Description
Core Product Summary
The Schneider Electric SCADAPack TBUP4-105-01-00 is a SCADAPack 32 Smart Remote Terminal Unit (RTU) featuring a 32-bit controller and integrated Ethernet connectivity. It is designed for remote data acquisition, telemetry communication, and programmable control in industrial automation systems.
This configuration combines the standard SCADAPack 32 controller and 5601A lower I/O arrangement with serial and Ethernet communication interfaces. Its configuration includes Modbus and DNP3 protocol support, IEC 61131-3 and C-language programming, and single-ended 0–20 mA analog inputs. The digital I/O arrangement includes 24 VDC digital inputs and dry-contact digital outputs. No analog output option is selected in the specified order code.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Schneider Electric |
| Product brand | SCADAPack |
| Model | TBUP4-105-01-00 |
| Product family | SCADAPack 32 |
| Product type | Smart Remote Terminal Unit |
| Controller | TBUP4, 32-bit |
| Processor | Hitachi SH-3 |
| Processor clock | 120 MHz |
| Memory | 8 MB SDRAM, 4 MB FLASH, 1 MB CMOS RAM |
| Lower I/O configuration | 5601A |
| Analog inputs | 8 channels, single-ended |
| Analog input signal | 0–20 mA |
| Digital inputs | 16 on lower I/O module, plus 4 on controller board |
| Digital outputs | 12 relay outputs on lower I/O module |
| Additional controller output | 1 status output, 30 VDC / 60 mA |
| Analog outputs | None selected |
| Serial communication | 3 RS-232 and 1 configurable RS-232/RS-485 |
| Ethernet | 10Base-T, RJ45 |
| Serial protocols | Modbus RTU, Modbus ASCII, DNP3, DF1, PPP |
| Ethernet protocols | Modbus TCP, Modbus RTU over UDP, Modbus ASCII over UDP, DNP over TCP/UDP |
| Programming | IEC 61131-3 and C language; Telepace enabled |
| Power input | 11–30 VDC |
| Typical power consumption | 4.3 W |
| Maximum power consumption | 10.8 W at full I/O capacity |
| Operating temperature | -40 to +70 °C |
| Relative humidity | 5–95%, non-condensing |
| Mounting | Industrial enclosure installation |
| Dimensions | 213 × 155 × 72 mm |
Detailed Product Overview
SCADAPack 32 Remote Control Architecture
The SCADAPack TBUP4-105-01-00 belongs to the SCADAPack 32 Smart RTU platform. Its 32-bit controller architecture combines field-level signal acquisition, local processing, and communication with supervisory control systems.
The controller uses a Hitachi SH-3 processor operating at 120 MHz. Its memory configuration consists of 8 MB SDRAM, 4 MB FLASH, and 1 MB CMOS RAM. Battery-backed CMOS RAM retains its contents for up to two years without external power, according to the product documentation.
This architecture allows the RTU to execute programmed control logic while exchanging process information with remote supervisory equipment.
Integrated Analog and Digital I/O
The specified configuration incorporates a 5601A lower I/O module.
Its field interface includes:
- Eight single-ended analog inputs with a 0–20 mA measuring range.
- Sixteen digital inputs.
- Twelve sealed mechanical relay digital outputs.
- Four additional digital inputs on the controller board.
- One controller-board status output.
The analog input channels support current-based field instrumentation. The digital inputs can collect discrete equipment states, while the relay outputs provide switching interfaces for compatible control circuits.
For system replacement, the installed I/O arrangement and field wiring should be compared with the existing controller before commissioning.
Ethernet and Serial Communication
The TBUP4 controller provides integrated 10Base-T Ethernet connectivity through an RJ45 interface.
Its communication architecture also includes three RS-232 ports and one configurable RS-232/RS-485 port. This combination supports communication with serial field equipment and Ethernet-connected supervisory systems.
Supported communication options include Modbus RTU, Modbus ASCII, DNP3, DF1, and PPP over serial connections. Ethernet communication supports Modbus TCP, Modbus over UDP, and DNP over TCP or UDP.
These interfaces allow the controller to participate in distributed telemetry architectures where communication settings must be coordinated with the master station and connected field devices.
Programming and Control Logic
The specified protocol and programming configuration uses IEC 61131-3 and C-language firmware, with Telepace enabled.
This gives system engineers programming options for developing and maintaining application logic. When replacing an existing unit, the application program, firmware configuration, communication parameters, and I/O mapping should be reviewed together.
Power and Environmental Requirements
The controller accepts an 11–30 VDC supply. Its documented typical consumption is 4.3 W, increasing to 10.8 W when operating at full I/O capacity.
The operating temperature range is -40 to +70 °C, with relative humidity from 5% to 95% without condensation.
These requirements are relevant when evaluating the available DC supply, enclosure conditions, and thermal environment at remote installations.

TBUP4-105-01-00

TBUP4-105-01-00
System Compatibility & Integration Requirements
| Integration item | Configuration or requirement |
|---|---|
| Controller family | SCADAPack 32 |
| Controller hardware | TBUP4 |
| Lower I/O hardware | 5601A |
| Analog input | 0–20 mA, single-ended |
| Digital input | 24 VDC input configuration |
| Digital output | Dry-contact relay output |
| Analog output | Not included in this order configuration |
| Ethernet | 10Base-T, RJ45 |
| Serial communication | RS-232 and configurable RS-232/RS-485 |
| Protocol configuration | Modbus and DNP3 |
| Programming environment | IEC 61131-3 and C, with Telepace enabled |
| Power supply | 11–30 VDC |
Integration considerations
- Confirm that the existing field instruments use the specified 0–20 mA analog input range.
- Check the digital input voltage and relay output requirements against the field circuits.
- Verify serial communication wiring, baud rate, parity, and protocol settings.
- Confirm Ethernet addressing and communication settings with the SCADA master.
- Review the controller application and firmware configuration before transferring an existing project.
Dimensions, Mounting & Connection Notes
Mechanical dimensions
| Parameter | Value |
|---|---|
| Width | 213 mm |
| Height | 155 mm |
| Depth | 72 mm |
The SCADAPack 32 uses removable terminal blocks for field connections.
Documented terminal characteristics include:
- Terminal conductor range: 12–22 AWG.
- Terminal contact rating: 15 A.
- Removable terminal block configurations with different pole counts.
Installation considerations:
- Provide a suitable industrial enclosure.
- Verify the DC supply polarity and voltage before energizing.
- Separate communication wiring from electrically noisy power circuits where appropriate.
- Check signal grounding and shielding arrangements.
- Identify the correct terminal assignments from the 5601A-specific wiring documentation.
Frequently Asked Questions
Q1: What is the Schneider Electric TBUP4-105-01-00?
It is a SCADAPack 32 Smart Remote Terminal Unit designed for industrial telemetry, remote monitoring, field-data acquisition, and programmable control.
Q2: Which I/O configuration does this model use?
The specified configuration uses the 5601A lower I/O module, with eight analog inputs, sixteen digital inputs, and twelve relay digital outputs.
Q3: Does the TBUP4-105-01-00 support Ethernet?
Yes. It includes a 10Base-T Ethernet interface with an RJ45 connector.
Q4: Which communication protocols does it support?
Supported protocols include Modbus RTU, Modbus ASCII, DNP3, DF1, and PPP over serial communication, along with Modbus and DNP communication over Ethernet.
Q5: What is the power supply requirement?
The controller operates from an 11–30 VDC supply.
Q6: Which programming environment is configured?
The specified order configuration uses IEC 61131-3 and C-language firmware, with Telepace enabled.
Q7: Does this configuration include analog outputs?
No. The final 0 configuration in the model code selects no analog output option.
Q8: What should be checked before replacing this RTU?
Check the controller model, lower I/O configuration, analog signal range, digital I/O wiring, communication interfaces, firmware, and application program.