Sale!

ABB SA167 3BSE003390R1 I/O Module

  • Model: SA167 (3BSE003390R1)
  • Brand: ABB
  • Series: S800 I/O System
  • Core Function: Analog input processing
  • Product Type: 16-channel AI module
  • Key Specs: 24 VDC | 0-20 mA | ±10 V ranges
  • Condition: New Surplus (not refurbished)
  • Inventory Status: EOL buffer stock for DCS upgrades
Categories: , , , , Brand:

Description

Product Core Brief

  • Model: SA167 (3BSE003390R1)
  • Brand: ABB
  • Series: S800 I/O System
  • Core Function: Analog input processing
  • Product Type: 16-channel AI module
  • Key Specs: 24 VDC | 0-20 mA | ±10 V ranges
  • Condition: New Surplus (not refurbished)
  • Inventory Status: EOL buffer stock for DCS upgrades​

Key Technical Specifications

Parameter Value
Brand/Model ABB SA167 3BSE003390R1
Channels 16 analog inputs
Input Types 0-20 mA
Power Supply 24 VDC (external)
Resolution 16-bit
Update Rate 10 ms/channel
Bus Interface PROFIBUS DP
Operating Temp −25 to +70 °C
Isolation 500 V galvanic
Dimensions 21 mm x 120 mm x 116 mm
Certifications SIL2 capable

Product Introduction & Supply Chain Strategy

The ABB SA167 3BSE003390R1 is a 16-channel analog input module from the S800 I/O series. It conditions field signals like pressure, flow, and temperature for DCS systems in oil/gas, power, and chemical plants.​

New Surplus secures supply against ABB discontinuations, cutting lead time variability. Avoid refurbished risks—degraded inputs cause false process alarms. Stock 1-2 units per site to minimize stock-outs while controlling carrying costs.

SA168 3BSE003389R1
SA167 3BSE003390R1

Installation & Configuration Guide

Stage 1: Pre-Installation

Lock out/tag out power to I/O rack. Tools: ESD strap, torque wrench (0.4 Nm), camera for terminal mapping and address switches. Record module slot and firmware via CI847 fieldbus.​

Stage 2: Removal

Isolate 24 V supply. Loosen terminal screws, label wires. Release module latch from backplane, pull straight out. Check old unit for corrosion on contacts.​

Stage 3: Installation

Match address switches exactly from photo. Insert into backplane slot until latched. Reconnect wires per labeling—twist shields to SCR ground. Torque to spec.​

Stage 4: Power-On & Testing

Power up rack, scan via DCS engineering station. Verify input scaling (e.g., 4-20 mA = 0-100%). Simulate signals, check no overranging LEDs. Download config backup.​

Firmware/Software Versions & Upgrade Notes

Firmware V2.x or V3.x—match rack CI847 version exactly. Mismatch triggers bus faults. Never upgrade during swap; use 800xA tools for offline flash only. Downgrade risks lost calibration data.​

Frequently Asked Questions (FAQ)

Confirm this is genuine New Surplus?
Yes—original ABB sealed bag, QC tested only. Pins show zero wear, unlike pulled field units with oxidation.​

Pricing logic vs OEM/refurb?
20-30% below OEM list via global New Surplus channels, but skips refurb roulette. One bad input channel cost a refinery $100k in off-spec product.​

EOL—stock now?
S800 legacy; last-time-buy phase. Set Min/Max 1/2 for critical loops—vendor consolidation won’t cover obsolescence.​

Hot-swap safe?
No—backplane isolation mandatory. Live swap corrupts PROFIBUS and fries module.​

Programming survives?
Config stored in CI847 head; module is passive. Restore from backup post-install.​

Warranty coverage?
1-2 years, includes live test data and serial traceability. Full SOP: insulation, signal sweep, bus comms.​

Channel isolation details?
500 V per channel to bus/ground. Add 20% buffer on 24 V loop power.​