Description
Core Product Summary
The DEIF TAC-311DG is a single-function AC current transducer for measuring sinusoidal AC current on single-phase or three-phase networks. It converts the measured current into a proportional DC current or voltage signal for PLCs, PCs, microprocessor controls, indicators, and alarm units.
The TAC-311DG uses average-value measurement and provides galvanic isolation between the input, output, and auxiliary supply. It offers Class 0.5 accuracy over -10 to +55 °C, a 45–65 Hz frequency range, adjustable span and zero, and a compact 55 × 75 mm housing for 35 mm DIN-rail or base mounting. The transducer requires an auxiliary supply and provides an output limit below 22.0 mA for 4–20 mA configurations.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | DEIF |
| Exact model | TAC-311DG |
| Product type | AC current single-function transducer |
| Measurement principle | Average measurement |
| Measured quantity | Sinusoidal AC current |
| Network type | Single-phase or three-phase |
| Frequency range | 45–65 Hz |
| Measuring current range | 1.0–7.25 A AC, maximum 1.2 VA |
| Accuracy | Class 0.5 from -10 to +55 °C according to IEC 688 |
| Standard output | 4–20 mA DC |
| Other available outputs | 0–5 mA, 0–10 mA, 0–20 mA, 0–10 V DC |
| Span adjustment | ±20% of full-scale output |
| Zero adjustment | ±20% of 4 mA for 4–20 mA output |
| Output limit, 4–20 mA version | Less than 22.0 mA DC |
| Response time / ripple | Less than 300 ms / 0.5% peak-to-peak |
| Temperature coefficient | Maximum 0.1% of full scale per 10 °C |
| Overload capacity | 2 × nominal current continuously; 10 × for 10 s; 40 × for 1 s |
| Galvanic isolation | 2200 V, 50 Hz, 1 minute between input, output, and auxiliary supply |
| Auxiliary supply, AC | 110/230/440 V AC ±20%, maximum 2.5 VA |
| Auxiliary supply, DC | 24 Vdc; 48–110 Vdc; or 88–220 Vdc, depending on order configuration |
| Ambient temperature | -10 to +55 °C normal; -25 to +70 °C operating; -40 to +70 °C storage |
| Protection | IP40 case; IP20 terminals |
| EMC | EN 50081-1/2 and EN 50082-1/2 |
| Dimensions | 55 × 75 mm; depth 110 mm |
| Weight | Approximately 0.4 kg |
| Mounting | 35 mm DIN rail or base mounting |
| Terminal capacity | Maximum 4.0 mm² single-stranded; maximum 2.5 mm² multi-stranded |
Engineering Selection Highlights
- The TAC-311DG is an AC current transducer, so it should be selected where a sinusoidal AC current signal must be converted into an isolated DC signal for a control or monitoring system.
- Its Class 0.5 accuracy from -10 to +55 °C provides a defined measurement-accuracy basis for current monitoring and control applications.
- The 45–65 Hz frequency range should be matched to the AC network frequency before selection.
- The 4–20 mA output provides a live-zero signal range, while 0–5 mA, 0–10 mA, 0–20 mA, and 0–10 V outputs are available depending on the ordered configuration.
- Span adjustment of ±20% of full scale and zero adjustment of ±20% of 4 mA allow the transducer output to be matched to the required measuring range.
- The transducer requires an auxiliary supply, with available AC and DC supply options determined by the exact order number.
- Its 2200 V galvanic isolation between input, output, and auxiliary supply is relevant where separation between measurement, control, and supply circuits is required.
- The IP40 case and IP20 terminals mean the unit is intended for installation in a suitable electrical enclosure rather than direct exposure to the environment.

TAC-311DG

TAC-311DG
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Measured network | Single-phase or three-phase sinusoidal AC current | Confirm the current-transformer secondary range and network frequency before selection. |
| Frequency range | 45–65 Hz | Suitable for standard 50 Hz and 60 Hz AC systems. |
| Output signal | 4–20 mA DC standard; other current or voltage outputs available by configuration | Match the output type to the receiving PLC, indicator, alarm unit, or controller input. |
| Output load | Maximum 12 V for current output; maximum 1 mA for voltage output | Verify the receiving input burden or load before wiring. |
| Auxiliary supply | 110/230/440 V AC or 24, 48–110, or 88–220 V DC, depending on order configuration | Confirm the supply variant marked on the unit and use the appropriate fuse. |
| Mounting | 35 mm DIN rail or base mounting | Suitable for cabinet installation. |
| Wiring capacity | 4.0 mm² single-stranded or 2.5 mm² multi-stranded maximum | Use conductors within the stated terminal capacity. |
| Installation environment | IP40 case and IP20 terminals | Install in an enclosure that provides the required environmental protection. |
Dimensions, Mounting & Connection Notes
The DEIF TAC-311DG measures 55 mm wide, 75 mm high, and 110 mm deep, and weighs approximately 0.4 kg. It can be mounted on a 35 mm DIN rail or base-mounted.
The transducer provides separate input, output, and auxiliary-supply connections. Its terminals accept up to 4.0 mm² single-stranded conductors or up to 2.5 mm² multi-stranded conductors. A 2 A fuse is recommended on the auxiliary supply.
The case is rated IP40 and the terminals are rated IP20. Galvanic isolation is provided between the input, output, and auxiliary supply at 2200 V, 50 Hz, for one minute.
Detailed Product Overview
The DEIF TAC-311DG is a compact, single-function AC current transducer. It measures sinusoidal AC current and converts the measured value into a proportional DC current or voltage signal. The transducer is intended for use on single-phase or three-phase networks and provides an output suitable for PLCs, PCs, microprocessor controls, indicators, and alarm units.
The measuring principle is average-value measurement. The input signal passes through a transformer that provides galvanic insulation between the input and output. The signal is then rectified, smoothed, and amplified to produce the DC output. The TAC-311DG requires a constant auxiliary supply, which is also transformer-isolated from the output.
The transducer provides Class 0.5 accuracy from -10 to +55 °C according to IEC 688. For the 0–10 V output version, Class 0.5 accuracy applies at a load of at least 100 kΩ, while Class 1.0 accuracy applies at a load of at least 10 kΩ. The response time is less than 300 ms, with output ripple below 0.5% peak-to-peak.
The standard 4–20 mA output provides a live-zero signal range. Span can be adjusted by ±20% of full-scale output, and zero can be adjusted by ±20% of the 4 mA zero level. Other available output configurations include 0–5 mA, 0–10 mA, 0–20 mA, and 0–10 V DC. The output limit for the 4–20 mA version is below 22.0 mA DC.
The TAC-311DG is available in several auxiliary-supply configurations: 24 Vdc, 48–110 Vdc, 88–220 Vdc, and 110/230/440 V AC. The AC supply accepts ±20% voltage variation and operates continuously from 45 to 65 Hz. The transducer’s input, output, and auxiliary supply are galvanically isolated from one another at 2200 V, 50 Hz, for one minute.
The unit is housed in a compact 55 × 75 mm enclosure with a 110 mm depth and weighs approximately 0.4 kg. It can be mounted on a 35 mm DIN rail or base-mounted. The case is rated IP40 and the terminals are rated IP20, so the transducer should be installed in a suitable electrical enclosure.
Applications & System Role
In a measurement and control architecture, the DEIF TAC-311DG sits between an AC current-measurement point and a control, monitoring, or alarm system. It receives an AC current signal, converts it to a proportional DC signal, and provides that signal to a PLC, PC, microprocessor control, indicator, or alarm unit.
The transducer is relevant for AC current monitoring in single-phase or three-phase electrical systems operating at 45–65 Hz. Its isolated output and adjustable span and zero support integration with control systems that require a scaled current or voltage signal.
FAQ
What is the DEIF TAC-311DG?
The DEIF TAC-311DG is a single-function AC current transducer that converts sinusoidal AC current into a proportional DC current or voltage signal.
What does the TAC-311DG measure?
It measures sinusoidal AC current on single-phase or three-phase networks.
What is the accuracy class of the TAC-311DG?
It provides Class 0.5 accuracy from -10 to +55 °C according to IEC 688.
What output signals are available?
The standard output is 4–20 mA DC. Other available outputs include 0–5 mA, 0–10 mA, 0–20 mA, and 0–10 V DC.
Does the TAC-311DG require an auxiliary supply?
Yes. The TAC-311DG requires an auxiliary supply; available supply variants include 24 Vdc, 48–110 Vdc, 88–220 Vdc, and 110/230/440 V AC.
What frequency range does it support?
It supports AC networks from 45 to 65 Hz.
What isolation does the transducer provide?
It provides 2200 V, 50 Hz, 1-minute galvanic isolation between input, output, and auxiliary supply.
How is the TAC-311DG mounted?
It can be mounted on a 35 mm DIN rail or base-mounted, and has a 55 × 75 mm housing with a 110 mm depth.