AEG THYRO-P LBA Local Operating and Display Unit for Thyro-P

The AEG THYRO-P LBA is the optional local operating and display unit for the Thyro-P communication-capable thyristor power controller. It is a pluggable, menu-driven handheld panel that connects to the RS 232 interface of the Thyro-P control device and can be connected or disconnected during operation, making one unit serviceable across multiple controllers.

Categories: , , , , SKU: THYRO-P LBA Brand:

Description

Core Product Summary

The AEG THYRO-P LBA is the optional local operating and display unit for the Thyro-P communication-capable thyristor power controller. It is a pluggable, menu-driven handheld panel that connects to the RS 232 interface of the Thyro-P control device and can be connected or disconnected during operation, making one unit serviceable across multiple controllers.

The LBA carries a backlit graphical LC display with 7 × 19 characters (64 × 114 pixels) and five keys, plus a sixth reset key accessible behind an opening in the front. In the standard version it operates in German, English, or French. Through its main menu and submenus it supports full parameterization and monitoring of the Thyro-P: set point processing, parameter display and modification, selection of the operation display, and readout of energy and operating hours. Its integrated copying function loads a complete parameter set from one controller into the LBA memory, stores it in the LBA EEPROM, and copies it into another Thyro-P — a practical commissioning aid for multi-controller installations. The operation display can show up to three process data values, such as actual current values, and certain submenus are password protected to guard adjusting parameters.

 

Key Technical Specifications

Parameter Value
Product type Local operating and display unit (LBA) for Thyro-P
Host device AEG Thyro-P thyristor power controller
Interface RS 232 interface of the Thyro-P control device
Hot plugging Connectable and disconnectable during operation
Display Backlit graphical LC display, 7 × 19 characters / 64 × 114 pixels
Keys Five operating keys plus one reset key behind the front opening
Protection rating IP30, protection class 3
Operating languages German, English, French (standard version)
Parameter memory RAM and EEPROM in the LBA for parameter set storage
Copying function Parameter transfer between Thyro-P controllers via the LBA
Access protection Password-protected submenus; activatable parameterizing lock
Functions Parameter setting, set point processing, operation display, status and fault indication

 

Detailed Product Overview

The Thyro-P power controller can be operated through several service interfaces: the LBA, the Thyro-Tool Family PC software, and a fieldbus connection. The LBA is the local option — the unit a commissioning or service engineer carries to the cabinet. After plugging into the RS 232 interface, parameters load automatically and the LBA presents its main menu; if communication cannot be established, a self-test runs to isolate the fault.

Its working menu structure maps to the commissioning workflow. Set point processing covers the upstream signal sources (motor poti, terminals, and bus), because Thyro-P combines enabled set points into an effective total set point. Parameter display and modification reaches all settings, with the deeper adjusting parameters — the ones that determine whether power control specifications are met — placed behind a password. The operation display shows up to three live process values at once, and a line diagram mode is available; when no key is pressed for one minute, the unit automatically returns to the operation display.

The copying function is the feature that most affects productivity in multi-controller systems. A complete user-specific parameter record is read from one Thyro-P into the LBA’s RAM, stored in the LBA’s EEPROM, and then written into another controller. One carefully commissioned controller therefore becomes the template for the rest of the line. The documented storage sequence matters in practice: parameters must first be saved in the LBA EEPROM before being stored in the Thyro-P.

The unit also participates in fault management. Faults and indications occurring in Thyro-P are entered into a fault memory with event time and survive mains outages; the most recent sixteen events can be recalled, and status messages appear in the status line of the LBA operation display. Relay indications and LED indications on the controller itself remain available in parallel, so the LBA is a diagnostic convenience rather than a single point of failure for monitoring.

An activatable parameterizing lock protects the configuration against unintended changes, complementing the password levels already described.

THYRO-P LBA

THYRO-P LBA

THYRO-P LBA

THYRO-P LBA

Dimensions, Mounting & Connection Notes

  • The LBA is a pluggable hand-held unit; it is not permanently mounted and requires no cabinet cutout. It connects to the RS 232 interface of the Thyro-P control device.
  • Connection and disconnection are permitted during controller operation; after plugging in, parameters load automatically and the main menu appears.
  • The reset key is an unnamed sixth key located behind an opening in the front of the unit; operating it performs the RESET function of the Thyro-P.
  • The housing is rated IP30 (protection class 3), so the unit is intended for use inside a cabinet or enclosure environment, not exposed panel-edge mounting.
  • If no key is pressed for one minute, the operation display appears automatically; this does not occur while a line diagram is running.
  • Before storing parameters (store in Thyro-P / LBA under Thyro-P), the parameters must first be saved in the EEPROM of the LBA.
  • Power component repairs on the controller itself are reserved to the manufacturer; the LBA is a service and operating accessory, not a repair tool.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Host controller AEG Thyro-P thyristor power controller Operates on the control device of the Thyro-P
Electrical interface RS 232 Connection at the Thyro-P control device
Operation during running process Plugging and unplugging permitted during operation Parameters load automatically on connection
Alternative service tools Thyro-Tool Family PC software; fieldbus interface Can be used instead of, or alongside, the LBA
Parameter storage LBA RAM and LBA EEPROM Save to LBA EEPROM before storing in Thyro-P
Copying between controllers Complete parameter set transferable via LBA Controller-to-controller through LBA memory
Access control Password-protected submenus and activatable parameterizing lock Deeper adjusting parameters require password entry
Languages German, English, French Selectable in the language menu

 

FAQ

What is the AEG THYRO-P LBA?
It is the optional local operating and display unit for the AEG Thyro-P thyristor power controller, used for parameterization, monitoring, and fault diagnosis at the machine.

Can it be plugged in while the controller is running?
Yes. The LBA may be connected to or disconnected from the RS 232 interface of the Thyro-P during operation, with automatic parameter loading on connection.

What does the display show?
A backlit graphical LC display with 7 × 19 characters (64 × 114 pixels) shows menus, up to three live process values on the operation display, status messages, and a line diagram mode.

Can parameters be copied between controllers?
Yes. The integrated copying function loads a complete parameter set from one Thyro-P into the LBA, stores it in the LBA EEPROM, and writes it into another Thyro-P.

Which languages does it support?
German, English, and French in the standard version, selectable through the language menu.

How are critical parameters protected?
Adjusting parameters sit in password-protected submenus, and an activatable parameterizing lock guards the configuration against unintended changes.

Can faults be diagnosed with the LBA?
Yes. Status messages appear in the LBA’s status line, and Thyro-P’s fault memory — which retains the most recent sixteen events with timestamps even through mains outages — can be read through the unit.

Are there alternatives to the LBA?
Yes. The Thyro-Tool Family PC software and the fieldbus interface offer overlapping parameterization and monitoring functions, and can be used instead of the LBA.