Description
Core Product Summary
The Yokogawa S2BN5D-121 is a base plate for barrier used in N-IO I/O units. It allows mounting of I/O modules and Pepperl+Fuchs (P+F) intrinsic safety barriers, providing field signal connection via spring clamp terminals and communication to the node interface unit via the F-SB bus. It is designed for wall mounting and supports explosion protection applications within the ProSafe-RS / N-IO system architecture.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Manufacturer | Yokogawa Electric Corporation |
| Model | S2BN5D-121 |
| Product type | Base Plate for Barrier (for N-IO, P+F) |
| System model | Part of S2ZN5D N-IO I/O Unit |
| Mounting | Wall mount (M4 screws) |
| Field terminals | Spring clamp |
| Number of I.S. barriers | Up to 16 |
| Number of channels | 16 |
| Compatible I/O modules | S2MMM843, S2MDV843 |
| Compatible barriers | Pepperl+Fuchs H-System (HiC series) |
| Communication | F-SB bus (via S2KLF10 cable) |
| System power | Via power supply cable for base plate (S2KPB10) |
| Withstanding voltage (field–system) | 1500 V AC for 1 minute |
| Weight (without barriers) | Approx. 1.24 kg |
Detailed Product Overview
The S2BN5D base plate serves as the mounting and interconnection platform for N-IO I/O modules and Pepperl+Fuchs intrinsic safety barriers. Field signals are connected directly to the spring clamp terminals on the base plate. The base plate communicates with the node interface unit over the F-SB bus and distributes system power to the mounted I/O modules.
It supports both single and dual-redundant I/O module configurations. Up to 16 P+F I.S. barriers can be installed. Barrier power is supplied through a dedicated interface. The design allows field cable fault detection (disconnection/short-circuit) when properly engineered with compatible barriers and I/O modules.
The S2BN5D-121 variant is the wall-mount version with spring clamp field terminals and explosion protection capability.

S2BN5D-121

S2BN5D-121
System Compatibility & Integration Requirements
- Used in Yokogawa N-IO systems (system model S2ZN5D) within ProSafe-RS safety instrumented systems.
- Requires compatible Node Interface Unit and F-SB bus cabling (S2KLF10).
- Power connection via S2KPB10 power supply cable for base plate.
- Compatible I/O modules: S2MMM843 (Analog/Digital I/O) and S2MDV843 (Digital I/O).
- Compatible with specified Pepperl+Fuchs H-System barriers (e.g., HiC2025, HiC2031, HiC2831, HiC2873, HiC2883 and related variants).
- Dummy covers (S2DCV02) must be fitted to unused I/O module slots.
- Engineering configuration of barrier and I/O module parameters is required for correct line-fault detection.
- Installation is vertical wall mounting only. Follow Yokogawa installation environmental standards and explosion-protection requirements.
Dimensions / Mounting
Wall-mounted using M4 screws (screws prepared separately). Vertical orientation only.
FAQ
What is the Yokogawa S2BN5D-121?
It is a wall-mount base plate for barrier that accepts N-IO I/O modules and Pepperl+Fuchs intrinsic safety barriers in Yokogawa N-IO / ProSafe-RS systems.
What terminals does it use for field wiring?
Spring clamp terminals.
How many barriers can be mounted?
Up to 16 intrinsic safety barriers (16 channels).
Which I/O modules are supported?
S2MMM843 and S2MDV843.
What is the primary system application?
N-IO I/O units requiring intrinsic safety barriers for hazardous-area field devices.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626