Description
Core Product Summary (Brand / Model / Key Attributes)
The ProSoft Technology PTQ-PDPMV1 is a high-performance PROFIBUS DP Master network interface module engineered specifically for Schneider Electric Modicon Quantum automation platforms. Operating as a single-slot in-chassis solution, it enables Quantum processors to seamlessly integrate and exchange deterministic data with PROFIBUS DP/PA field devices, drives, and decentralized I/O blocks.
The module supports complete master specifications according to IEC 61158, utilizing advanced Siemens ASIC and Infineon microprocessing technology. It handles both cyclic process data and Class 1/Class 2 acyclic DPV1 parameter data, supporting up to 125 slave devices. Configured via ProSoft Configuration Builder (PCB) and compatible with Unity Pro and Concept programming environments, the PTQ-PDPMV1 supports standard baud rates up to 12 Mbit/s with auto-baud detection, and integrates smoothly into Unity Hot Standby (HSBY) system architectures.
Key Technical Specifications
| Parameter | Verified Specification Value |
| Manufacturer | ProSoft Technology |
| Model / Order Number | PTQ-PDPMV1 |
| Product Type | PROFIBUS DP Master Network Interface Module |
| Compatible Processor Family | Schneider Electric Modicon Quantum PLC Series |
| Backplane Slot Usage | Single-slot, local rack compatible (up to 6 modules per rack) |
| Supported Protocols | PROFIBUS DP-V0, DP-V1, PROFIdrive 3.1 |
| Maximum Slave Capacity | Up to 125 slave devices (with repeaters) |
| Transmission Speeds | Up to 12 Mbit/s with auto-baud detection |
| Processor & Hardware | Siemens ASIC ASPC2 Step E with Infineon C165 Microprocessor |
| Data Transfer Type | Asynchronous data exchange with Quantum PLC memory (3x, 4x types) |
| Physical Network Interface | RS-485 via 9-pin D-sub female connector (optically isolated) |
| Software Compatibility | Unity Pro (v2.2+), Concept (v2.6+), ProWORX (v2.20+), ProSoft Configuration Builder |
| Hot Standby Support | Complies with Unity HEC Hot Standby specifications (Unity Pro environment) |
Detailed Product Overview
The ProSoft PTQ-PDPMV1 module acts as a bridge between a Modicon Quantum processor and a industrial PROFIBUS network. It manages time-critical cyclic input/output data exchanges independently from the processor scan cycle while simultaneously processing complex DPV1 acyclic commands, diagnostic tracking, and alarm acknowledgments.
Designed for demanding process and discrete automation environments, the unit supports advanced features such as Sync/Freeze commands, Multicast/Broadcast telegrams, and transparent routing to PROFIBUS PA sub-nets via DP/PA couplers. Its hardware architecture ensures high reliability and fast backplane throughput. In high-availability applications, the module supports Unity Pro Hot Standby systems, ensuring rapid switchover times (nominal 100 ms) and continuous network health tracking via background ping services.

PTQ-PDPMV1

PTQ-PDPMV1
Engineering Selection Highlights
- Native Quantum Integration: Built specifically for the Modicon Quantum backplane, mapping data directly into standard PLC memory registers (3x/4x).
- Comprehensive DPV1 Support: Facilitates both Class 1 and Class 2 acyclic parameter read/write operations for smart field instruments and drives.
- Hot Standby (HSBY) Compatibility: Fully integrates into Unity Pro redundant CPU architectures, providing automatic secondary master tracking and bumpless failover.
- High Network Capacity: Manages up to 125 slave nodes across standard baud rates up to 12 Mbit/s with automatic speed detection.
- FDT/DTM Integration: Supplied with communication DTM software (comDTM) to streamline device management and configuration through standard container tools like PACTware.
Dimensions, Mounting & Connection Notes
The PTQ-PDPMV1 is built in a standard single-slot form factor designed to slide directly into any available I/O or options slot of a Modicon Quantum rack. Power is drawn directly from the backplane bus.
The front panel features a 9-pin D-sub female connector for the PROFIBUS RS-485 network drop, alongside diagnostic LED indicators that display module status, backplane transfer activity, token-hold states, and communication errors. Proper grounding of the PROFIBUS cable shield at the cabinet entry point is mandatory to protect against high-frequency electromagnetic interference.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| PLC Rack Placement | Local rack only; must reside in the same rack as the Quantum CPU | Up to 6 modules can populate a single rack (limited to 4 modules in standard Hot Standby setups). |
| Programming Software | Schneider Unity Pro, Concept, or ProWORX | Requires appropriate version support (e.g., Unity Pro v2.2 or higher). |
| Network Configuration | ProSoft Configuration Builder (PCB) | Uses drag-and-drop Busview interface for establishing device configurations. |
| Cabling & Termination | Standard PROFIBUS shielded twisted-pair cable | Connects via a 9-pin D-sub female port featuring optical isolation. |
FAQ
What is the primary function of the ProSoft PTQ-PDPMV1?
The PTQ-PDPMV1 is a PROFIBUS DP Master communication module that links Schneider Electric Modicon Quantum processors to decentralized PROFIBUS networks.
How many slave devices can a single PTQ-PDPMV1 module support?
It supports up to 125 PROFIBUS slave devices on the network using appropriate signal repeaters.
Is the PTQ-PDPMV1 compatible with Quantum Hot Standby systems?
Yes, it is fully compatible with Unity Pro Hot Standby (HSBY) redundancy architectures utilizing supported CPU models.
What software is required to configure the module?
Network layout and module parameters are configured using ProSoft Configuration Builder (PCB), while device-level parameterization can be handled via included FDT/DTM drivers.
How does the module transfer data to the Quantum processor?
Data is transferred asynchronously across the Quantum backplane into designated PLC memory spaces (3x and 4x data types).
Verification & Troubleshooting Notes
- Module Status LEDs: Review front-panel indicators; a flashing or red error LED typically points to a configuration mismatch, incorrect station address, or broken token ring.
- Hot Standby Health Verification: In redundant setups, ensure firmware versions match system requirements and that secondary master health pings are active to guarantee seamless switchover performance.
- Baud Rate Mismatch: If communication fails to establish, confirm that network devices match the system baud rate; the module features auto-baud detection, but line termination must be correctly powered and set at both ends of the trunk.