Yokogawa YS1700-100/A06/A31 Programmable Indicating Controller with RS-485

Parameter Value
Product type Programmable indicating controller (single-loop)
Series YS1700
Model code YS1700-100/A06/A31
Application With hard manual unit
Type Basic type
Power supply 100 V AC / 24 V DC common (dual power)
Direct input option /A06 – Isolated 2-wire transmitter input
Communication option /A31 – RS-485 (PC-link, Modbus, YS protocol, peer-to-peer)
Display Full-dot-matrix color LCD
Categories: , , , , SKU: YS1700-100/A06/A31 Brand:

Description

Core Product Summary

The Yokogawa YS1700-100/A06/A31 is a programmable indicating controller from the YS1700 series. It is a single-loop controller that can be customized by user programs for a wide range of process control applications.

This configuration includes a hard manual unit, basic type construction, dual 100 V AC / 24 V DC power supply, isolated 2-wire transmitter input (/A06), and RS-485 communication (/A31) supporting PC-link, Modbus, YS protocol, and peer-to-peer communication. It features a full-dot-matrix color LCD, dual CPU architecture for fail-safe operation, and high-capacity programming capability.

 

Key Technical Specifications

Parameter Value
Product type Programmable indicating controller (single-loop)
Series YS1700
Model code YS1700-100/A06/A31
Application With hard manual unit
Type Basic type
Power supply 100 V AC / 24 V DC common (dual power)
Direct input option /A06 – Isolated 2-wire transmitter input
Communication option /A31 – RS-485 (PC-link, Modbus, YS protocol, peer-to-peer)
Display Full-dot-matrix color LCD
Programming capacity 1000 steps (text program) or 400 modules (function block)
Control cycle Selectable 0.05 / 0.1 / 0.2 s
Analog inputs (basic) Multiple 1–5 V DC (expandable)
Accuracy (1–5 V input) ±0.1 % of span
Depth 250 mm (basic type)
Faceplate protection IP54 (basic type)
Mounting Panel mount
Dimensions (H × W × D) 144 × 72 × 250 mm
Weight Approx. 1.6 kg
Approvals CE Mark (basic type)

 

Engineering Selection Highlights

  • Hard manual unit allows independent manual adjustment of the controller output even if both CPUs fail.
  • Isolated 2-wire transmitter input (/A06) provides direct connection to field transmitters with power supply and isolation.
  • RS-485 communication (/A31) supports PC-link, Modbus, YS protocol, and peer-to-peer networking for integration with PLCs, DCS, or other YS controllers.
  • Dual CPU design (control + display) maintains indication and manual operation during a single CPU failure.
  • Large programming capacity (1000 text steps or 400 function blocks) with IEEE 754 floating-point calculations and over 100 calculation modules.
  • Function selection mode allows single-loop, cascade, or selector control without programming.
  • Dual power supply accepts 100 V AC or 24 V DC without polarity concern.
  • Compact 250 mm depth basic type with IP54 faceplate suitable for industrial panel mounting.
YS1700-100/A06/A31

YS1700-100/A06/A31

YS1700-100/A06/A31

YS1700-100/A06/A31

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Power supply 100 V AC ±10 % (50/60 Hz) or 24 V DC ±10 % Dual power, polarity-free for DC
Input Isolated 2-wire transmitter (/A06) Provides transmitter power and isolation
Communication RS-485 (/A31) PC-link, Modbus, YS protocol, peer-to-peer
Programming software YSS1000 setting software Required for user program development
DCS integration Compatible with Yokogawa CENTUM via RS-485 Direct communication supported
Expansion Optional expandable I/O (basic type with expandable I/O version) Up to 8 AI, 4 AO, 14 DI/DO total
Mounting Panel mount Standard 144 × 72 mm face

 

Dimensions, Mounting & Connection Notes

  • Overall dimensions: 144 mm (H) × 72 mm (W) × 250 mm (D) from panel.
  • Panel cutout: Approximately 137 × 68 mm.
  • Weight: Approximately 1.6 kg.
  • Faceplate: IP54 dust- and splash-proof (basic type).
  • Terminals: M4 screw terminals for signals, power, and ground.
  • Communication: RS-485 via rear screw terminals.
  • Front access: Dedicated connector for YSS1000 programming software.

 

Detailed Product Overview

The Yokogawa YS1700-100/A06/A31 is a programmable indicating controller belonging to the YS1700 series of single-loop controllers. It is designed for high reliability and flexibility in industrial process control.

This specific configuration is defined by the following suffix codes:

  • -1 – With hard manual unit
  • 0 – Basic type
  • 0 – 100 V AC / 24 V DC dual power supply
  • /A06 – Isolated 2-wire transmitter input
  • /A31 – RS-485 communication (PC-link, Modbus, YS protocol, and peer-to-peer)

The controller features a full-dot-matrix color LCD that displays process values, setpoints, alarms, and status information clearly. Dual CPUs (one dedicated to control and one to display) ensure that indication and manual operation remain available even if one processor fails. The independent hard manual circuit allows the operator to adjust the output signal manually if the digital circuits fail completely.

Programming is performed with the optional YSS1000 setting software. Users can choose text programming (up to 1000 steps) or function-block programming (up to 400 modules). More than 100 calculation modules are available, including exponential, logarithmic, temperature compensation, and pressure compensation functions, all using IEEE 754 single-precision floating-point arithmetic.

In function selection mode, the controller can operate as a single-loop, cascade, or selector controller without requiring a user program. Digital and analog I/O functions are assigned by parameter setting.

The isolated 2-wire transmitter input supplies power to the field transmitter and provides galvanic isolation. The RS-485 port supports multiple industrial protocols, allowing the controller to communicate with PCs, PLCs, other YS controllers, or Yokogawa CENTUM systems.

Power can be supplied from either 100 V AC or 24 V DC; the DC input is polarity-independent. The basic-type enclosure has a depth of 250 mm and an IP54-rated faceplate. Mounting is by standard panel cutout with upper and lower mounting brackets.

The YS1700-100/A06/A31 is intended for process industries that require a reliable, programmable single-loop controller with direct transmitter connection and serial communication capability.

 

Applications & System Role

The YS1700-100/A06/A31 functions as a programmable single-loop controller for process control applications. It performs PID control, cascade control, selector control, and custom logic defined by user programs.

It is used for continuous process control of variables such as temperature, pressure, flow, and level. The isolated 2-wire transmitter input simplifies connection to field instruments, while the RS-485 interface enables integration into supervisory systems, PLCs, or Yokogawa DCS networks. The hard manual unit provides a reliable backup for operator intervention during electronic failures.

 

FAQ

What is the Yokogawa YS1700-100/A06/A31?
It is a programmable single-loop indicating controller with a hard manual unit, isolated 2-wire transmitter input, and RS-485 communication.

What does the /A06 option provide?
It provides an isolated 2-wire transmitter input that supplies power to the field transmitter and isolates the signal.

What communication protocols does the /A31 option support?
RS-485 communication supporting PC-link, Modbus, YS protocol, and peer-to-peer communication.

Does the controller have a hard manual function?
Yes. The -1 suffix includes a hard manual unit that allows manual output adjustment independent of the digital circuits.

What power supplies are accepted?
100 V AC or 24 V DC (dual power supply, DC input is polarity-free).

What is the programming capacity?
Up to 1000 steps for text programs or 400 modules for function-block programs using the YSS1000 software.

What is the faceplate protection rating?
IP54 (dust- and splash-proof) for the basic type.