Description
Core Product Summary
The Allen-Bradley 2711-K5A8 is a PanelView Standard 550 keypad operator-interface terminal from Rockwell Automation. It provides machine-level monitoring and operator control through a 5.5 in. monochrome LCD, a stainless-steel domed membrane keypad, and a DH+ communication port.
The terminal uses 85–264 V AC, 47–63 Hz power and includes an RS-232 printer port. Its application memory consists of 170 KB of runtime memory and 240 KB of nonvolatile memory; it supports ATA memory cards and is configured with PanelBuilder32 software. The 2711-K5A8 is intended for panel-mounted installations where DH+ connectivity to compatible Allen-Bradley controllers is required.
Key Technical Specifications
| Attribute | Specification |
|---|---|
| Manufacturer | Allen-Bradley / Rockwell Automation |
| Catalog number | 2711-K5A8 |
| Product family | PanelView Standard 550 |
| Product type | Keypad operator-interface terminal |
| Display | 5.5 in. monochrome LCD, blue mode |
| Display area | 120 x 60 mm (4.75 x 2.38 in.) |
| Display resolution | 256 x 128 pixels |
| Backlight | LED, 100,000-hour backlight life |
| Operator input | Keypad |
| Keypad | Stainless-steel domed membrane keypad with navigation and function keys |
| Function keys | 10 function keys, F1 through F10 |
| Keypad actuation | 1 million presses |
| Real-time clock | Battery-backed clock for time-stamping critical data |
| Battery | Field-replaceable |
| Application memory | 170 KB application runtime |
| Nonvolatile memory | 240 KB for application objects, text, and bitmaps |
| ATA memory card | Supported |
| Communication port | DH+ |
| Printer port | RS-232 printer port |
| RS-232 printer-port speeds | 1200, 2400, 9600, and 19,200 Kbps |
| Input power | 85–264 V AC, 47–63 Hz |
| Power consumption | 45 VA maximum |
| Approximate weight | 1.2 kg (2.7 lb) |
| Approximate dimensions | 167 x 266 x 106 mm (6.57 x 10.47 x 4.17 in.) |
| Configuration software | PanelBuilder32 |
| Enclosure ratings | NEMA Type 12, 13, and 4X (indoor use only); IEC IP54 and IP65 |
| Operating temperature | 0 to 55 °C (32 to 131 °F) |
| Storage temperature | -20 to 70 °C (-4 to 158 °F) |
| Relative humidity | 5 to 95% noncondensing at 0 to 55 °C |
| Operating vibration | 2 g up to 2000 Hz |
| Operating altitude | 2000 m (6561 ft) |
| Operating/nonoperating shock | 30 g / 50 g |
Engineering Selection Highlights
- The 2711-K5A8 is a keypad-only PanelView Standard 550 terminal, so it suits applications that require physical operator controls rather than a touch-screen interface.
- Its DH+ communication port makes it appropriate for systems that use DH+ as the runtime communication path.
- The RS-232 printer port supports online printing at 1200, 2400, 9600, or 19,200 Kbps, which can be used for alarm and event output.
- The terminal requires 85–264 V AC power at 47–63 Hz; it is not a 24 V DC-powered PanelView 550 variant.
- Its 170 KB runtime memory and 240 KB nonvolatile memory define the available capacity for the PanelBuilder32 application, including objects, text, and bitmaps.
- ATA memory-card support provides a documented method for application-file storage and transfer.
- The terminal is panel-mounted and has published enclosure ratings of NEMA Type 12, 13, and 4X for indoor use, plus IEC IP54 and IP65.

2711-K5A8
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Controller communication | DH+ port | Use a DH+ connection for runtime communication with compatible Allen-Bradley controllers. |
| DH+ cable | Shielded twinaxial cable, 1770-CD | The published runtime-communication table specifies shielded twinaxial cable for DH+ connections. |
| PLC-5 connection | DH+ port with 1770-CD shielded twinaxial cable | The terminal connects to PLC-5-family controllers over DH+ using the specified cable. |
| SLC 5/04 connection | DH+ port with 1770-CD shielded twinaxial cable | The published compatibility table identifies the SLC 5/04 DH+ channel as the matching connection path. |
| ControlLogix connection | 1756-DHRIO module with 1770-CD shielded twinaxial cable | DH+ connectivity to ControlLogix requires the 1756-DHRIO interface module. |
| Application development | PanelBuilder32 software | Applications are created and configured in PanelBuilder32. |
| Application transfer | Direct computer-to-terminal transfer, network transfer, pass-through/gateway connection, or ATA memory card | PanelBuilder32 supports these documented transfer methods. |
| Memory expansion | ATA memory card | The terminal supports ATA memory cards; compatible card capacities listed by Rockwell include 2 MB, 4 MB, 10 MB, and 32 MB. |
| Printer connection | RS-232 printer port | The port is designated for printing functions. |
Dimensions, Mounting & Connection Notes
The 2711-K5A8 has approximate overall dimensions of 167 x 266 x 106 mm (6.57 x 10.47 x 4.17 in.) and weighs approximately 1.2 kg (2.7 lb). It is a panel-mounted operator terminal, and its published enclosure ratings include NEMA Type 12, 13, and 4X for indoor use as well as IEC IP54 and IP65.
The terminal provides a DH+ communication port and an RS-232 printer port. For DH+ runtime communication, Rockwell specifies shielded twinaxial cable, catalog number 1770-CD. The RS-232 printer port supports 1200, 2400, 9600, and 19,200 Kbps communication rates.
Detailed Product Overview
The Allen-Bradley 2711-K5A8 belongs to the PanelView Standard 550 family of operator-interface terminals. Its role is to provide a local operator window into a controller-based automation system: displaying status, process values, alarms, and graphics while accepting operator commands through a physical keypad.
The terminal uses a 5.5 in. monochrome LCD in blue mode with a 256 x 128-pixel resolution and a 120 x 60 mm display area. Its LED backlight is specified for 100,000 hours of life. The stainless-steel domed membrane keypad includes navigation keys and ten function keys, F1 through F10, and is rated for one million actuations. This input arrangement is appropriate where operators need fixed, tactile controls rather than touch-screen interaction.
For system integration, the 2711-K5A8 is equipped with a DH+ communication port. Rockwell’s runtime-communication documentation identifies shielded twinaxial cable, catalog number 1770-CD, for DH+ connections to PLC-5-family controllers, SLC 5/04 controllers, and ControlLogix systems through a 1756-DHRIO module. This makes the exact communication interface—not merely the terminal size or display type—the primary compatibility consideration when selecting this catalog number.
The terminal is powered from 85–264 V AC at 47–63 Hz and consumes up to 45 VA. It contains 170 KB of application runtime memory and 240 KB of nonvolatile memory for application objects, text, and bitmaps. It also supports ATA memory cards, which can be used for application-file storage and transfer. Applications are developed in PanelBuilder32, Rockwell’s configuration software for the PanelView Standard family.
Installation planning should account for the terminal’s 167 x 266 x 106 mm external dimensions and its panel-mount format. The published environmental limits include 0 to 55 °C operation, -20 to 70 °C storage, 5 to 95% noncondensing relative humidity, 2 g vibration up to 2000 Hz, and 2000 m operating altitude. The enclosure is rated NEMA Type 12, 13, and 4X for indoor use, and IEC IP54 and IP65.
Applications & System Role
The 2711-K5A8 serves as the operator-interface layer in an Allen-Bradley control system. It presents process and machine information on its monochrome display while allowing operators to initiate commands, navigate screens, enter values, acknowledge alarms, and interact with controller-based logic through its keypad.
Its DH+ port positions the terminal for installations that retain DH+ as the controller-network interface. The RS-232 printer port adds a documented path for online printing, including alarm-related output supported by the PanelView Standard application environment. The terminal’s keypad, screen-security features, alarm handling, analog gauges, and graphics capability make it suitable for machine-level monitoring and control applications configured in PanelBuilder32.
FAQ
What is the Allen-Bradley 2711-K5A8?
The Allen-Bradley 2711-K5A8 is a PanelView Standard 550 keypad operator-interface terminal used to monitor and control machines through an Allen-Bradley automation system.
What type of display does the 2711-K5A8 have?
It has a 5.5 in. monochrome LCD in blue mode with a 256 x 128-pixel resolution and a 120 x 60 mm display area.
Does the 2711-K5A8 use a touchscreen?
No. The 2711-K5A8 is a keypad-only terminal with a stainless-steel domed membrane keypad, navigation keys, and ten function keys.
Which communication interface does the 2711-K5A8 use?
The terminal has a DH+ communication port for runtime communication with compatible Allen-Bradley controllers.
What power supply does the 2711-K5A8 require?
It requires 85–264 V AC at 47–63 Hz and consumes up to 45 VA.
Which software is used to configure the 2711-K5A8?
The terminal is configured with PanelBuilder32 software.
Does the 2711-K5A8 support a printer?
Yes. It includes an RS-232 printer port that supports 1200, 2400, 9600, and 19,200 Kbps communication rates.
What are the terminal’s memory capabilities?
It provides 170 KB of application runtime memory, 240 KB of nonvolatile memory, and support for ATA memory cards.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626