1, 6, and 7 from the cable to match the module’s keyed bungs Both keying strips must be polarized for Companion Slot cable installations

 

Dimensions, Mounting & Connection Notes

Before installation, visually inspect the module housing for damage and check the rear I/O connector for bent pins. A damaged module or one with bent pins must not be installed, and bent pins must not be straightened — return the module for replacement. The module contains static-sensitive parts: observe static-handling precautions, never touch exposed connector pins, and never remove the module housing. Record the module type, revision, and serial number before installation.

Installation sequence: confirm the field cable assembly is installed and correctly located; verify that any I/O module keys are seated correctly in their slots; release the ejector tabs with the release key until fully open; insert the module holding the ejectors; press it fully home at the top and bottom of the fascia; then close the ejectors until they click into their locked position. The module should seat with minimal resistance — never force it into the chassis.

Field connections are made through the FTU field connector, which mates with the Field I/O Cable Assembly at the rear of the Trusted Controller or Expander Chassis. The pin-out carries the 40 channel positive outputs arranged in five Power Groups of eight, each with its own group positive and return, plus the three SmartSlot link contacts. All Trusted modules are keyed at manufacture to prevent insertion into the wrong chassis position; the integrator keys the cable by removing keying pieces to match the module. During operation, all three front-panel Healthy indicators should be green; a flashing red Healthy indicator signals a fault that should be investigated, and if the cause is within the module it should be replaced through the configured Companion Slot or SmartSlot arrangement.

 

FAQ

What is the ICS Triplex T8480?
The T8480 is a Trusted TMR 4-20 mA analog output module with 40 Triple Modular Redundant output channels, part of the Trusted I/O module range for the Trusted TMR safety platform.

What does the T8480 do?
It delivers commanded 4-20 mA regulated currents to up to 40 field loads, driving each load through three monitored fail-safe driver channels with closed-loop current control, automatic diagnostics, per-channel line monitoring, and Group Fail-Safe Switches per group of eight outputs.

How does the T8480 keep the output current correct after a fault?
Each slice continuously compares its measured channel current and load voltage with the other slices. If a slice reports a discrepancy beyond the control loop’s authority, that slice is disabled and the surviving slices compensate to maintain the commanded current without interruption.

Does the T8480 treat a short circuit as a fault?
No. Short circuits are not treated as a fault condition for this analog current output; the module is designed to drive 20 mA indefinitely into 0 Ω. Channel voltages are provided to the application so a short can be detected at the application level if required.

Does the T8480 need external fuses?
No. Each channel has automatic overcurrent protection, so external fuses are not required.

What line faults does the T8480 report?
Per-channel line monitoring reports an open circuit or loss of field loop power, each with a distinct state reported to the application alongside the numerical output state (energized, de-energized, no load/open circuit, no field supply voltage).

Can the T8480 be replaced while the system is running?
Yes. The module supports online hot replacement using a dedicated Companion (adjacent) Slot or a SmartSlot, with the SmartSlot link coordinating the Active/Standby changeover.

How should unused outputs be handled?
Command them off in the application and wire each through a 10 kΩ 0.5 W resistor to zero volts so the drawn current exceeds the NO-LOAD threshold and prevents NO-LOAD fault signaling.

Can the T8480 be connected directly to a hazardous area?
No. The module is not approved for direct connection to hazardous areas and must be used in conjunction with Intrinsic Safety Barrier devices.

 

Documented Performance Data

Metric Value Condition
Sequence of Events event resolution 1 ms Onboard SOE reporting; output state changes timestamped by the module’s onboard timer
Output state determination Automatic onboard voltage and current measurement per channel Reported states: output energized, no-load/open circuit, output de-energized, no field supply voltage
Short-circuit drive capability 20 mA driven indefinitely into 0 Ω By design; not treated as a channel fault
Current regulation method Closed loop with ADC feedback and pulse-ratio-modulated gate drive FPGA-based control logic per channel, triplicated across slices
Isolated serial link rate 6.25 Mbit/sec Between each FIU slice and its HIU slice
FTA cable loop impedance 0.5 mm² conductor, 40 Ω/km A 50 m custom multi-core FTA cable ≈ 4 Ω loop, ≈ 2 Vdc drop at 0.5 A
Isolation barrier impulse withstand 2500 V Opto/galvanic isolation barrier