Description
Core Product Summary
The ICS Triplex T9402 is a 16-channel, 24 Vdc isolated Digital Input Module for the Rockwell Automation AADvance controller platform. It interfaces digital field devices to an AADvance controller and transmits input status and measured input-voltage data to the processor modules.
The T9402 provides configurable line monitoring and on-site fault detection through five configurable voltage bands and eight switching thresholds per channel. It supports 1 ms event resolution, front-panel module and channel status LEDs, redundant 18–32 Vdc power, and channel isolation rated at ±1.5 kVdc withstand. The module can be used in simplex, dual, or triple I/O architectures and supports IEC 61508 SIL 3 depending on the controller configuration.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | ICS Triplex |
| Exact model | T9402 |
| Product type | AADvance Digital Input Module |
| Product family | Rockwell Automation AADvance / ICS Triplex |
| Number of input channels | 16 |
| Input type | Digital input, isolated |
| Nominal supply voltage | 24 Vdc |
| Supply voltage range | 18–32 Vdc |
| Module power consumption | 2.2 W |
| Module heat dissipation | 2.2 W |
| Channel power consumption | 0.11 W |
| Input voltage measurement accuracy | ±0.5 V |
| Safety accuracy limit | 1% |
| Channel isolation | ±1.5 kVdc withstand for 1 minute, channel to channel and channel to chassis |
| Line monitoring | Five configurable voltage bands and eight switching thresholds per channel |
| Sampling update interval without filter | 5 ms |
| Event resolution | 1 ms |
| Timestamp accuracy | 5 ms |
| Scan time | 0.924 ms simplex, 1.676 ms dual, 2.453 ms triple |
| Degradation modes | 1oo1D, 1oo2D, 2oo3D |
| Enclosure | Plastic, non-flammable |
| Dimensions | 166 mm H × 42 mm W × 118 mm D |
| Weight | 340 g |
| Certification | IEC 61508 SIL 3, depending on processor and I/O module configuration |
Engineering Selection Highlights
- The T9402 provides 16 isolated 24 Vdc digital input channels, making it suitable for AADvance controllers that require a compact digital-input interface.
- Its isolated channel design supports channel-to-channel and channel-to-chassis isolation rated at ±1.5 kVdc withstand.
- Configurable line monitoring uses five voltage bands and eight switching thresholds per channel, allowing field-wiring and device-condition diagnostics to be tailored to the application.
- The module supports 1 ms event resolution and 5 ms timestamp accuracy, which is relevant for applications requiring time-ordered digital input events.
- The T9402 can be applied in simplex, dual, or triple I/O architectures, with corresponding scan times of 0.924 ms, 1.676 ms, and 2.453 ms.
- Redundant 18–32 Vdc power operation should be matched to the AADvance controller power distribution design.
- The module is configured through AADvance Workbench, including line-monitoring parameters and channel behavior.

T9402

T9402
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| AADvance controller family | Rockwell Automation AADvance / ICS Triplex | The T9402 is an AADvance I/O module. |
| Controller architecture | AADvance processor and I/O base units | The module operates within the AADvance controller architecture. |
| I/O architecture | Simplex, dual, or triple configurations | The selected architecture determines the module scan time and fault-tolerance arrangement. |
| Power supply | Redundant 24 Vdc nominal, 18–32 Vdc range | The module requires power from the AADvance controller power system. |
| Engineering software | AADvance Workbench | Module parameters, including line monitoring, are configured in AADvance Workbench. |
| Event handling | 1 ms event resolution and 5 ms timestamp accuracy | Suitable for AADvance Sequence of Events applications. |
| Safety certification | IEC 61508 SIL 3 | Certification depends on the processor and I/O module configuration. |
Dimensions, Mounting & Connection Notes
The ICS Triplex T9402 measures 166 mm high, 42 mm wide, and 118 mm deep, and weighs 340 g. It uses a non-flammable plastic enclosure and is installed in the AADvance I/O base unit.
The module provides 16 isolated 24 Vdc digital input channels. It receives redundant 24 Vdc power from the AADvance controller power system and provides front-panel LEDs for module status and channel status. The module is configured through AADvance Workbench.
Detailed Product Overview
The ICS Triplex T9402 is a 16-channel, 24 Vdc isolated Digital Input Module for the AADvance controller platform. It interfaces digital field devices to the AADvance controller and provides the processor modules with both digital status information and measured input-voltage data.
Each input channel is isolated from other channels and from the chassis, with a maximum withstand rating of ±1.5 kVdc for one minute. The module operates from redundant 24 Vdc nominal power over an 18–32 Vdc range. It consumes 2.2 W and dissipates 2.2 W, with each channel consuming 0.11 W.
The T9402 supports configurable line monitoring and on-site fault detection. Each channel provides five configurable voltage bands and eight switching thresholds, allowing hysteresis to be applied to the input detection thresholds. This capability supports detection of field-loop and field-device conditions beyond a simple on/off status.
The module provides a 5 ms sampling update interval without filtering, 1 ms event resolution, and 5 ms timestamp accuracy. These characteristics support Sequence of Events applications where the order and timing of digital input changes are important.
The T9402 can be used in simplex, dual, or triple I/O architectures. Its typical module scan time is 0.924 ms in a simplex configuration, 1.676 ms in a dual configuration, and 2.453 ms in a triple configuration. These scan times are module-level values and do not include the effects of application logic or communications loading.
The module is configured using AADvance Workbench. Front-panel LEDs provide local indication of module and channel status, supporting installation checks, commissioning, and troubleshooting.
Applications & System Role
Within an AADvance automation architecture, the ICS Triplex T9402 acquires digital field signals and presents them to the AADvance processor modules. It monitors field-device status and channel conditions, measures input voltage, and provides diagnostic information for field wiring and field devices.
The module is relevant for AADvance controllers used in functional-safety and critical-control applications that require digital inputs with configurable line monitoring, isolated channels, and time-stamped event reporting. Its support for simplex, dual, and triple architectures allows it to be used in fail-safe or fault-tolerant AADvance system designs.
FAQ
What is the ICS Triplex T9402?
The ICS Triplex T9402 is a 16-channel, 24 Vdc isolated Digital Input Module for the AADvance controller platform.
How many input channels does the T9402 provide?
It provides 16 isolated digital input channels.
What supply voltage does the T9402 require?
It uses redundant 24 Vdc nominal power and operates over an 18–32 Vdc range.
Does the T9402 support line monitoring?
Yes. Each channel supports five configurable voltage bands and eight switching thresholds for line monitoring and on-site fault detection.
What event resolution does the T9402 provide?
It provides 1 ms event resolution and 5 ms timestamp accuracy.
Can the T9402 be used in redundant I/O architectures?
Yes. It can be used in simplex, dual, or triple AADvance I/O architectures.
What is the module’s channel isolation rating?
Channel-to-channel and channel-to-chassis isolation is rated at ±1.5 kVdc withstand for one minute.
Which software is used to configure the T9402?
The module is configured using AADvance Workbench.

WhatsApp: +86 16626708626