Sale!

ICS Triplex T9851 AADvance Digital Output TA for T9451 Module

The ICS Triplex T9851 is an 8-channel simplex commoned digital output termination assembly for the AADvance safety controller platform. It provides field wiring terminations and routes output signals from a single compatible T9451 digital output module to field devices.

Categories: , , , , SKU: T9851 Brand:

Description

Core Product Summary

The ICS Triplex T9851 is an 8-channel simplex commoned digital output termination assembly for the AADvance safety controller platform. It provides field wiring terminations and routes output signals from a single compatible T9451 digital output module to field devices.

The assembly accepts two independent nominal 24 V DC field power sources, each protected by a replaceable 10 A fuse. It mounts on the T9300 I/O base unit and is designed for non-isolated simplex digital output applications in AADvance systems.

Key Technical Specifications

Parameter Value
Product type Digital output termination assembly (TA)
System / series AADvance
Channels 8
Configuration Simplex, commoned
Compatible output module One T9451
Field power inputs Two nominal 24 V DC sources
Field supply fuses Two replaceable 10 A fuses (one per source)
Field connections 8
Conductor size Maximum 1.31 mm² (16 AWG)
Strip length 6 mm (¼ in.)
Dimensions (H × W) 132 mm × 42 mm
Weight 133 g (5 oz)
Mounting base T9300 I/O base unit

Detailed Product Overview

The ICS Triplex T9851 functions as the field interface for simplex digital output configurations in AADvance controllers. It connects the output channels of a single T9451 digital output module to field actuators such as solenoids, valves, or indicator devices, while providing dual redundant field power feeds.

Each of the two 24 V DC field power inputs is protected by an individual 10 A replaceable fuse. These fuses help safeguard the output module against certain field-side faults. The commoned design simplifies wiring for applications that do not require channel-to-channel isolation.

The T9851 is the simplex member of the AADvance digital output termination family. The T9852 supports dual configurations with two T9451 modules. Correct selection of the termination assembly is required to match the intended redundancy level and module population.

Installation is performed on the T9300 I/O base. Field wiring and power connections use screw terminals. Recommended conductor size, strip length, and minimum terminal torque must be observed. The assembly includes polarization keying to ensure correct mating with the T9451 module.

T9851

T9851

T9851

T9851

Dimensions, Mounting & Connection Notes

  • Dimensions (height × width analog 132 mm × 42 mm
  • Weight: 133 g (5 oz)
  • Mounting: Attaches to T9300 I/O base unit; base mounts on DIN rail or panel
  • Field terminals: Screw compression type
  • Conductor cross-section: maximum 1.31 mm² (16 AWG)
  • Stripping length: 6 mm (¼ in.)
  • Terminal screw tightening torque: minimum 0.5 Nm (follow full manufacturer procedure)
  • Field power: Two separate 24 V DC inputs, each with a replaceable 10 A fuse

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
System / controller family AADvance Not compatible with Trusted series
I/O base T9300 Required mounting base
Compatible module One T9451 digital output module Simplex configuration only
Redundancy level Simplex Use T9852 for dual arrangements
Field power Two independent nominal 24 V DC sources Each protected by a 10 A fuse
Field wiring Max. 1.31 mm² (16 AWG), 6 mm strip length Screw terminals
Fuse type 10 A (replaceable) One per field power source

FAQ

What is the ICS Triplex T9851?
It is an 8-channel simplex commoned digital output termination assembly for the AADvance platform.

Which module does the T9851 support?
It supports one T9451 digital output module.

How many field power sources does it accept?
Two independent nominal 24 V DC sources.

What fuse protection is provided?
Two replaceable 10 A fuses, one for each field power source.

Is the T9851 isolated?
It is a commoned (non-isolated) design intended for simplex applications.

On which base does the T9851 mount?
It mounts on the T9300 I/O base unit.

Can the T9851 be used for dual configurations?
No. Dual configurations require the T9852 termination assembly.

What conductor size is accepted?
Maximum 1.31 mm² (16 AWG) with a 6 mm strip length.