Description
Core Product Summary
The ICS Triplex T9801 is a 16-channel simplex commoned digital input termination assembly for the AADvance safety controller platform. It provides field wiring terminations and routes discrete input signals to a single compatible T9401 or T9402 digital input module.
Designed for non-isolated simplex applications, the T9801 mounts on the T9300 I/O base unit. Each channel includes a replaceable 50 mA fuse for overcurrent protection. The assembly supports standard field wiring up to 1.31 mm² (16 AWG) and is intended for use in AADvance systems requiring simplex digital input termination.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Product type | Digital input termination assembly (TA) |
| System / series | AADvance |
| Channels | 16 |
| Configuration | Simplex, commoned (non-isolated) |
| Compatible input modules | One T9401 or T9402 |
| Field connections | 16 |
| Input channel fuses | 50 mA, 125 V, Type T (Littelfuse) |
| Channel load | (5.125 ± 0.2 %) kΩ |
| Channel isolation | None |
| Maximum field loop power dissipation | 0.2 W per field loop |
| Conductor size | Maximum 1.31 mm² (16 AWG) |
| Strip length | 6 mm (¼ in.) |
| Dimensions (H × W) | 132 mm × 42 mm |
| Weight | 133 g (5 oz) |
| Mounting base | T9300 I/O base unit |
Detailed Product Overview
The ICS Triplex T9801 serves as the field interface for simplex digital input configurations in AADvance controllers. It accepts up to 16 discrete field signals, protects each channel with an individual replaceable fuse, and presents the signals to a single T9401 (8-channel) or T9402 (16-channel) digital input module plugged into the same T9300 I/O base.
Because the assembly is commoned and non-isolated, it is suitable for applications where galvanic isolation between channels or between field and system is not required. The fixed channel load of approximately 5.125 kΩ ensures consistent voltage measurement by the associated input module. Fuses can be replaced without removing the termination assembly or the I/O module, simplifying maintenance.
The T9801 is one of three digital input termination options in the AADvance family. T9802 supports dual (isolated) arrangements with two modules, and T9803 supports TMR (isolated) arrangements with three modules. Selection of the correct termination assembly is determined by the required redundancy level and must match the number of installed input modules.
Installation requires the T9300 I/O base. Field wiring is connected via screw terminals; the recommended conductor size and strip length must be observed, and terminal screws tightened to the specified minimum torque. The assembly is coded for correct module mating and is intended only for AADvance systems.

T9801

T9801
Dimensions, Mounting & Connection Notes
- Dimensions (height × width): 132 mm × 42 mm
- Weight: 133 g (5 oz)
- Mounting: Attaches to T9300 I/O base unit; base mounts on DIN rail or panel
- Field terminals: Screw compression type
- Conductor cross-section: maximum 1.31 mm² (16 AWG)
- Stripping length: 6 mm (¼ in.)
- Terminal screw tightening torque: minimum 0.5 Nm (follow full manufacturer procedure)
- Fuse access: Cover opens for replacement without removing the assembly or module
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| System / controller family | AADvance | Not compatible with Trusted series |
| I/O base | T9300 | Required mounting base |
| Compatible modules | One T9401 or T9402 digital input module | Simplex configuration only |
| Redundancy level | Simplex | Use T9802 for dual or T9803 for TMR |
| Field wiring | Max. 1.31 mm² (16 AWG), 6 mm strip length | Screw terminals |
| Channel protection | 50 mA Type T fuses (replaceable) | Accessible without module removal |
| Coding | Module polarization keying | Ensures correct module type mating |
FAQ
What is the ICS Triplex T9801?
It is a 16-channel simplex commoned (non-isolated) digital input termination assembly for the AADvance platform.
Which modules does the T9801 support?
It supports one T9401 or T9402 digital input module.
Is the T9801 isolated?
No. It is a non-isolated, commoned design intended for simplex applications.
What fuse protection is provided?
Each of the 16 channels has a replaceable 50 mA, 125 V Type T fuse.
What is the channel load?
(5.125 ± 0.2 %) kΩ.
On which base does the T9801 mount?
It mounts on the T9300 I/O base unit.
Can the T9801 be used for dual or TMR configurations?
No. Dual configurations require the T9802 and TMR configurations require the T9803.
What conductor size is accepted?
Maximum 1.31 mm² (16 AWG) with a 6 mm strip length.