Description
Core Product Summary
The Yokogawa SDV144-S63 is a 16-channel digital input module for Yokogawa ProSafe-RS safety control systems. It accepts voltage-free contact signals from field devices and provides module isolation between the input signals and the system.
The -S63 configuration includes a signal cable interface adapter, no explosion-protection construction, ISA Standard G3 coating, and an operating temperature range of -20 to 70 °C. It connects to field wiring through the AKB331 dedicated signal cable and supports dual-redundant operation when configured with compatible terminal hardware. The module is intended for installation in a ProSafe-RS Safety Node Unit or Safety Control Unit.
Key Technical Specifications
| Item | Specification |
|---|---|
| Manufacturer / model | Yokogawa SDV144-S63 |
| Product type | Digital input module |
| System family | Yokogawa ProSafe-RS |
| Number of inputs | 16 channels |
| Input type | No-voltage contact |
| Isolation | Module isolation |
| ON condition | 1 kΩ maximum |
| OFF condition | 100 kΩ minimum |
| Input current | 6 mA ± 20% at 24 V DC external supply and 0 Ω input |
| Contact rating | 24 V DC +20% / -10%, 10 mA or greater |
| External power supply | 24 V DC +20% / -10%; 200 mA current capacity |
| Maximum instantaneous input voltage | 30.0 V DC |
| Input response time | 40 ms maximum |
| Withstand voltage | 2 kV AC for 1 minute between input signal and system, with 16 input lines collectively connected |
| Current consumption | 290 mA maximum at 5 V DC; 140 mA maximum at 24 V DC |
| Environmental rating | ISA Standard G3 |
| Operating temperature | -20 to 70 °C |
| External connection | Dedicated signal cable, AKB331 |
| Weight | Approximately 0.41 kg with signal cable interface adapter |
| Dimensions with adapter | 124 × 94 × 130 mm (W × H × D) |
Detailed Product Overview
The Yokogawa SDV144-S63 converts field contact states into digital data for a ProSafe-RS safety control unit or safety node unit. Its 16 input channels accept no-voltage contacts such as relay contacts, limit switches, and other dry-contact field devices. Module isolation separates the field input circuits from the system side, supporting electrical separation between field wiring and the safety controller.
The module’s input thresholds define the wiring and contact requirements for correct signal recognition. An ON state requires no more than 1 kΩ total circuit resistance, while an OFF state requires at least 100 kΩ. The input draws approximately 6 mA under the specified 24 V DC external-supply condition, and the external supply must provide a 200 mA current capacity.
The -S63 suffix identifies a module with a signal cable interface adapter, ISA Standard G3 coating, and a -20 to 70 °C operating range. Because the adapter is structurally integrated with the module, field connection is made through the AKB331 dedicated signal cable rather than a pressure-clamp terminal block or MIL cable. This configuration is appropriate where a terminal board or relay board provides the field-side termination.
The SDV144 family supports dual-redundant configuration. For a redundant installation, Yokogawa specifies an additional module with the same specification but without option codes, connected through compatible dual-redundant terminal hardware. The module also supports field-wiring diagnostics when SCB100 or SCB110 wiring-check adapters are installed near the field equipment: SCB100 supports open-circuit detection for normally OFF signals, while SCB110 supports short-circuit detection for normally ON signals.
Dimensions, Mounting & Connection Notes
The SDV144-S63 measures 124 mm wide, 94 mm high, and 130 mm deep with its signal cable interface adapter. Its weight is approximately 0.41 kg in this configuration.
The module mounts in a Yokogawa ProSafe-RS Safety Node Unit or Safety Control Unit. The -S63 version uses the integrated signal-cable interface adapter and connects through an AKB331 dedicated signal cable; pressure-clamp terminal-block and MIL-cable options are not used with this suffix.
For field power, connect the positive terminal of the external 24 V DC supply to the 24 V DC terminal and the negative terminal to COM. The documented field-wiring guidance recommends a floating field power supply for higher noise immunity and states that the secondary side of the field power supply connected to the digital input module should not be grounded.
For pressure-clamp terminations used elsewhere in the SDV144 family, Yokogawa documents 0.5 to 2 mm² (AWG 20 to 14) wire without sleeve and 0.5 to 1.5 mm² (AWG 20 to 16) wire with sleeve. These wire-size values apply to pressure-clamp terminal connections, not to the AKB331 signal-cable connection used by the SDV144-S63.

SDV144-S63

SDV144-S63
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control system | Yokogawa ProSafe-RS | Installs in a Safety Node Unit or Safety Control Unit |
| I/O architecture | Yokogawa FIO | The SDV144 is an FIO digital input module |
| Field signal | No-voltage contact | ON: 1 kΩ maximum; OFF: 100 kΩ minimum |
| Field power | 24 V DC +20% / -10%, 200 mA capacity | Connect the positive supply to the 24 V DC terminal and negative to COM |
| Field connection | AKB331 dedicated signal cable | Required by the -S6 signal-cable-interface-adapter configuration |
| Terminal board | SED4D | Supported for dedicated signal-cable connection |
| Redundant terminal board | SBD4D | Supports dual-redundant SDV144 connection |
| Relay read-back | SRM53D or SRM54D | The SDV144 can read back relay output status |
| Redundant module | Additional SDV144 with the same specification, without option codes | Required for dual-redundant configuration |
| Wiring diagnostics | SCB100 and/or SCB110 | Installed near field equipment for open- or short-circuit detection |
| False-insertion prevention | /PRP option and AKB331 cable with /SDV144 option | The prevention pin is available only with the signal-cable-interface-adapter configuration |
FAQ
What is the Yokogawa SDV144-S63?
It is a Yokogawa ProSafe-RS 16-channel digital input module for voltage-free contact signals, with module isolation and a signal cable interface adapter.
How many input channels does the SDV144-S63 provide?
It provides 16 digital input channels with module isolation.
What type of field signal does it accept?
It accepts no-voltage contact signals. An ON input requires 1 kΩ maximum resistance and an OFF input requires 100 kΩ minimum resistance.
What external power supply does it require?
It requires a 24 V DC external supply within +20% / -10%, with a current capacity of 200 mA.
Which cable connects the SDV144-S63 to field wiring?
The AKB331 dedicated signal cable connects the module’s integrated signal cable interface adapter to a compatible terminal board or relay board.
Can the SDV144-S63 be used in a redundant configuration?
Yes. The SDV144 can be made dual-redundant; a redundant installation uses an additional module with the same specification but without option codes and compatible dual-redundant terminal hardware.
What environmental protection does the -S63 suffix provide?
The suffix indicates ISA Standard G3 coating and an operating temperature range of -20 to 70 °C.
Can it detect field-wiring faults?
Yes, when SCB100 or SCB110 wiring-check adapters are installed. SCB100 supports open-circuit detection for normally OFF inputs, and SCB110 supports short-circuit detection for normally ON inputs.
Documented Performance Data
| Metric | Value / Range | Operating Condition |
|---|---|---|
| Input response time | 40 ms maximum | SDV144 digital input module |
| Input current | 6 mA ± 20% | External 24 V DC supply at 0 Ω input |
| Withstand voltage | 2 kV AC for 1 minute | Between input signal and system, 16 input lines collectively connected; floating field power supply |
| Event time-stamp resolution | 1 ms | Digital input module event collection in ProSafe-RS |