Sale!

ICS Triplex T9100 AADvance Processor Base Unit

Parameter Specification
Brand ICS Triplex
Exact model T9100
Product type AADvance Processor Base Unit
Product family Rockwell Automation AADvance / ICS Triplex
Function Processor backplane for an AADvance controller
Supported processor modules Up to three T9110 Processor Modules
Backplane supply voltage 18–32 Vdc
Backplane current rating 10.4 A total

Description

Core Product Summary

The ICS Triplex T9100 is an AADvance Processor Base Unit, also described as a processor backplane, for the AADvance controller platform. It provides the physical and electrical foundation that holds the processor modules used by an AADvance safety controller.

The T9100 supports up to three T9110 Processor Modules and provides external Ethernet, serial-data, and power connections. Its backplane operates from an 18–32 Vdc supply, with a total backplane rating of 10.4 A and 400 mA available per slot. In an AADvance architecture, the T9100 supports SIL 2 applications with two processor modules fitted, and SIL 3 applications with two or three processor modules fitted.

 

Key Technical Specifications

Parameter Specification
Brand ICS Triplex
Exact model T9100
Product type AADvance Processor Base Unit
Product family Rockwell Automation AADvance / ICS Triplex
Function Processor backplane for an AADvance controller
Supported processor modules Up to three T9110 Processor Modules
Backplane supply voltage 18–32 Vdc
Backplane current rating 10.4 A total
Per-slot current rating 400 mA
Supported safety configurations SIL 2 with two processor modules; SIL 3 with two or three processor modules
External connections Ethernet, serial data, and power
System communication Proprietary internal protocol over a custom wired harness
External protocol support TCP and UDP services including MODBUS, CIP, IXL, Telnet, and SNTP
Controller I/O capacity Up to 48 I/O modules, using 8- or 16-channel modules
Sequence of Events resolution 1 ms for processor-module internal variables
Certification IEC 61508 SIL 2 and SIL 3, depending on processor and I/O configuration

 

Engineering Selection Highlights

  • The T9100 is the processor base unit for an AADvance controller, so it should be selected as the mounting and backplane hardware for T9110 Processor Modules.
  • Its support for up to three processor modules allows simplex, dual, or triple processor configurations within the AADvance architecture.
  • A minimum of two T9110 processor modules is required for AADvance safety applications; two modules support SIL 2, while two or three modules support SIL 3 configurations.
  • The 18–32 Vdc backplane supply range and 10.4 A total backplane rating should be used when sizing the controller power supply and power distribution arrangement.
  • The base unit provides external Ethernet, serial-data, and power connections, allowing the processor section to interface with networks, workstations, and controller power sources.
  • The T9100 is part of an AADvance system that supports up to 48 I/O modules using 8- or 16-channel modules, so I/O capacity planning should include the associated T9300 I/O base units and modules.
  • The platform’s 1 ms Sequence of Events resolution for processor internal variables is relevant where time-ordered internal event data is required.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
AADvance controller family Rockwell Automation AADvance / ICS Triplex The T9100 is the processor base unit for this controller family.
Processor modules T9110 Processor Module The base unit supports one to three T9110 processor modules.
Safety configuration Two processor modules for SIL 2; two or three processor modules for SIL 3 Processor quantity must match the required safety architecture.
I/O base unit T9300 I/O Base Unit The T9300 hosts the AADvance I/O modules in the controller architecture.
I/O modules Up to 48 I/O modules, 8- or 16-channel types I/O capacity depends on the selected AADvance system architecture.
Backplane power 18–32 Vdc, 10.4 A total, 400 mA per slot Power supply sizing must account for the complete controller configuration.
Network integration Ethernet, TCP, UDP, MODBUS, CIP, IXL, Telnet, and SNTP Confirm protocol and network requirements for the connected systems.
Engineering software AADvance Workbench or AADvance-Trusted SIS Workstation Configuration and application development use the applicable AADvance software environment.

 

Detailed Product Overview

The ICS Triplex T9100 is the AADvance Processor Base Unit for the AADvance controller platform. It is the backplane assembly that holds the processor modules in an AADvance controller and provides the electrical and physical foundation for the controller’s processing section.

The T9100 supports up to three T9110 Processor Modules. This allows an AADvance controller to be configured with one processor module for non-safety or critical-control use, or with two or three processor modules for safety-related architectures. In AADvance safety applications, a minimum of two processor modules is required: two modules support SIL 2 applications, while two or three modules support SIL 3 applications.

The base unit provides external Ethernet, serial-data, and power connections. Internally, the processor modules and I/O modules communicate using a proprietary protocol over a custom wired harness. Externally, the AADvance platform supports transport-layer services including TCP and UDP for MODBUS, CIP, IXL, Telnet, and SNTP.

The T9100 backplane operates from an 18–32 Vdc supply. Its electrical rating is 10.4 A total, with 400 mA available per slot. These ratings should be considered when specifying the controller power supply, power distribution, and enclosure heat dissipation.

The T9100 is part of an AADvance controller architecture that can support up to 48 I/O modules using 8- or 16-channel modules. The associated T9300 I/O Base Unit hosts the I/O modules, while termination assemblies provide the field-wiring interface. The processor and I/O architecture can be configured for fail-safe, fault-tolerant, or triple-modular-redundant arrangements according to the application requirements.

The AADvance platform is developed for IEC 61131 compliance and is certified for safety systems up to SIL 3, depending on the processor and I/O module configuration. The T9100 therefore forms the processor-side foundation for AADvance controllers used in emergency shutdown, fire and gas protection, burner management, critical process control, and distributed monitoring and control applications.

T9100

T9100

T9100

T9100

Applications & System Role

In an AADvance automation architecture, the ICS Triplex T9100 serves as the processor base unit that houses and interconnects the controller’s processor modules. It provides the backplane over which the processor modules communicate with the rest of the AADvance controller and provides the external Ethernet, serial, and power connections required by the processor section.

The T9100 is relevant for AADvance controllers used in functional-safety and critical-control applications. Its supported processor configurations allow the controller architecture to be arranged for SIL 2 or SIL 3 safety applications, depending on the number of processor modules and the selected I/O configuration.

 

FAQ

What is the ICS Triplex T9100?
The ICS Triplex T9100 is an AADvance Processor Base Unit, or processor backplane, for the AADvance controller platform.

How many processor modules does the T9100 support?
It supports up to three T9110 Processor Modules.

Which safety configurations does the T9100 support?
It supports SIL 2 applications with two processor modules fitted and SIL 3 applications with two or three processor modules fitted.

What is the backplane supply voltage range?
The T9100 backplane operates from an 18–32 Vdc supply.

What is the backplane current rating?
The backplane is rated for 10.4 A total, with 400 mA available per slot.

Which external connections does the T9100 provide?
It provides external Ethernet, serial-data, and power connections.

How many I/O modules can an AADvance controller support?
An AADvance system can support up to 48 I/O modules using 8- or 16-channel modules.

Which software is used to configure an AADvance controller?
Configuration and application development use AADvance Workbench or AADvance-Trusted SIS Workstation software, depending on the system configuration.