Sale!

Yokogawa YNT512D Dual-Redundant V net Bus Repeater Module

The Yokogawa YNT512D is a dual-redundant bus repeater module designed to extend the transmission distance and maintain signal integrity within Yokogawa CENTUM VP, CENTUM CS 3000, and ProSafe-RS control networks. It is specifically engineered for use with V net, RIO bus, and VL net communication architectures. By amplifying and retransmitting control signals, this module allows system integrators to overcome standard coaxial cable length limitations without degrading network performance.

Categories: , , , , SKU: YNT512D Brand:

Description

Core Product Summary

The Yokogawa YNT512D is a dual-redundant bus repeater module designed to extend the transmission distance and maintain signal integrity within Yokogawa CENTUM VP, CENTUM CS 3000, and ProSafe-RS control networks. It is specifically engineered for use with V net, RIO bus, and VL net communication architectures. By amplifying and retransmitting control signals, this module allows system integrators to overcome standard coaxial cable length limitations without degrading network performance.

The “D” in the model designation indicates a dual-redundant configuration, ensuring high availability for critical process control applications. The YNT512D supports a maximum extension distance of 500 meters per repeater on V net and VL net, and up to 750 meters on the RIO bus. It is available in various power supply configurations (e.g., 24 V DC, 100–240 V AC) and mounting styles to accommodate diverse industrial control panel requirements.

 

Key Technical Specifications

Parameter Verified Specification
Manufacturer Yokogawa Electric Corporation
Product Type Dual-Redundant Bus Repeater
Compatible Networks V net, RIO bus, VL net
Transmission Speed 10 Mbps (V net / VL net), 2 Mbps (RIO bus)
Maximum Extension Distance 500 m per repeater (V net / VL net); 750 m per repeater (RIO bus)
Network Topology Bus topology
Redundancy Dual-redundant (indicated by “D” suffix)
Power Supply Options 24 V DC (±10%) or 100–240 V AC (50/60 Hz, ±10%), depending on specific suffix
Operating Temperature 0 to 50 °C
Ambient Humidity 10 to 90% RH, non-condensing
Regulatory Compliance CE, CSA, and applicable EMC standards for industrial environments

 

Detailed Product Overview

The Yokogawa YNT512D serves as a critical network infrastructure component in large-scale distributed control systems (DCS) and safety instrumented systems (SIS). In standard configurations, V net and RIO bus coaxial cables are subject to strict length limitations (e.g., 185 to 500 meters depending on cable type). The YNT512D bus repeater regenerates the signal, effectively resetting the distance counter and allowing the network to be extended in discrete segments. This capability is essential for sprawling facilities such as oil refineries, chemical plants, and power generation sites where control rooms and field devices are separated by significant distances.

The dual-redundant architecture of the YNT512D aligns with the fault-tolerant design philosophy of Yokogawa’s V net. In the event of a single cable fault or repeater failure, the secondary communication path maintains uninterrupted data flow between Human Interface Stations (HIS), Field Control Stations (FCS), and Bus Converters (BCV). This redundancy is mandatory for systems requiring high availability and is a core requirement for ProSafe-RS safety network segments.

Integration of the YNT512D requires adherence to specific topological rules. The total transmission distance is constrained by the number of repeaters in the path, calculated using Yokogawa’s specified formula (L = 24 – n for V net, where n is the total number of bus and optical repeaters). Additionally, when mixing different coaxial cable types (e.g., YCB111 and YCB141), bus adapter units or the YNT512D itself must be used to ensure proper impedance matching and signal regeneration. The module is designed for installation in standard 19-inch racks or control panel enclosures, with specific variants offering different power input options to match the facility’s existing distribution infrastructure.

YNT512D

YNT512D

YNT512D

YNT512D

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Supported Networks V net, RIO bus, VL net Ensure the repeater variant matches the specific bus type and power requirements of the segment.
Maximum Repeater Count Up to 8 units (bus and optical combined) between any two stations Exceeding this limit violates the total transmission distance calculation (L = 24 – n).
Cabling YCB111, YCB141, or YCB311 coaxial cables Proper grounding units (e.g., YCB117) are required per segment when using YCB111 or YCB311 cables.
Power Supply 24 V DC or 100–240 V AC Must match the specific suffix of the ordered YNT512D model (e.g., -V12, -P11, -Q12).
System Software CENTUM VP, CENTUM CS 3000, ProSafe-RS The repeater operates at the physical layer and requires no software configuration, but system documentation must reflect its presence.

 

Dimensions, Mounting & Connection Notes

  • Form Factor: Compact module designed for standard control panel or 19-inch rack mounting (exact dimensions vary by specific suffix and housing variant, commonly approx. 144 mm x 144 mm x 72 mm).
  • Weight: Approximately 0.3 kg to 1.5 kg, depending on the housing and power supply configuration.
  • Mounting Method: DIN rail or rack-mount brackets, secured according to the specific installation manual for the ordered variant.
  • Connections: BNC or dedicated coaxial connectors for V net/RIO bus segments, along with terminal blocks for power input and grounding.
  • Environmental Constraints: Must be installed in an environment maintaining 0 to 50 °C and 10 to 90% RH (non-condensing). Adequate ventilation is required to dissipate heat from the internal signal regeneration circuitry.

 

FAQ

What is the primary function of the Yokogawa YNT512D?
It is a dual-redundant bus repeater that amplifies and retransmits control network signals to extend the physical transmission distance of V net, RIO bus, and VL net architectures.

What is the maximum distance a single YNT512D can extend a V net segment?
A single YNT512D bus repeater can extend the V net or VL net transmission distance by up to 500 meters. For RIO bus, the maximum extension is 750 meters.

What does the “D” in YNT512D stand for?
The “D” indicates a dual-redundant configuration, meaning the module supports two independent communication paths for high availability and fault tolerance.

Can the YNT512D be used to connect different types of coaxial cables?
Yes, it can be used to interface and regenerate signals between different coaxial cable types (such as YCB111 and YCB141) that would otherwise require a bus adapter unit.

Is there a limit to how many repeaters can be installed in a single network path?
Yes. A maximum of 8 bus repeaters and optical bus repeaters combined can be mounted between any two stations. The total distance is also limited by the formula L = 24 – n (where n is the number of repeaters).

What power supply options are available for the YNT512D?
Depending on the specific model suffix (e.g., YNT512D-V12, YNT512D-P11/KT, YNT512D-Q12), the module can be powered by 24 V DC or 100–240 V AC (50/60 Hz).

 

Documented Performance Data

  • V net Transmission Speed: 10 Mbps
  • RIO bus Transmission Speed: 2 Mbps
  • V net / VL net Max Extension: 500 m per repeater
  • RIO bus Max Extension: 750 m per repeater
  • Operating Temperature Range: 0 to 50 °C
  • Withstanding Voltage: 1500 V AC for 1 minute (AC models), 500 V AC for 1 minute (DC models)