Sale!

COFI TRE820P/4 230V 8kV Compact Ignition Transformer

Specification Parameter Technical Value / Standard
Manufacturer COFI Ignitions (Italy)
Model / Order Code TRE820P/4 (TRE820P Series)
Product Category Inductive Ignition Transformer
Primary Input Voltage 230 VAC (±10%), 50/60 Hz
Primary Input Current 0.9 A
Secondary Voltage (RMS) 1 × 8 kV (Single Output / Grounded Return)
Categories: , , , , SKU: TRE820P/4 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The COFI TRE820P/4 (also referenced as TRE820P-4 or TRE820P) is a high-voltage inductive ignition transformer manufactured by COFI Ignitions in Italy. Designed for industrial and commercial combustion systems, this compact unit supplies high-energy electrical arc ignition for gas, light oil, and heavy oil burners across heating, melting, and process thermal applications.

Operating on a primary supply of 230 VAC (0.9 A, 50 Hz), the TRE820P/4 generates an output ignition voltage of 8 kV RMS (11 kV peak) at a secondary current of 20 mA. Its compact high-density design achieves high ignition output within a minimal enclosure footprint. Featuring an insulated secondary winding suitable for single-rod or dual-rod burner configurations, an IP00 protection rating, and an operating duty cycle of 19% over 3 minutes, the TRE820P/4 delivers reliable arc initiation while withstanding industrial thermal stresses.

 

Key Technical Specifications

Specification Parameter Technical Value / Standard
Manufacturer COFI Ignitions (Italy)
Model / Order Code TRE820P/4 (TRE820P Series)
Product Category Inductive Ignition Transformer
Primary Input Voltage 230 VAC (±10%), 50/60 Hz
Primary Input Current 0.9 A
Secondary Voltage (RMS) 1 × 8 kV (Single Output / Grounded Return)
Secondary Peak Voltage 11 kV Peak
Secondary Output Current 20 mA
Duty Cycle (ED) 19% over 3 minutes (max 34 seconds continuous runtime per 180s cycle)
Output Frequency ~20 kHz high-frequency spark generation
Recommended Spark Gap 3.0 mm to 5.0 mm
High Voltage Termination VIRAS (Screw-in) or Plug-in connection options
Protection Rating IP00 (open enclosure for internal control box mounting)
Insulation Class Class B
Ambient Temperature Range -20°C to +60°C
Approximate Weight ~1.0 kg to 1.9 kg

 

Detailed Product Overview

The COFI TRE820P/4 functions as the high-voltage ignition source inside industrial burner management systems. In automatic burner sequencing, the burner control unit energizes the primary side of the transformer during the pre-ignition and trial-for-ignition phases, creating a continuous 8 kV high-frequency electrical spark across the ignition electrode gap to ignite atomized fuel mist or gas stream mixtures.

The “P” designator within the TRE820 series highlights a high-efficiency coil winding layout that packs mid-sized transformer performance into a space-saving housing. The secondary winding is insulated, enabling flexibility in burner flame monitoring setups: it supports both dedicated two-rod setups (separate ignition rod and ionization flame rod) and single-rod setups (where the same electrode handles both high-voltage ignition and flame ionization sensing via external burner control switching).

Encapsulated in thermosetting epoxy resin, the internal core and coils are protected against moisture, vibration, and dust accumulation inside burner enclosure assemblies. High-voltage connection terminals accommodate direct unscreened ignition cables, delivering immediate arc response to minimize unburned fuel accumulation during burner start cycles.

TRE820P/4

TRE820P/4

TRE820P/4

TRE820P/4

Engineering Selection Highlights

  • Compact Form Factor: Delivers an 8 kV / 20 mA ignition arc while occupying minimal installation depth inside burner control housings.
  • High-Peak Voltage Reserve: 11 kV peak output ensures reliable arc breakdown through dense oil mist and high-velocity gas streams.
  • Versatile Rod Compatibility: Suitable for 2-rod systems or single-rod ignition/flame detection control loops.
  • Epoxy Resin Encapsulation: Thermosetting resin potting protects high-voltage windings from atmospheric moisture and environmental contaminants.
  • Standardized Industrial Ratings: Standard 230V / 50Hz supply requirements match standard European and global industrial control voltages.

 

System Compatibility & Integration Requirements

System Component / Layer Compatibility / Integration Requirement Practical Note
Primary AC Power 230 VAC, 50/60 Hz (0.9 A nominal line draw) Switched directly via burner control unit relay contacts.
High-Voltage Ignition Cable Unscreened silicone/copper HV cable (1 mm², rated ≥20 kV) Keep cable length under 5 meters to minimize capacitive spark energy loss.
Electrode Assembly Standard ignition rod setting a 3–5 mm spark gap Ensure ground return path to the burner body uses a heavy wire gauge (>4 mm²).
Burner Housing / Enclosure IP00 internal mounting; requires protective enclosure Mount inside burner electrical control box or metal enclosure.

 

Dimensions, Mounting & Connection Notes

  • Mounting Method: Mounts via integrated base panel hole points directly onto the back wall or chassis plate of the burner control box.
  • Grounding Requirements: A direct low-impedance ground connection from the transformer ground terminal to the burner frame ground is mandatory for safe spark discharge and accurate ionization current flow.
  • High-Voltage Termination: Ensure high-voltage cables (screw VIRAS or plug SPRAS connectors) are fully seated and insulated to prevent high-voltage arcing to nearby cabinet walls.
  • Thermal Clearances: Allow surrounding air space within the cabinet to prevent thermal accumulation from exceeding the maximum ambient rating of +60°C.

 

FAQ

What is the primary function of the COFI TRE820P/4?

The COFI TRE820P/4 is an inductive high-voltage ignition transformer that steps up a 230V AC supply to an 8 kV arc to ignite oil or gas burners in industrial heating systems.

What are the output electrical ratings of the TRE820P/4?

It outputs a secondary RMS voltage of 8 kV (11 kV peak) with a continuous secondary current of 20 mA.

What does the 19% duty cycle (ED 19% 3 min) mean?

It indicates that within a 3-minute (180-second) operational window, the transformer can run for a maximum total of 34 seconds (e.g., up to two 5-second ignition attempts per minute) without overheating.

Can the TRE820P/4 be used in single-rod flame sensing setups?

Yes. Its insulated secondary winding allows it to be used in systems where a single electrode performs both high-voltage ignition and flame ionization detection when interfaced with an appropriate control box.

What type of high-voltage cable should be used?

Use unscreened silicone/copper high-voltage cable (rated for at least 20 kV) under 5 meters in length to maintain maximum spark intensity.

 

Verification & Troubleshooting Notes

  • Duty Cycle Verification: If the ignition transformer fails prematurely or trips thermal limits, verify that the burner control programmer is not leaving the transformer energized continuously beyond the 34-second limit per 3-minute period.
  • Spark Gap Inspection: Inspect the ignition electrode tip gap; adjust spacing to within the recommended 3.0 mm to 5.0 mm range. A gap that is too wide can cause internal high-voltage breakdown inside the transformer body.
  • Ground Continuity Test: Verify low resistance (<1 Ohm) between the transformer ground wire/terminal and the metallic frame of the burner. Poor grounding leads to weak sparks or erratic flame signal readings during burner start up.
  • Primary Voltage Diagnostics: Measure input AC voltage at the primary terminals during an ignition sequence to ensure line voltage does not sag below 230V under load, which reduces spark output energy.