Sale!

ICS Triplex T9482 AADvance 8-Channel Isolated Analog Output Module

Parameter Specification
Brand ICS Triplex
Exact model T9482
Product type AADvance Analog Output Module
Product family Rockwell Automation AADvance / ICS Triplex
Number of output channels 8
Output type Analog output, isolated
Nominal supply voltage 24 Vdc
Supply voltage range 18–32 Vdc
Output signal 4–20 mA
Categories: , , , , SKU: T9482 Brand:

Description

Core Product Summary

The ICS Triplex T9482 is an 8-channel, 24 Vdc isolated Analog Output Module for the Rockwell Automation AADvance controller platform. It converts controller output values into 4–20 mA signals for compatible field devices and provides the analog-output interface between the AADvance controller and the process.

The T9482 operates from redundant 24 Vdc nominal power over an 18–32 Vdc range. It supports simplex and dual I/O architectures, with typical module scan times of 0.981 ms and 1.761 ms respectively. The module is used with the AADvance analogue output termination assemblies and is suitable for AADvance controller configurations certified to IEC 61508 SIL 3, depending on the processor and I/O module configuration.

 

Key Technical Specifications

Parameter Specification
Brand ICS Triplex
Exact model T9482
Product type AADvance Analog Output Module
Product family Rockwell Automation AADvance / ICS Triplex
Number of output channels 8
Output type Analog output, isolated
Nominal supply voltage 24 Vdc
Supply voltage range 18–32 Vdc
Output signal 4–20 mA
I/O architectures Simplex and dual
Typical module scan time, simplex 0.981 ms
Typical module scan time, dual 1.761 ms
Channel isolation Channel-to-channel and channel-to-chassis isolation, ±1.5 kVdc withstand for 1 minute
Enclosure Plastic, non-flammable
Certification IEC 61508 SIL 3, depending on processor and I/O module configuration

 

Engineering Selection Highlights

  • The T9482 provides eight isolated 4–20 mA analog output channels, making it suitable for AADvance controllers that require analog control outputs to field devices.
  • Its isolated output design supports channel-to-channel and channel-to-chassis isolation rated at ±1.5 kVdc withstand for one minute.
  • The module supports simplex and dual I/O architectures, allowing selection between a basic output arrangement and a fault-tolerant output arrangement.
  • The T9482 operates from redundant 24 Vdc nominal power over an 18–32 Vdc range, so controller power distribution must be designed for the AADvance system supply requirements.
  • The module is used with the AADvance analogue output termination assemblies, which provide the field-wiring interface for the output channels.
  • In SIL 3 high-demand applications where the required safe state is greater than 4 mA, the AADvance platform requires dual analog output modules.
  • The module’s typical scan times of 0.981 ms for simplex and 1.761 ms for dual configurations are module-level values and do not include application logic or communications loading.
T9482

T9482

T9482

T9482

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
AADvance controller family Rockwell Automation AADvance / ICS Triplex The T9482 is an AADvance I/O module.
Controller architecture AADvance processor and I/O base units The module operates within the AADvance controller architecture.
I/O architecture Simplex or dual configurations The selected architecture determines the module scan time and fault-tolerance arrangement.
Field interface AADvance analogue output termination assembly The termination assembly provides the field-wiring interface for the module.
Power supply Redundant 24 Vdc nominal, 18–32 Vdc range The module requires power from the AADvance controller power system.
Safety configuration IEC 61508 SIL 3 Certification depends on the processor and I/O module configuration.
SIL 3 high-demand use Dual analog output modules required when the safe state is greater than 4 mA Confirm the required safe-state value before selecting a single or dual module arrangement.

 

Dimensions, Mounting & Connection Notes

The ICS Triplex T9482 is an AADvance plug-in I/O module with a non-flammable plastic enclosure. It installs in the AADvance I/O base unit and connects to the field through the applicable AADvance analogue output termination assembly.

The module provides eight isolated 4–20 mA output channels. It receives redundant 24 Vdc nominal power from the AADvance controller power system. The AADvance documentation provides the recommended circuit for analog outputs and notes that all channels are isolated from each other, although channels may be bridged at the positive terminal when fed by a common system-mounted supply.

 

Detailed Product Overview

The ICS Triplex T9482 is an 8-channel isolated Analog Output Module for the AADvance controller platform. It is part of the AADvance I/O range and provides the interface between the AADvance processor modules and analog field devices.

The module produces 4–20 mA output signals for field devices. Its eight channels are isolated from one another and from the chassis, with a maximum withstand rating of ±1.5 kVdc for one minute. The module operates from redundant 24 Vdc nominal power over an 18–32 Vdc range.

The T9482 supports simplex and dual I/O architectures. In a simplex configuration, its typical module scan time is 0.981 ms; in a dual configuration, it is 1.761 ms. These values are module-level scan times and exclude the effects of application logic and network communications loading.

The module connects to field devices through the AADvance analogue output termination assembly. The AADvance system documentation provides a recommended circuit for analog outputs and notes that channels may be bridged at the positive terminal when they are fed by a common system-mounted supply.

The T9482 is suitable for AADvance controller configurations certified to IEC 61508 SIL 3, depending on the processor and I/O module configuration. For SIL 3 high-demand applications where the required safe state is greater than 4 mA, the AADvance platform requires dual analog output modules.

 

Applications & System Role

Within an AADvance automation architecture, the ICS Triplex T9482 converts controller output commands into 4–20 mA analog signals for field devices. It provides the analog-output interface between the AADvance processor modules and process equipment.

The module is relevant for AADvance controllers used in functional-safety and critical-control applications that require analog outputs with isolated channels and support for simplex or dual I/O architectures. It can be used in AADvance systems configured for emergency shutdown, fire and gas protection, critical process control, burner management, boiler and furnace control, and distributed process monitoring and control.

 

FAQ

What is the ICS Triplex T9482?
The ICS Triplex T9482 is an 8-channel, 24 Vdc isolated Analog Output Module for the AADvance controller platform.

How many output channels does the T9482 provide?
It provides eight isolated analog output channels.

What output signal does the T9482 produce?
It produces 4–20 mA analog output signals.

What supply voltage does the T9482 require?
It uses redundant 24 Vdc nominal power and operates over an 18–32 Vdc range.

Can the T9482 be used in redundant I/O architectures?
Yes. It supports simplex and dual AADvance I/O architectures.

What are the module scan times?
The typical module scan time is 0.981 ms in simplex configuration and 1.761 ms in dual configuration.

Which termination assembly is used with the T9482?
It is used with the AADvance analogue output termination assembly.

Does the T9482 support SIL 3 applications?
Yes, depending on the processor and I/O module configuration. For SIL 3 high-demand applications with a safe state greater than 4 mA, dual analog output modules are required.