Sale!

Pioneer Magnetics PM33211BP-5-1-3-F 3000W AC/DC PFC Front-End Power Supply

Parameter Value
Manufacturer Pioneer Magnetics
Model / Order Number PM33211BP-5-1-3-F
Product family PM33xx PowerFactor series (high-voltage AC/DC front end)
Rated output power 3000 W
DC output 48 VDC at up to 62 A (single output)
AC input range (option -5) 180–264 VAC
Power factor correction Active PFC (switching, with PFC)
Construction Closed-frame front end
Operating configuration Standalone or parallel (redundant) operation
Operating temperature Full rated power, 0–50°C
Output adjustment ±10%
Output stability ±0.1% per 24 hours
Overvoltage protection Latching OVP, trip at approx. 125% ±5% of nominal output; clears after AC removal (approx. 30 s)
Output isolation Fully floating output
Safety approvals UL 1950, CSA 22.2 No. 950, TÜV EN 60950
Package format 5 × 5 inch front-end package
Categories: , , , , SKU: PM33211BP-5-1-3-F Brand:

Description

Core Product Summary

The Pioneer Magnetics PM33211BP-5-1-3-F is a 3000-watt AC/DC switching power supply front end from the PM33xx PowerFactor series, engineered for high-voltage single-output applications with active power factor correction. As a closed-frame front-end converter, it rectifies AC line input into a regulated 48 VDC bus at up to 62 A and is designed to operate either as a standalone supply or in parallel configurations where higher output capacity is required.

The “-5” input designation corresponds to a high-range AC input of 180–264 VAC, which suits installations supplied from 208/230/240 VAC services rather than universal-input sites. The unit is built in the standard 5 × 5 inch front-end package used across the PM33xx family, delivers full rated power across 0–50°C ambient, and carries UL 1950, CSA 22.2 No. 950, and TÜV EN 60950 safety approvals. Output protection includes a latching overvoltage trip set at approximately 125% of nominal, which clears after AC input is removed.

 

Key Technical Specifications

Parameter Value
Manufacturer Pioneer Magnetics
Model / Order Number PM33211BP-5-1-3-F
Product family PM33xx PowerFactor series (high-voltage AC/DC front end)
Rated output power 3000 W
DC output 48 VDC at up to 62 A (single output)
AC input range (option -5) 180–264 VAC
Power factor correction Active PFC (switching, with PFC)
Construction Closed-frame front end
Operating configuration Standalone or parallel (redundant) operation
Operating temperature Full rated power, 0–50°C
Output adjustment ±10%
Output stability ±0.1% per 24 hours
Overvoltage protection Latching OVP, trip at approx. 125% ±5% of nominal output; clears after AC removal (approx. 30 s)
Output isolation Fully floating output
Safety approvals UL 1950, CSA 22.2 No. 950, TÜV EN 60950
Package format 5 × 5 inch front-end package

 

Detailed Product Overview

The PM33211BP-5-1-3-F sits at the 3000-watt tier of Pioneer Magnetics’ PowerFactor line, which spans roughly 1000 W to 5000 W in the PM33xx high-voltage AC/DC classification. Within that line the unit fills the role of a rectifier front end: it takes facility AC power, applies power factor correction so the load presented to the line stays close to resistive, and produces a regulated 48 VDC bus suitable for telecom-style DC plants, distributed power architectures, or downstream DC/DC conversion stages.

Two characteristics of this build matter most at selection time. First, the “-5” input option restricts the acceptable AC window to 180–264 VAC. This is a deliberate trade-off against the wide-input (“-6”) builds: a narrower, higher input range allows a more efficient input stage for sites standardized on 208, 230, or 240 VAC services, but it means the unit is not the right choice for a location that must also tolerate 100–120 VAC operation. Engineers specifying a replacement unit should match the input suffix to the site supply, not just the power rating.

Second, the 48 V / 62 A output places this model in the standard telecom/instrument DC bus class at the 3000 W tier. The fully floating output allows the positive or negative rail to be referenced to chassis or system ground as the architecture requires. Output trimming of ±10% provides margin for battery-charging equivalents or line-loss compensation where the design permits, and the specified ±0.1% per 24-hour stability supports loads sensitive to long-term drift.

Protection behavior is worth understanding before commissioning. The overvoltage protection is a latching type, tripping at roughly 125% ±5% of the nominal output. Once tripped, the supply does not self-recover when the fault clears; it resets after AC input is removed (approximately 30 seconds). This behavior protects downstream loads from sustained overvoltage but means an OVP event during operation should be treated as a fault to diagnose, not a transient to ride through.

The high-voltage PowerFactor models are explicitly designed to support both standalone duty and parallel connection, with I/O available in standard non-plug and hot-plug interface variants. For parallel or redundant deployments, the interface type of each unit must be matched, and current sharing behavior should be confirmed against the specific chassis or rack wiring used. The closed-frame construction targets fixed installation in equipment enclosures or power racks rather than benchtop use.

Thermally, the supply delivers its full 3000 W rating from 0°C to 50°C ambient. Above this band, output must be derated according to the family’s thermal characteristics; enclosing the unit without forced airflow or with restricted inlet clearance will reduce the power actually available to the load. The 5 × 5 inch front-end package format matches the mechanical standard used across the PM33xx series, allowing the unit to occupy the same mounting envelope as other front ends in the family.

PM33211BP-5-1-3-F

PM33211BP-5-1-3-F

PM33211BP-5-1-3-F

PM33211BP-5-1-3-F

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
AC input service 180–264 VAC (option -5) Suited to 208/230/240 VAC sites; not a universal-input build
DC bus class 48 VDC, up to 62 A Standard telecom/instrument bus level
Operating mode Standalone or parallel configuration High-voltage PowerFactor models support both
I/O interface variants Non-plug and hot-plug interfaces available in the model family Interface type must match the chassis/rack connection scheme
Mounting envelope 5 × 5 inch front-end package Same package standard as the PM33xx series
Thermal environment Full power 0–50°C Ensure adequate intake airflow and clearance in the enclosure
OVP reset behavior Latching; clears approx. 30 s after AC removal Plan AC disconnect access for fault recovery
Output grounding Fully floating output Either polarity may be referenced to system ground

 

Dimensions, Mounting & Connection Notes

Item Value
Package format 5 × 5 inch front-end package
Approximate depth 11.25 in (family envelope for PM33xx front ends)
Construction Closed frame
Mounting Fixed installation in enclosure or power-rack position; front-end package footprint
Input AC line connection per the high-range 180–264 VAC input option
Output Regulated 48 VDC single output, fully floating

Installation should provide unobstructed airflow to the unit consistent with the 0–50°C full-power rating, and the latching OVP reset path — removal of AC input — should remain accessible after the unit is mounted. Terminal, torque, and clearance details specific to this build should be taken from the nameplate and the installation data shipped with the unit.

 

FAQ

What is the Pioneer Magnetics PM33211BP-5-1-3-F?
It is a 3000 W AC/DC switching power supply front end from the PM33xx PowerFactor series, providing a regulated single 48 VDC output at up to 62 A with active power factor correction.

What does the “-5” in the model number mean?
The “-5” option designates a high-range AC input of 180–264 VAC, intended for 208/230/240 VAC services rather than universal 90–264 VAC sites.

Which power class does the PM33211 occupy in the PM33xx family?
The PM33211 is the 3000-watt tier of the PowerFactor high-voltage front-end line, which spans models from roughly 1000 W to 5000 W.

Can this unit be operated in parallel with other units?
Yes. The high-voltage PowerFactor models are designed to support both standalone and parallel configurations, with non-plug and hot-plug I/O interface variants available in the family.

How does the overvoltage protection behave?
The OVP is a latching type that trips at approximately 125% ±5% of the nominal output and resets only after AC input has been removed for approximately 30 seconds.

Over what temperature range does the supply deliver full power?
The unit provides its full 3000 W rating from 0°C to 50°C ambient; above this range output must be derated.

Which safety approvals apply?
The power supply family is approved to UL 1950, CSA 22.2 No. 950, and TÜV EN 60950.

Can the output voltage be adjusted?
Yes, the output is adjustable within ±10%, with a specified long-term stability of ±0.1% per 24 hours.