Sale!

Yokogawa PW482-11 | AC Power Supply Module for CENTUM VP

The Yokogawa PW482-11 is an AC-input power supply module for the Yokogawa CENTUM VP distributed control system, also used in CENTUM CS 3000 hardware. The PW482 model family supplies conditioned power to Field Control Units (FCUs), FIO node units, and optical ESB bus repeater units, converting a 220–240 VAC ±10%, 50/60 Hz ±3 Hz mains input into the internal system voltages with a maximum power consumption of 230 VA. The -11 suffix identifies a specific hardware style of the PW482 module.

Categories: , , , , SKU: PW482-11 Brand:

Description

Core Product Summary

The Yokogawa PW482-11 is an AC-input power supply module for the Yokogawa CENTUM VP distributed control system, also used in CENTUM CS 3000 hardware. The PW482 model family supplies conditioned power to Field Control Units (FCUs), FIO node units, and optical ESB bus repeater units, converting a 220–240 VAC ±10%, 50/60 Hz ±3 Hz mains input into the internal system voltages with a maximum power consumption of 230 VA. The -11 suffix identifies a specific hardware style of the PW482 module.

The module installs into the dedicated power supply slots (P1–P2) of the supported base plates. A single configuration occupies slot P1; a dual-redundant configuration uses two identical PW482 modules in P1 and P2 so that one module can continue powering the unit if the other fails. Supported hosts include FCUs AFV30D/S and A2FV50D/S, A2FV70D/S, FIO node units ANB10D/S and ANB11D/S, and the optical ESB bus repeater unit ANT10U on base plates A2BE1D and A2BE2D. Power wiring terminates at the module’s power supply terminals with M4 screws.

 

Key Technical Specifications

Parameter Value
Product type AC-input power supply module for DCS node units
Model family Yokogawa PW482
Input voltage 220–240 V AC ±10%
Input frequency 50/60 Hz ±3 Hz
Maximum power consumption 230 VA
Installation slots P1–P2 (single configuration: slot P1)
Redundancy Dual-redundant with two identical PW482 modules
Power terminals M4 screw terminals
Host systems CENTUM VP / CENTUM CS 3000

 

Engineering Selection Highlights

  • Input voltage class — The PW482 is the 220–240 VAC ±10% member of the PW48x supply family; it must not be ordered for cabinets wired for 100–120 VAC or 24 VDC supplies, which use the corresponding PW481 and PW484 modules.
  • Slot discipline — Power supply modules occupy only slots P1–P2 on the base plate. In a single configuration the module must sit in P1, so a spare slot plan should reserve P2 for a future redundancy upgrade.
  • Redundancy requires identical modules — Dual-redundant operation is enabled only by installing two modules with the same model code; mixing different PW48x models in P1/P2 is not a supported redundant pair.
  • Host compatibility is defined per unit type — Supported FCUs are AFV30D/S, A2FV50D/S, and A2FV70D/S; supported FIO node units are ANB10D/S and ANB11D/S; the optical ESB bus repeater unit ANT10U and base plates A2BE1D/A2BE2D are also supported hosts.
  • M4 power terminals — Cabinet power wiring must be prepared with M4 ring/lug terminations and appropriately sized conductors for the 230 VA maximum draw.
  • Consumption budget — The 230 VA maximum input consumption at 220–240 VAC is the figure Yokogawa documents for node-unit power budgeting; use it, not the module’s output rating, when sizing upstream breakers and UPS capacity.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
FCU hosts AFV30D, AFV30S, A2FV50D, A2FV50S, A2FV70D, A2FV70S Confirm the exact FCU model before ordering spares
FIO node units ANB10D, ANB10S, ANB11D, ANB11S Same power module family covers both node types
Optical ESB bus repeater ANT10U Also powered by PW48x modules
Base plates A2BE1D, A2BE2D Power modules install in the P1–P2 slots
Redundant configuration 2 identical PW482 modules (same model code) Mixed model codes are not a valid redundant pair
Input supply 220–240 V AC ±10%, 50/60 Hz ±3 Hz Match cabinet mains class; other classes use PW481/PW484
Power connection M4 screw terminals Prepare terminations accordingly

 

Detailed Product Overview

The Yokogawa PW482-11 belongs to the PW48x power supply module family that Yokogawa designed for the node-level hardware of its CENTUM distributed control systems. Within that family, model PW481 covers 100–120 VAC input, PW484 covers 24 VDC input, and PW482 covers 220–240 VAC input. Selecting the correct family member is therefore the first and most consequential decision: the modules are host-compatible, but each accepts only its own input voltage class, so a PW482 ordered into a low-voltage cabinet cannot be compensated for at installation time.

Functionally, the module occupies the power supply slot of a base plate and converts the incoming mains into the internal supply rails for the unit’s electronics. At 220–240 VAC input, Yokogawa documents a maximum power consumption of 230 VA per node unit, which is the figure to use when sizing feeders, breakers, and any UPS protecting the cabinet. Input frequency tolerance of ±3 Hz around 50/60 Hz covers normal supply variation in both major grid standards.

Installation follows fixed slot rules. The module fits slots P1 and P2 only, and a non-redundant configuration requires slot P1. Redundancy is achieved by populating both slots with two modules carrying the same model code — a rule worth highlighting because it means a redundancy upgrade is a planned two-module purchase, not a mixed pair assembled from available spares. Power conductors land on M4 screw terminals, so termination hardware should match that size.

For maintenance planning, the PW482-11 functions as the standard replacement part for 220–240 VAC power supply faults in supported FCUs, FIO node units, and ESB bus repeater units. Because the module family is shared across multiple unit types, holding one verified spare can cover several different node types in the same cabinet cluster. Verification before installation should confirm the host unit model is one of the documented supported types and that the unit’s input wiring matches the 220–240 VAC class.

PW482-11

PW482-11

PW482-11

PW482-11

Applications & System Role

In a CENTUM VP or CENTUM CS 3000 architecture, the PW482-11 sits at the power entry point of a node unit. FCUs execute continuous control and interlock functions; FIO node units aggregate field I/O; and optical ESB bus repeater units extend the ESB bus segment between cabinets. Each of these units depends on a PW48x supply module to convert cabinet AC mains into the regulated internal voltages that run the processor, communication, and I/O electronics on the base plate.

Because these units can run on a single supply, the PW482 also serves as the building block for power redundancy: two identical modules share the load path so that the node keeps operating through a single module failure. For engineering and procurement teams, the module is a planned spare part for any 220–240 VAC CENTUM VP node with slot P2 empty or populated.

 

FAQ

What is the Yokogawa PW482-11?
It is a 220–240 VAC input power supply module used in Yokogawa CENTUM VP and CENTUM CS 3000 node hardware; the -11 suffix identifies a specific hardware style of the PW482 model.

Where is the PW482-11 installed?
It installs in the P1–P2 power supply slots of supported base plates inside FCUs (AFV30D/S, A2FV50D/S, A2FV70D/S), FIO node units (ANB10D/S, ANB11D/S), and the optical ESB bus repeater unit ANT10U.

What input voltage does the PW482-11 require?
It requires 220–240 V AC ±10% at 50/60 Hz ±3 Hz. It is not the correct module for 100–120 VAC or 24 VDC supplies, which use PW481 and PW484 respectively.

How is power redundancy configured with this module?
A dual-redundant configuration uses two identical PW482 modules with the same model code installed in slots P1 and P2; in a single configuration, only slot P1 is populated.

How much power does the module draw?
Maximum power consumption is 230 VA, which is the value to use for cabinet power budgeting at the 220–240 VAC input class.

What terminations does the module use for power wiring?
The power supply terminals accept M4 screws, so field wiring should be prepared with matching M4 terminations.

Which systems use the PW482 family?
The module family powers node units of the CENTUM VP distributed control system, including units carried over from CENTUM CS 3000 hardware generations.