Sale!

TOSHIBA SN626 nv Series Station Bus Transmission Module

The TOSHIBA SN626 is a transmission module for Toshiba industrial controller systems, listed for the nv Series controller (type1 light) station bus and for the T Series (S2T/S2E, T-PDS) controller family. It implements a TOSLINE-S20 connection using an optical bus medium, giving the controller a port onto Toshiba’s control LAN / field-equipment network for communication with other controller units, PLCs, drives, and instrumentation.

Categories: , , , , SKU: SN626 Brand:

Description

Core Product Summary

The TOSHIBA SN626 is a transmission module for Toshiba industrial controller systems, listed for the nv Series controller (type1 light) station bus and for the T Series (S2T/S2E, T-PDS) controller family. It implements a TOSLINE-S20 connection using an optical bus medium, giving the controller a port onto Toshiba’s control LAN / field-equipment network for communication with other controller units, PLCs, drives, and instrumentation.

TOSLINE-S20 is a 2 Mbps network that supports both message transmission and scan transmission, in which data is periodically exchanged between stations without individual polling. On the optical bus physical layer used by the SN626, the network spans up to 1 km between stations and up to 10 km for the overall system. Within the module range, the SN625 provides the coaxial (electrical) bus version and the SN627 the optical loop version, so the SN626 is the variant selected when the station bus is run over optical fiber in bus topology.

 

Key Technical Specifications

Parameter Value
Product type Station bus transmission module (communications module)
Compatible controller platforms Toshiba nv Series (type1 light) and T Series / T-PDS (S2T, S2E) controllers
Network implemented TOSLINE-S20
Physical medium Optical fiber, bus topology
Transmission rate 2 Mbps
Transmission services Message transmission and scan transmission (periodic data exchange)
Scan transmission capacity (TOSLINE-S20) 1024 words
Station-to-station distance (optical) 1 km maximum
Overall system length 10 km maximum
Related order designation GSN626**S
Sibling variants SN625 (TOSLINE-S20 coaxial/electrical bus), SN627 (TOSLINE-S20LP optical loop)

 

Engineering Selection Highlights

  • Medium-specific variant: the SN626 is the optical bus version of TOSLINE-S20; selecting it means the station bus cabling is optical fiber, whereas coaxial installations use the SN625 and optical loop (S20LP) installations use the SN627 — the three are not interchangeable on the same cable plant.
  • Controller platform fit: the module is specified for nv Series (type1 light) and the T Series S2T/S2E controller families, so it belongs in Toshiba controller racks of those generations rather than in current V Series or nv Series type2/type3 platforms.
  • Scan transmission for periodic data: TOSLINE-S20 scan transmission exchanges up to 1024 words of data periodically between stations, which suits inter-controller signal exchange and drive/meter data collection that must refresh at a fixed cycle rather than on request.
  • Distance capability: 1 km between stations and up to 10 km system length on optical fiber allow the station bus to span between control rooms and remote equipment rooms without repeaters within those limits.
  • Host computer link option: TOSLINE-S20 is one of the serial connection systems supported for linking Toshiba PLCs to PC-based SCADA/software packages, so an SN626 can serve as the gateway between the controller station bus and a supervisory computer link.
  • Order designation cross-reference: units also appear under the designation GSN626**S; matching either designation against the installed configuration avoids mixing the optical bus module with its coaxial or loop siblings.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Controller platform nv Series controller (type1 light); T Series S2T/S2E (T-PDS) Fits the station bus slot of these Toshiba controller platforms
Network Control LAN / field-equipment network for controller-to-controller and controller-to-device data exchange
Physical layer Optical fiber bus topology Optical cable plant required; not usable on the coaxial bus of the SN625
Partner stations Other TOSLINE-S20 stations (PLC, drive, and meter interfaces) 2 Mbps network with 1 km maximum station-to-station spacing
Data services Message transmission and scan transmission Scan transmission periodically refreshes shared data between stations
Sibling modules SN625 (coaxial bus), SN627 (optical loop, TOSLINE-S20LP) Same network family, different media/topology — do not substitute between them
Host connection TOSLINE-S20 serial connection to PC-based computer links One of the serial connection systems supported by Toshiba PC-link software
SN626

SN626

SN626

SN626

Applications & System Role

In a Toshiba controller architecture, the SN626 is the communications module that places a controller station onto the TOSLINE-S20 station bus. The station bus is the layer at which multiple controller units, PLCs, drives, and measurement devices exchange data: interlocking signals between controllers are carried by scan transmission at a fixed refresh cycle, while message transmission handles on-demand communication. By implementing the optical bus version, the SN626 is the module chosen where the bus must span plant areas with fiber cabling, for example between a control room cabinet and equipment distributed across an installation.

Typical fit scenarios follow from the network’s documented role: linking nv Series type1 light or S2T-generation controller stations into one data-sharing station bus; connecting controller units with Toshiba drives and metering devices over the control LAN; and providing the TOSLINE-S20 connection used by PC-based supervisory software for serial computer-link access to the controllers.

 

Detailed Product Overview

Toshiba’s nv Series and the related T Series controller families organize their communications into defined buses: the I/O bus for local input/output, and the station bus for inter-station data exchange. Transmission modules implement the station bus, and the SN621/SN625/SN626/SN627 group covers the TOSLINE-S20 options. The SN626 specifically implements the optical bus medium, distinguishing it from the electrical (coaxial) SN625 and from the SN627, which uses an optical loop topology on the extended TOSLINE-S20LP network.

TOSLINE-S20 itself is documented by Toshiba as a control LAN and field-equipment network for transmission between controller units and with PLCs, drives, and meters. Its two communication services matter for different engineering purposes. Scan transmission allocates a defined data area — up to 1024 words on the network — that every station refreshes periodically, giving deterministic, cyclic exchange of interlock signals and process values without request-response overhead. Message transmission complements this with on-demand data transfer between stations. A module such as the SN626 therefore determines not only which cable plant a controller can join, but also how the machine or plant shares data between its control nodes.

The choice of the optical bus variant is normally driven by the installation environment rather than by data behavior: the network’s data services are the same across the S20 media options, but fiber offers electrical isolation and suitably long reach for stations spread across a facility, with station-to-station spans up to 1 km and an overall system length up to 10 km. Within a cabinet, the module occupies a defined transmission-module slot in the compatible controller platforms, and configuration of the station bus — station addresses and the scan data layout — is performed with the platform’s engineering tools.

For engineers maintaining installations built on these controller generations, the decisive selection checks are the controller platform and model, the bus medium installed between stations, and the module’s role in the scan transmission data layout. Because TOSLINE-S20 also serves as one of the supported serial connection systems for PC-based computer links, an SN626 may additionally be the access point through which supervisory software reaches the controllers — worth confirming before replacing or reconfiguring a station, since the host connection depends on the bus configuration being intact.

 

FAQ

What is the TOSHIBA SN626?
It is a station bus transmission module for Toshiba nv Series (type1 light) and T Series (S2T/S2E) controllers, implementing a TOSLINE-S20 connection over an optical bus medium.

What network does it implement?
TOSLINE-S20, Toshiba’s control LAN / field-equipment network for data exchange between controller units, PLCs, drives, and meters.

What are the key network specifications?
TOSLINE-S20 operates at 2 Mbps, supports both message and scan transmission, carries up to 1024 words of scan data, and on the optical bus medium spans up to 1 km between stations and up to 10 km overall.

What is the difference between the SN625, SN626, and SN627?
All three are TOSLINE-S20 transmission modules, but the SN625 uses the coaxial (electrical) bus, the SN626 the optical bus, and the SN627 the optical loop on TOSLINE-S20LP; they are not interchangeable on the same cable plant.

What is scan transmission?
It is TOSLINE-S20’s cyclic communication service, in which a defined data area is periodically sent and received between stations, providing deterministic exchange of interlock and process signals.

Which controllers accept this module?
It is specified for the nv Series controller (type1 light) and the T Series S2T/S2E controller families with T-PDS.

Can it connect a controller to a supervisory computer?
Yes, TOSLINE-S20 is one of the serial connection systems supported by Toshiba PC-link software, so an SN626 can provide the host computer connection to the station bus.

What does the designation GSN626S refer to?
It is the order designation under which the same TOSLINE-S20 optical bus module is referenced in Toshiba documentation and parts listings.