Description
Key Technical Specifications
| Parameter | Value |
|---|---|
| Manufacturer | Yokogawa Electric Corporation |
| Model | NFPW444 |
| Typical order code | NFPW444-50 |
| Compatible system | Yokogawa STARDOM FCN / FCN-RTU |
| Compatible base modules | NFBU050 and NFBU200 |
| Rated input voltage | 24 VDC |
| Input voltage range | 21.6–31.2 VDC |
| Maximum input current | 3.3 A |
| Internal fuse | 6.3 A |
| Maximum inrush current | 20 A |
| System output | +5.1 VDC, 0–7.8 A rated; 11.8 A peak |
| Total system output power | 40 W rated; 60 W peak |
| Analog field power output | 24 VDC, maximum 4 A |
| Redundancy | 1:1 redundant configuration supported |
| Hot-swap capability | Supported |
| Status LEDs | SYS for +5 V system power; FLD for +24 V field power |
| Check terminals | +5 V and +24 V |
| Operating temperature | 0 to 55°C; -20 to 70°C for NFPW444 |
| Derating | Above 55°C, limit output current to 75% of rated value |
| Weight | 0.6 kg |
The Yokogawa NFPW444 is a 24 VDC input power supply module for STARDOM FCN and FCN-RTU systems. It provides +5.1 VDC system power at up to 7.8 A and 24 VDC analog field power at up to 4 A, and it supports 1:1 redundant and hot-swappable configurations.
Product Introduction
The Yokogawa NFPW444 supplies regulated power to the FCN-RTU CPU, I/O modules, SB bus, and analog field circuits. It mounts on NFBU050 or NFBU200 base modules and distributes both +5.1 VDC system power and 24 VDC analog field power.
Its main advantage is availability of redundancy: two NFPW444 modules can be configured for 1:1 redundant operation, while the module itself supports hot-swap replacement. The front-panel SYS and FLD LEDs and +5 V/+24 V check terminals simplify power-status verification during commissioning and maintenance.

NFPW444

NFPW444
Troubleshooting Quick Reference
| Symptom | Possible Cause | Relevance to this Part | Quick Check Method | Recommendation |
|---|---|---|---|---|
| SYS LED off | 24 VDC input loss, blown fuse, poor module seating, or failed power module | ✅ High | Measure 24 VDC at the input terminals and +5.1 VDC at the check terminal | Verify input power and module seating before replacing |
| FLD LED off | 24 VDC field-power circuit fault, wiring issue, or overloaded field supply | ✅ High | Measure 24 VDC at the FLD check terminal and inspect field-power load | Reduce or isolate field load; replace module if input is normal but output remains absent |
| CPU or I/O modules offline | Insufficient +5 V system output, poor backplane contact, or excessive I/O load | ✅ High | Measure +5 V at the check terminal and calculate total I/O power consumption | Verify the load stays within 7.8 A rated output; replace only after load and seating checks |
| Intermittent power loss | Loose terminals, corroded contacts, thermal derating, or failing power module | ✅ High | Check terminal torque, module seating, cabinet temperature, and output voltage under load | Correct connections and cooling; replace if voltage drops persist |
| Module overheats | High ambient temperature, blocked ventilation, or excessive output load | ✅ Medium | Measure cabinet temperature and compare load with the 40 W rated / 60 W peak limits | Improve airflow or reduce load; apply 75% derating above 55°C |
| Redundancy alarm | Mismatched modules, failed secondary PSU, wiring issue, or configuration error | ✅ High | Verify both modules are NFPW444, correctly seated, and supplying valid output voltages | Replace the failed module; do not mix incompatible power-module types |
| Blown input fuse repeatedly | Shorted field circuit, wiring fault, or internal power-module failure | ✅ High | Disconnect field loads and measure input current; inspect for short circuits | Correct the short before installing a replacement module |
If the fault remains unresolved, send photos of the NFPW444 nameplate, base module, wiring, LED status, and voltage measurements before ordering a replacement.
Frequently Asked Questions
Can I hot-swap the Yokogawa NFPW444?
Yes. In a properly configured redundant system, the NFPW444 supports hot-swap replacement. For a single, non-redundant power configuration, shut down the FCN system before removing the module. Use a grounded ESD wrist strap and follow site lockout/tagout procedures.
Is the NFPW444 obsolete?
Some NFPW444 submodels have been phased out. The module remains a legacy Yokogawa STARDOM FCN/FCN-RTU power supply, so current supply is generally limited to New Surplus, refurbished, or tested pre-owned inventory.
Can I use two NFPW444 modules for redundancy?
Yes. The NFPW444 is the FCN-RTU power module that supports 1:1 redundant configuration. Both modules should be the same compatible model and correctly configured on the supported base module.
Will it fit an NFBU050 base module?
Yes. Yokogawa specifies the NFPW444 for both NFBU050 and NFBU200 base modules. Confirm the exact base-module model and available slot before installation.
Can I use an NFPW426 and NFPW444 together?
No. Yokogawa states that when NFPW426 and NFPW444 are used in combination, only one module can be used. Do not mix them in a redundant configuration.
Why is this surplus module less expensive than a new OEM unit?
Because Yokogawa has phased out some NFPW444 submodels, pricing reflects available surplus inventory rather than current OEM production. New Surplus stock is unused original product; it may have older date codes but should not have field-operating hours.
What should I check before ordering?
Confirm the exact suffix, such as NFPW444-50, the FCN base-module model, 24 VDC input availability, total +5 V and +24 V load, redundancy requirement, and ambient temperature. Above 55°C, Yokogawa restricts the NFPW444 to 75% of its rated output current.