Description
Core Product Summary (Brand / Model / Key Attributes)
The STI SpecSeal LCI 300 (also designated as LCI300) is a latex-based, single-grade intumescent firestop sealant manufactured by Specified Technologies Inc. (STI). Formulated for interior firestopping applications, this water-based sealant expands when exposed to heat to form a dense char that blocks the passage of fire, smoke, and hot gases through through-penetration firestop systems and construction joints.
Designed for application via standard caulking guns, trowels, or knives, SpecSeal LCI 300 adheres to common construction substrates including concrete, masonry, wood, steel, copper, and plastic piping. It features high build capability for vertical and overhead joints, remains halogen-free and asbestos-free, and cures to form a tough, paintable, water-resistant seal compliant with rigorous UL fire-resistance test standards.
Key Technical Specifications
| Parameter | Specification |
| Product Type | Intumescent Firestop Sealant |
| Manufacturer | Specified Technologies Inc. (STI) |
| Model / Part Number | SpecSeal LCI 300 (LCI300 / LCI305) |
| Base Material | Water-based latex emulsion |
| Color | Red |
| Expansion Temperature | Begins expanding at ~320 °F (~160 °C) |
| Expansion Rate | Up to 8x to 10x free expansion |
| Flame Spread / Smoke Index | Flame Spread < 25, Smoke Developed < 50 (ASTM E84 / UL 723) |
| Application Temperature Range | 40 °F to 95 °F (4 °C to 35 °C) |
| In-Service Temperature Range | -10 °F to 185 °F (-23 °C to 85 °C) |
| Cure Time | Full cure within 7 to 14 days (depending on temperature and humidity) |
| VOC Content | Low VOC (< 30 g/L) |
Detailed Product Overview
STI SpecSeal LCI 300 is engineered to protect electrical, plumbing, HVAC, and structural penetrations penetrating fire-rated walls and floors. Upon exposure to temperatures exceeding 320 °F, the intumescent material expands rapidly to seal gaps left by combustible materials (such as plastic pipe insulation or cable jackets) as they burn away during a fire event.
The latex-based formulation provides excellent adhesion to most construction materials without requiring additional primers in standard installations. Its non-sag consistency ensures easy placement in vertical wall joints and overhead floor/ceiling assemblies. Once fully cured, LCI 300 resists moisture exposure, maintains acoustic isolation performance, and accepts standard latex paint finishes.
Application involves cleaning the penetration opening of debris, installing required backing materials (such as mineral wool forming insulation where specified by UL system designs), and applying the sealant to the designated depth.
Engineering Selection Highlights
- Intumescent Protection: Expands 8x to 10x when exposed to elevated heat, maintaining barrier integrity around burning or melting penetrants.
- Water-Based Latex Formula: Allows easy cleanup with water while un-cured and reduces environmental impact with low VOC emissions.
- High Build & Non-Sag: Holds form on vertical walls and overhead joints without sagging during application.
- Substrate Versatility: Bonds firmly to concrete, gypsum board, metallic pipe, cable trays, and insulated pipe sleeves.
- Paintable Finish: Accepts latex-based paints once cured to match surrounding wall or ceiling finishes.

LCI 300

LCI 300
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Fire Test Standards | ASTM E814 / UL 1479 and ASTM E1966 / UL 2079 | Consult specific UL designated design numbers for depth and backing requirements |
| Approved Substrates | Concrete, masonry, drywall, steel, copper, metallic conduit | Surfaces must be clean, dry, and free of frost, oil, or loose debris |
| Backing Material | Mineral wool or foam backer rod (as required by tested system) | Compression and depth of backing must follow tested UL system criteria |
| Cleanup & Tooling | Soap and water (before curing) | Tool flush with surface within 10–15 minutes of application |
Dimensions, Mounting & Connection Notes
- Packaging Formats: Available in standard 10.1 oz (300 ml) cartridges, 20 oz sausages, and 5-gallon bulk pails.
- Application Method: Standard manual, pneumatic, or battery-powered caulking guns; knife or trowel for bulk applications.
- Joint / Opening Prep: Minimum depth and width dimensions must strictly follow UL firestop system installation drawings.
- Storage Conditions: Store in dry indoor conditions between 40 °F and 95 °F (4 °C to 35 °C); protect from freezing prior to application.
FAQ
- What is STI SpecSeal LCI 300?
It is a latex-based intumescent firestop sealant designed to seal mechanical, electrical, and structural penetrations in fire-rated wall and floor assemblies.
- How does LCI 300 work during a fire?
When exposed to heat above 320 °F, the sealant expands intumescently to fill voids and prevent the spread of fire, smoke, and toxic gases.
- Can LCI 300 be painted?
Yes, once fully cured, SpecSeal LCI 300 can be painted over with standard latex paints.
- Is LCI 300 suitable for wet or exterior applications?
LCI 300 is designed primarily for interior applications. Once fully cured it is water-resistant, but it should not be continuously submerged or used in exposed exterior locations subject to weather.
- Does LCI 300 require mineral wool backing?
Backing requirements depend on the specific UL or firestop system design. Many fire-rated systems specify mineral wool or backer rod to achieve required hourly ratings.
Verification & Troubleshooting Notes
- Pre-Cure Freeze Protection: Do not allow un-cured sealant cartridges or installed joints to freeze, as ice crystal formation permanently damages latex emulsion stability.
- UL System Compliance: Always verify that the installed depth, annular space, penetrant type, and substrate match an active UL-tested firestop design.
- Surface Cleanliness: Ensure all oil, dust, wax, and moisture are removed from contact surfaces prior to application to prevent bond failure.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626