Sale!

Yokogawa SPW481 Dual-Redundant Compatible Power Supply Module

The Yokogawa SPW481 is a 100–120 V AC input power supply module for CENTUM VP Field Control Units (FCU), FIO node units, and optical ESB bus repeater units. It converts AC input power into the regulated DC voltages required by the system backplane and modules.

Categories: , , , , SKU: SPW481 Brand:

Description

Core Product Summary

The Yokogawa SPW481 is a 100–120 V AC input power supply module for CENTUM VP Field Control Units (FCU), FIO node units, and optical ESB bus repeater units. It converts AC input power into the regulated DC voltages required by the system backplane and modules.

The module supports single or dual-redundant installation in slots P1 and P2. Maximum power consumption is 200 VA. It is designed for use with compatible Yokogawa control and safety system hardware and connects via a dedicated system connector.

Key Technical Specifications

Parameter Value
Model SPW481 (PW481 series)
Product type AC input power supply module
Input voltage 100–120 V AC ±10 %
Input frequency 50/60 Hz ±3 Hz
Maximum power consumption 200 VA
Weight Approx. 1 kg
Interface Dedicated system connector
Mounting slots P1–P2 (dual-redundant capable)
Compatible units FCU (AFV30D/S, A2FV50D/S, A2FV70D/S), FIO Node Units (ANB10D/S, ANB11D/S), Optical ESB Bus Repeater (ANT10U), Base Plates (A2BE1D, A2BE2D)
Redundancy Dual-redundant by installing two identical modules

Detailed Product Overview

The Yokogawa SPW481 belongs to the PW48x series of power supply modules used in CENTUM VP distributed control systems and related ProSafe-RS safety architectures. It provides the primary AC-to-DC conversion for Field Control Units, FIO node units, and optical ESB bus repeater units.

The module accepts a nominal 100–120 V AC supply with ±10 % tolerance at 50/60 Hz (±3 Hz). Maximum power consumption is specified at 200 VA. Output power is delivered through a proprietary connector that mates directly with the system backplane, supplying the voltages required by CPU, I/O, and communication modules.

Installation occurs in dedicated power slots P1 and P2. A single module is placed in slot P1 for non-redundant configurations. Dual-redundant operation is achieved by installing two identical modules of the same model code, allowing continued system power availability if one module is removed or fails.

Suffix options define environmental and protection characteristics. Standard versions without explosion protection and versions with explosion protection are available. An ISA Standard G3 option with extended temperature range (–20 °C to 70 °C) is also offered for corrosive or wide-temperature environments.

The module is intended exclusively for the listed Yokogawa units. All other environmental and installation specifications follow those of the host FCU, node unit, or repeater in which it is installed.

SPW481

SPW481

SPW481

SPW481

Dimensions, Mounting & Connection Notes

The module installs in the power supply slots (P1–P2) of compatible Field Control Units, FIO node units, optical ESB bus repeater units, or base plates. Connection is made via the dedicated backplane connector. Exact outline dimensions and terminal details are defined in the host unit hardware documentation. Approximate weight is 1 kg.

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Host units FCU: AFV30D/S, A2FV50D/S, A2FV70D/S; FIO Node: ANB10D/S, ANB11D/S; Optical ESB Repeater: ANT10U; Base Plates: A2BE1D/2D Must match system hardware
Input power 100–120 V AC ±10 %, 50/60 Hz ±3 Hz Maximum 200 VA
Mounting Slots P1–P2 Single: P1 only; Dual-redundant: two identical modules
Connector Dedicated system connector Not for general-purpose use
Redundancy Supported with two identical modules Same model code required

FAQ

What is the Yokogawa SPW481?
It is a 100–120 V AC input power supply module for Yokogawa CENTUM VP Field Control Units, FIO node units, and optical ESB bus repeater units.

What is the input voltage range?
100–120 V AC ±10 % at 50/60 Hz ±3 Hz.

What is the maximum power consumption?
200 VA.

Can it be used in a redundant configuration?
Yes. Dual-redundant operation is achieved by installing two identical modules in slots P1 and P2.

Which units is it compatible with?
FCU models AFV30D/S, A2FV50D/S, A2FV70D/S; FIO node units ANB10D/S, ANB11D/S; optical ESB bus repeater ANT10U; and base plates A2BE1D/A2BE2D.

How is the module connected?
It uses a dedicated system connector that mates with the host unit backplane.