Sale!

ABB EI813F AC 800F Ethernet Communication Module

Parameter Specification
Manufacturer ABB
Model EI813F
Order Number 3BDH000022R1
Product Type Ethernet Communication Module
Product Family ABB Freelance
Controller Platform AC 800F
Communication Standard IEEE 802.3 Ethernet
Ethernet Standard 10BASE-T
Number of Channels 1
Categories: , , , , SKU: EI813F Brand:

Description

Core Product Summary

The ABB EI813F (3BDH000022R1) is a 10BASE-T Ethernet communication module designed for the ABB Freelance AC 800F distributed control system. It provides a twisted-pair Ethernet connection between the AC 800F controller and the system bus network, allowing communication through network hubs or switches.

The module has one Ethernet communication channel and is installed in the AC 800F controller assembly. Its network interface is intended for system-level communication rather than direct process I/O signal acquisition. When selecting this module for an existing installation, engineers should check the controller model, Ethernet slot assignment, cable configuration, and applicable controller software requirements.

 

Key Technical Specifications

Parameter Specification
Manufacturer ABB
Model EI813F
Order Number 3BDH000022R1
Product Type Ethernet Communication Module
Product Family ABB Freelance
Controller Platform AC 800F
Communication Standard IEEE 802.3 Ethernet
Ethernet Standard 10BASE-T
Number of Channels 1
Transmission Medium Twisted-pair cable
Network Connection Hub or switch
Connector RJ45
Installation Position AC 800F Ethernet slots E1 / E2
Nominal Power Dissipation 1.3 W
Module Function System bus communication

 

Detailed Product Overview

Ethernet Communication in the ABB AC 800F System

The ABB EI813F is an Ethernet interface module used in the communication architecture of the Freelance AC 800F controller. Its purpose is to connect the controller to the system bus through a 10BASE-T Ethernet network.

Unlike fieldbus modules that connect directly to process-level devices, the EI813F provides network connectivity at the controller system level. It supports communication through twisted-pair cabling and connects to external network infrastructure such as Ethernet hubs or switches.

This distinction matters when selecting replacement hardware. An Ethernet system-bus module and a PROFIBUS or FOUNDATION Fieldbus interface perform different functions within the AC 800F architecture.

10BASE-T Communication Interface

The EI813F uses the 10BASE-T Ethernet standard and a twisted-pair physical connection. Its single communication channel provides the network connection required by the AC 800F system bus.

The RJ45 connection makes it suitable for integration with conventional Ethernet network infrastructure configured for the applicable system requirements.

When replacing an installed module, engineers should inspect the existing cable type, connector condition, network topology, and controller configuration before reconnecting the communication interface.

Controller Integration

The EI813F belongs to the ABB AC 800F modular controller architecture. The controller accommodates up to two Ethernet modules in designated positions E1 and E2.

For installations using the PM 803F CPU board, the EI 811F, EI 812F, and EI 813F Ethernet modules require controller software version 7.1 or higher.

The Ethernet modules must not be inserted or removed while the AC 800F controller is powered. This is an important maintenance restriction when planning module replacement.

EI813F

EI813F

System Compatibility & Integration Requirements

Component Compatibility / Requirement Integration Notes
ABB AC 800F Supported controller platform Installed in the AC 800F assembly
PM 803F Supported with software V7.1 or higher Check software version before integration
Ethernet slots E1 and E2 Maximum two Ethernet modules per controller
System Bus ABB Freelance system bus Provides controller network connectivity
Ethernet network 10BASE-T Twisted-pair connection
Network equipment Ethernet hubs or switches Check the existing network configuration
Connector RJ45 Inspect cable and connector condition

Important installation restrictions:

  • Do not remove or insert the Ethernet module while the AC 800F is powered.
  • Confirm the correct Ethernet slot assignment.
  • Check the controller software version, particularly with PM 803F.
  • Verify the existing 10BASE-T network infrastructure.
  • Do not assume that other AC 800F Ethernet module types have identical physical interfaces.

 

Dimensions, Mounting & Connection Notes

The EI813F is installed as a plug-in Ethernet module within the AC 800F controller assembly.

Item Description
Installation Platform ABB AC 800F
Installation Position E1 or E2
Mounting Method Controller plug-in module
Network Connector RJ45
Cable Type Twisted pair
Ethernet Standard 10BASE-T
Nominal Power Dissipation 1.3 W

Installation Recommendations

  1. Confirm the module identification and order number before installation.
  2. Check that the controller has an available Ethernet module position.
  3. Power down the AC 800F before inserting or removing the module.
  4. Inspect the RJ45 connector and network cable.
  5. Confirm the hub or switch connection.
  6. Check the controller configuration and communication status after installation.

 

FAQ

Q1. What is the ABB EI813F?

The ABB EI813F is a 10BASE-T Ethernet communication module for the Freelance AC 800F distributed control system.

Q2. What is the order number of ABB EI813F?

The commonly associated ABB order number is 3BDH000022R1.

Q3. Which controller uses the EI813F module?

The EI813F is designed for the ABB AC 800F controller platform.

Q4. What Ethernet standard does the EI813F support?

It supports 10BASE-T Ethernet using twisted-pair cabling.

Q5. What connector does the ABB EI813F use?

The module uses an RJ45 network connection.

Q6. Can the EI813F be removed while the controller is running?

No. ABB AC 800F installation instructions specify that Ethernet modules must not be inserted or removed while the controller is powered.

Q7. How many Ethernet modules can an AC 800F accommodate?

The AC 800F controller supports up to two Ethernet modules in positions E1 and E2.

Q8. What software version is required for EI813F with PM 803F?

The documented requirement for using the EI813F with a PM 803F CPU board is software version 7.1 or higher.