Description
Key Technical Specifications
| Parameter | Value |
|---|---|
| Model | MVI56-MCM |
| Manufacturer | ProSoft Technology |
| Compatible platform | Rockwell Automation ControlLogix 1756 chassis, local or remote |
| Function | Modbus RTU/ASCII master/slave interface between ControlLogix processor and serial devices |
| Chassis slots required | 1 |
| Serial application ports | 2 independent ports, PRT1 and PRT2 |
| Serial electrical interfaces | RS-232, RS-422, or RS-485, jumper selectable |
| Serial connectors | RJ45 with supplied RJ45-to-DB-9 male adapter cables |
| Serial protocols | Modbus RTU Master/Slave and Modbus ASCII Master/Slave |
| Baud rate | 110 baud to 115,200 baud |
| Data bits | 7 or 8 |
| Stop bits | 1 or 2 |
| Parity | None, even, or odd |
| RTS on/off delay | 0 to 65,535 ms |
| Error checking | Modbus RTU: CRC-16; Modbus ASCII: LRC |
| Modbus slave address | 1 to 247 |
| Master commands | Up to 100 commands per master port |
| Shared database | 5,000 user-assignable 16-bit registers |
| Backplane data transfer | Input image: 250 words; output image: 248 words |
| Port isolation | 500 V optical isolation from backplane |
| Configuration/debug port | CFG, RS-232 only |
| Configuration method | Ladder logic and controller tags in RSLogix 5000 / Studio 5000 |
| Backplane current load | 800 mA at 5 V DC; 3 mA at 24 V DC |
| Operating temperature | 0 to +60°C |
| Storage temperature | −40 to +85°C |
| Relative humidity | 5% to 95%, non-condensing |
| Shock rating | 30 g operational; 50 g non-operational |
| Vibration rating | 5 g from 10 to 150 Hz |
The MVI56-MCM is the general-purpose Modbus serial master/slave module for ControlLogix. It is preferred for a local chassis with the controller or for a remote chassis accessed over Ethernet; the MVI56-MCMR is the reduced-I/O variant intended for ControlNet remote chassis applications.
Product Introduction
The ProSoft MVI56-MCM is a single-slot Modbus master/slave communication module for Rockwell Automation ControlLogix 1756 chassis. It connects a ControlLogix processor to Modbus RTU or ASCII instruments, drives, meters, PLCs, and PACs over two isolated serial ports.
Each port can be independently configured as a Modbus master or slave, allowing simultaneous polling of field devices and response to external SCADA or HMI masters. The module maintains a 5,000-word shared database and exchanges a 250-word input image and 248-word output image with the processor over the backplane.

MVI56-MCM

MVI56-MCM
Troubleshooting Quick Reference
| Symptom | Possible Cause | Relevance to this Part | Quick Check Method | Recommendation |
|---|---|---|---|---|
| Module not recognized in RSLogix/Studio 5000 | Missing EDS file, wrong slot, or chassis configuration issue | ✅ High | Verify slot number, import the ProSoft EDS file, and confirm the module appears in the I/O tree | Correct chassis configuration before replacing the MVI56-MCM |
| No Modbus communication on PRT1 or PRT2 | Wrong RS-232/422/485 jumper, wiring fault, or baud/parity mismatch | ✅ High | Check port jumper positions, DB-9 adapter pinout, baud rate, parity, data bits, and stop bits | Match port jumpers and serial settings to the field device |
| One port works, other does not | Port-specific jumper, wiring, or ladder/configuration issue | ✅ High | Swap known-good serial devices between PRT1 and PRT2; compare controller-tag configuration | Isolate the fault to port hardware, wiring, or configuration |
| Master polls but device does not respond | Wrong slave address, function code, register address, or cable fault | ✅ High | Use a Modbus analyzer or serial sniffer; verify slave ID, function code, and starting address | Correct master command configuration before replacing hardware |
| Slave device cannot access data | Incorrect slave ID, register mapping, or write protection | ✅ High | Confirm slave ID, register offsets, and read/write permissions in controller tags | Correct slave mapping and access settings |
| Data does not update in processor tags | Ladder copy logic, module scheduling, or backplane image configuration issue | ✅ High | Verify scheduled connection, input/output image sizes, and ladder MOV/COP instructions | Correct ladder data transfer and module scheduling |
| Module OK LED off or ERR LED on | Backplane power issue, module fault, or invalid configuration | ✅ High | Measure chassis power budget; reseat the module; review LED status and controller diagnostics | Restore power or replace the faulty module |
| Communication drops intermittently | RS-485 termination, shield/ground issue, or excessive polling load | ✅ Medium | Inspect RS-485 termination and shield grounding; review polling interval and command list | Correct bus termination and optimize polling configuration |
❗ Do not assume the MVI56-MCM has failed because a Modbus device stops responding. Wrong slave ID, incorrect register offset, reversed RS-485 wiring, or a bad DB-9 adapter causes most serial communication faults.
If the fault remains after checking the EDS/chassis configuration, port jumpers, serial wiring, Modbus register mapping, and ladder data transfer, contact technical support with photos of the module, jumper settings, RSLogix I/O tree, and controller-tag configuration.
Frequently Asked Questions
Can the MVI56-MCM act as both Modbus master and slave?
Yes. Each of the two serial ports can be independently configured as a Modbus master or slave, and both ports share the module’s 5,000-word user database.
Does it support Modbus TCP/IP?
No. The MVI56-MCM supports Modbus RTU and ASCII over its two serial ports. It does not provide Modbus TCP/IP data exchange; use the MVI56-MNET or MVI56E-MNET for Ethernet-based Modbus TCP/IP integration.
Why choose the MVI56-MCM instead of the MVI56-MCMR?
Choose the MVI56-MCM for a local ControlLogix chassis or a remote chassis connected over Ethernet. It uses larger 250-word input and 248-word output images. The MVI56-MCMR uses smaller 42-word I/O images and is intended for ControlNet remote chassis applications.
How many Modbus slave devices can it poll?
Each master port supports up to 100 configured commands. The practical number of slave devices depends on the command list, polling interval, register count, and serial network response time.
Can I use RS-485 two-wire devices on both ports?
Yes. Each application port supports RS-232, RS-422, or RS-485 through jumper selection. For RS-485, verify polarity, biasing, termination, and cable shield grounding; do not connect both ports to the same multidrop network unless the application specifically requires it.
Can I hot-swap the MVI56-MCM?
No. Although it is a 1756 chassis module, removing it while active can interrupt Modbus communications and processor I/O connections. Follow a controlled removal procedure, then verify the module status and scheduled connection after reinstallation.
Why is New Surplus less expensive than factory-new stock?
New Surplus means genuine ProSoft inventory manufactured earlier but not installed or commissioned. We inspect, document, and functionally verify each unit before shipment. It is not used, repaired, or refurbished stock unless clearly stated on the product page.