Sale!

Vibro-Meter VM600 RPS6U 200-582-500-013 AC Rack Power Supply

The Vibro-Meter VM600 RPS6U (Part Number 200-582-500-013) is a high-reliability AC-input rack power supply designed for the VM600 series machinery protection and condition monitoring systems. It delivers a maximum combined output of 330 W, providing regulated +5 VDC, +12 VDC, and -12 VDC rails to power the rack backplane and all installed modules.

Categories: , , , , SKU: VM600 RPS6U 200-582-500-013 Brand:

Description

Core Product Summary

The Vibro-Meter VM600 RPS6U (Part Number 200-582-500-013) is a high-reliability AC-input rack power supply designed for the VM600 series machinery protection and condition monitoring systems. It delivers a maximum combined output of 330 W, providing regulated +5 VDC, +12 VDC, and -12 VDC rails to power the rack backplane and all installed modules.

This 6U module features autoranging AC input capabilities and comprehensive internal protection, including over-voltage latch-off and automatic short-circuit recovery. It supports both single-supply operation and redundant dual-supply configurations within a standard VM600 ABE04x system rack, ensuring continuous system availability for critical rotating machinery monitoring applications.

 

Key Technical Specifications

Parameter Specification
Product Family Vibro-Meter VM600 Series
Module Type RPS6U Rack Power Supply (AC-Input)
Part Number 200-582-500-013
Nominal Input Voltage 115 / 230 VAC (Autoranging: 90 to 132 VAC and 180 to 264 VAC)
Input Frequency 47 to 63 Hz
Maximum Output Power 330 W (total combination load)
Output Voltages & Currents +5 VDC (up to 50 A), +12 VDC (up to 8 A), -12 VDC (up to 4 A)
Voltage Accuracy +5.35 VDC nominal (5.35 to 5.45 V at 3 to 50 A load)
±12.5 VDC nominal (12.2 to 12.8 V at 0 to 8 A load)
Ripple and Noise < 50 mV peak-to-peak (20 MHz bandwidth)
Efficiency 84% typical
Protection Features Output over-voltage (automatic latch-off), short-circuit and overload (automatic recovery)
Operating Temperature 0 to 70 °C (Derating applies above 50 °C for natural convection)
MTBF > 40,000 hours at 70 °C (MIL-HDBK-217F)

 

Detailed Product Overview

The VM600 RPS6U serves as the primary electrical power source for the VM600 machinery protection system architecture. Installed in the front card cage of a 19-inch, 6U ABE04x system rack, it connects directly to the VME bus backplane via high-current DIN connectors. The module converts standard AC mains power into the precise DC voltage rails required by the system’s processing, I/O, and relay cards.

A critical design feature of the RPS6U is its support for system-level redundancy. While a single 330 W unit can power a fully populated rack at ambient temperatures up to 50 °C, installing two RPS6U modules enables redundant operation. In this configuration, if one power supply fails, the remaining unit automatically assumes 100% of the load, preventing system interruption. Alternatively, dual units can operate non-redundantly to prevent power derating in environments exceeding 50 °C.

The module incorporates robust internal safeguards. Over-voltage conditions trigger an automatic latch-off to protect downstream electronics, while short-circuit and overload conditions initiate automatic recovery once the fault is cleared. Status is continuously monitored via front-panel LEDs indicating the presence of the external mains supply (“IN”) and the normal generation of the +5 VDC, +12 VDC, and -12 VDC rails.

VM600 RPS6U 200-582-500-013

VM600 RPS6U 200-582-500-013

VM600 RPS6U 200-582-500-013

VM600 RPS6U 200-582-500-013

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Supported Rack Systems VM600 ABE04x (6U) system racks Installs in the front card cage (slots 15–17 or 18–20).
Backplane Interface Two high-current DIN 41612 type H15 connectors Routes power to all installed front and rear modules.
Companion Modules MPC4, IOC4T, CMC16, RLC16, CPUM, etc. Powers all VM600 series cards within the same chassis.
Redundancy Configuration Compatible associated rear panel Required (e.g., PNR 200-582-960-NHh or 200-582-962-NHh) to support dual independent AC inputs for external mains redundancy.
Environmental Constraint Natural convection vs. forced-air cooling Natural convection requires output power derating above 50 °C. Forced-air cooling eliminates this derating requirement.

 

Dimensions, Mounting & Connection Notes

  • Form Factor: 6U Eurocard format (262 mm height × standard rack width × approx. 187 mm depth).
  • Mounting Method: Front-panel insertion into the VM600 ABE04x rack card cage.
  • Connection Type: Rear-facing high-current DIN 41612 type H15 connectors mate with the rack backplane. External AC power is routed through a designated associated rear panel (e.g., IEC C14 socket or screw-terminal block).
  • Weight: Approximately 2.4 kg.
  • Installation Constraint: DC-input rear panels do not include internal fuses; an appropriately rated external circuit breaker is mandatory for DC configurations. AC rear panels include integrated fuses and EMI filters.

 

FAQ

What is the function of the Vibro-Meter VM600 RPS6U 200-582-500-013?
It is the primary AC-input rack power supply for the VM600 machinery protection system, converting mains AC power into regulated +5 VDC, +12 VDC, and -12 VDC rails for all installed modules.

Can the RPS6U be configured for redundant operation?
Yes. Two RPS6U modules can be installed in a single ABE04x rack. In a redundant configuration, if one unit fails, the other automatically supplies 100% of the rack’s power requirements.

What is the maximum output power of this module?
The maximum total combination output power is 330 W. This is shared across the +5 VDC, +12 VDC, and -12 VDC rails, with maximum current limits of 50 A, 8 A, and 4 A, respectively.

Does the RPS6U require external cooling?
The module is designed for natural convection cooling up to 50 °C. Above this temperature, output power derating applies unless forced-air cooling is provided within the enclosure.

How is the RPS6U connected to the external power source?
It connects to an associated rear panel installed at the back of the rack. The rear panel provides the physical AC input interface (mains socket or screw terminals), fuses, and EMI filtering before routing power to the RPS6U.

 

Documented Performance Data

Metric Value / Range Test / Operating Condition
Efficiency 84% typical At nominal line input and maximum combination load
Line Regulation < ±1% for all outputs ±10% change in nominal input
Load Regulation < ±1% for +5 VDC
< ±2% for ±12 VDC
±40% change from 60% max output power
Interruption Tolerance 10 ms (single unit)
20 ms (dual units)
At 100% combination load without resetting modules
MTBF > 40,000 hours Calculated at 70 °C per MIL-HDBK-217F