Sale!

Woodward 8440-2165 SPM-D2-1115B/LSXR Generator Synchronizer

Item Verified value
Manufacturer Woodward
Part number 8440-2165
Product model SPM-D2-1115B/LSXR
Product family SPM-D2-11
Product type Digital synchronizer and load-sharing controller
Generator / bus voltage sensing Two-phase, 100 VAC nominal
Nominal voltage range 63/110 VAC
Maximum voltage 150 VAC
Current sensing Single-phase CT, /5 A

Description

Core Product Summary

The Woodward 8440-2165 is the SPM-D2-1115B/LSXR digital synchronizer and load-sharing controller for two- or three-phase AC generator sets. It automatically matches generator frequency, phase, and voltage before breaker closure, then provides active- and reactive-power sharing during parallel operation.

This 8440-2165 version provides 100 VAC generator and bus voltage measurement inputs and a single-phase current-transformer input configured for /5 A current transformers. It is intended for use with compatible speed controls and automatic voltage regulators and combines synchronizing, load and power-factor control, generator protection, and a front-panel synchroscope in one unit.

 

Key Technical Specifications

Item Verified value
Manufacturer Woodward
Part number 8440-2165
Product model SPM-D2-1115B/LSXR
Product family SPM-D2-11
Product type Digital synchronizer and load-sharing controller
Generator / bus voltage sensing Two-phase, 100 VAC nominal
Nominal voltage range 63/110 VAC
Maximum voltage 150 VAC
Current sensing Single-phase CT, /5 A
Linear current-measuring range 3.0 × IN
Measuring frequency 50/60 Hz, 40 to 70 Hz
Voltage-measurement accuracy Class 1
Supply voltage 12/24 VDC, 9.5 to 32 VDC
Power consumption Maximum 8 W
Operating temperature -20°C to +70°C
Relative humidity 95%, non-condensing
Display Two-line bright LCD
Configuration HMI or Woodward ToolKit software via USB
Dimensions 142 × 72 × 122 mm
Weight Approximately 800 g
Front-panel protection IP42; IP54 with sealing kit 8923-1037
Rear protection IP20
Approvals CE marked; UL/cUL listed for ordinary locations

 

Detailed Product Overview

The Woodward 8440-2165 belongs to the SPM-D2-11 synchronizer family. It is configured as the /LSXR version, which uses single-phase, two-wire voltage measurement for the generator and bus, single-phase current-transformer measurement, analog kW and kVAR load-sharing lines, and generator protection.

Before a generator breaker closes, the controller performs frequency, zero-phase, and voltage synchronization. It can use analog or digital control signals to adjust the connected speed control and automatic voltage regulator, bringing the generator into the required synchronizing condition.

After paralleling, the 8440-2165 supports active-power and reactive-power sharing through two analog load-sharing lines. It also provides active-power and power-factor control in grid-parallel operation, and voltage and frequency regulation in island operation.

The controller includes generator protection functions for over/under-voltage, over/under-frequency, overload, reverse power, and under-power conditions. Its front panel provides a two-line LCD for operating values, alarms, and parameter setting, together with a synchroscope and breaker-state indication for commissioning and operation.

Configuration is password protected and can be performed locally through the HMI or through Woodward ToolKit software over USB. The SPM-D2-11 is designed for use with compatible Woodward or other manufacturers’ speed controls and AVRs, with control outputs configurable as digital potentiometer signals or analog signals.

8440-2165

8440-2165

8440-2165

8440-2165

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Generator type Two- or three-phase AC generator The SPM-D2-11 is specified for use with these generator types.
Speed control Compatible Woodward or other manufacturer governor The controller adjusts speed through digital potentiometer or configurable analog/PWM outputs.
Voltage regulator Compatible Woodward or other manufacturer AVR The controller adjusts voltage through digital potentiometer or configurable analog outputs.
Voltage measurement 100 VAC nominal, 63/110 VAC range The 8440-2165 is the 100 VAC measuring-input version.
Current measurement Single-phase CT, /5 A Use a current transformer with a /5 A secondary.
Load sharing Analog kW and kVAR load-sharing lines Two analog lines support active- and reactive-power sharing.
Configuration HMI or Woodward ToolKit via USB Password protection is provided for parameters.
Supply 12/24 VDC, 9.5 to 32 VDC Provide a DC supply within the stated range.
Grid-parallel operation Additional network-decoupling relay required Woodward identifies an easYprotec or HighPROTEC relay as required for this function.

 

Dimensions, Mounting & Connection Notes

The 8440-2165 is a panel-front-mount controller in APRANORM DIN 43 700 format. Its housing measures 142 × 72 × 122 mm, and the required front-panel cutout is 138 × 68 mm, with stated tolerances of +1.0 mm in width and +0.7 mm in height.

Connections use screw or plug-in terminals suitable for 1.5 mm² or 2.5 mm² conductors. A back-plate mounting option is available using mounting brackets, Woodward part number 8923-1023.

With correct installation, the front panel is rated IP42, or IP54 when fitted with sealing kit 8923-1037; the rear of the unit is rated IP20. The controller weighs approximately 800 g.

 

FAQ

What is Woodward 8440-2165?
It is the Woodward SPM-D2-1115B/LSXR digital synchronizer and load-sharing controller for generator paralleling applications.

What voltage-measurement configuration does 8440-2165 use?
It uses 100 VAC nominal generator and bus voltage measurement, with a 63/110 VAC nominal range and 150 VAC maximum voltage.

Which current transformers does it require?
It uses a single-phase current-transformer input configured for /5 A current transformers.

What control functions does it provide?
It provides synchronization for one breaker, active- and reactive-power sharing, active-power and power-factor control, island-mode voltage and frequency regulation, and generator protection.

Which speed controls and AVRs can it work with?
It is designed for use with compatible Woodward or other manufacturers’ speed controls and automatic voltage regulators.

How is the controller configured?
It can be configured through its HMI or through Woodward ToolKit software using the USB connection.

What are its mounting dimensions?
The housing is 142 × 72 × 122 mm, with a 138 × 68 mm front-panel cutout.

What approvals apply to the SPM-D2-11 series?
The series is CE marked and UL/cUL listed for ordinary locations.

 

Documented Performance Data

Metric Value/range Test/operating condition
Voltage-measurement accuracy Class 1 Generator and bus two-phase RMS voltage measurement
Measuring frequency 50/60 Hz; 40 to 70 Hz Generator and bus measurement
Linear voltage-measuring range 1.25 × VN 100 VAC nominal measuring-input version
Linear current-measuring range 3.0 × IN /5 A current-transformer input
Power consumption Maximum 8 W Controller operating specification
Operating temperature -20°C to +70°C Controller operating specification
Relative humidity 95%, non-condensing Controller operating specification