Description
Key Technical Specifications
| Parameter | Specification / Value |
| Manufacturer | Emerson Process Management |
| Part Number / System ID | KJ3002X1-BF1 |
| Alternative Model Code | VE4002S1T2B1 / Assembly 12P0683X082 |
| System Compatibility | Emerson DeltaV Distributed Control System |
| Number of Channels | 8 analog input channels |
| Signal Type | 4–20 mA DC / HART protocol transparent |
| Analog-to-Digital Conversion | 16-bit resolution |
| Accuracy | ±0.1% of full scale @ 25°C |
| Field Loop Power | Provides 24 VDC transmitter power per channel |
| Backplane Power Consumption | 24 VDC @ 300 mA (max) via local bus carrier |
| Isolation Rating | 500 VAC channel-to-bus galvanic isolation |
| Operating Temperature | −40°C to +70°C (−40°F to +158°F) |
Product Introduction & Supply Chain Strategy
The Emerson DeltaV KJ3002X1-BF1 (VE4002S1T2B1) is an 8-channel 4–20 mA HART analog input module engineered for high-precision process variable acquisition across DeltaV automation systems. It converts field transmitter signals—such as pressure, temperature, level, and flow—into digital values for central controller execution while supporting HART pass-through for remote asset management software.
Maintaining the KJ3002X1-BF1 as New Surplus safeguards critical plant operations against unexpected loop outages caused by electrical surges or hardware aging. Purchasing factory-fresh original surplus prevents calibration drift, degraded ADC components, and communication failure risks common to second-hand electronics, ensuring 100% loop accuracy and a low Total Cost of Ownership (TCO).

KJ3002X1-BF1

KJ3002X1-BF1
Installation & Configuration Guide
1.Pre-Installation Preparation:Prerequisite & Safety Setup.
Verify cabinet safety status and confirm local bus power conditions. Wear a grounded ESD wrist strap before handling the module to protect internal semiconductor circuits against static discharge. Confirm that the corresponding 8-slot carrier and terminal block base (e.g., KJ2201X1-JA1) are securely installed.
2.Removing an Existing Module:Hardware Extraction.
Unlatch the top and bottom module retaining clips on the card face. Carefully pull the module straight forward off the carrier slot to disengage the backplane pin connections without twisting the card enclosure.
3.Mounting the Replacement Card:Module Insertion & Locking.
Align the replacement KJ3002X1-BF1 card with the guide rails of the target carrier slot. Push the module firmly inward until the backplane connectors seat completely, then press the top and bottom locking tabs until they snap securely into place.
4.Power-On, LED Check, and Diagnostics:Loop Validation.
Verify that the green Power/Status LED on the module front panel illuminates solid. Open DeltaV Explorer or DeltaV Diagnostics on the engineering workstation to confirm that the controller recognizes the new module and that all 8 HART analog channels display valid process readings.
Firmware/Software Versions & Upgrade Notes
- Hardware Compatibility: Fully compatible with all Emerson DeltaV controllers and local bus carriers supporting M-Series / S-Series 8-channel analog input modules.
- Auto-Sensing Architecture: The DeltaV system automatically downloads software configuration parameters and channel definitions from the CPU controller to the replacement KJ3002X1-BF1 module upon insertion.
- HART Pass-Through Precautions: Ensure that HART device descriptions (DDs) on your AMS Device Manager station match your field instruments. Swapping the hardware module does not erase instrument calibration parameters stored in field transmitters.
Frequently Asked Questions (FAQ)
Why is New Surplus preferred over refurbished DeltaV analog cards?
Refurbished analog modules frequently suffer from component drift, aging capacitors, and micro-cracks from past thermal stress, leading to inaccurate 4–20 mA process readings or sudden channel failures. Our New Surplus KJ3002X1-BF1 cards are uninstalled, factory-fresh original units that guarantee original OEM measurement precision and long operational lifespan.
How do you verify that this card is authentic and unused?
Every unit undergoes strict inbound quality verification. We inspect original Emerson packaging, verify zero insertion wear on backplane edge pins, check for flawless circuit board physical condition, and perform power-on diagnostic checks. A complete QC report accompanies each shipment.
Does the support hot-swapping under power?
Yes. DeltaV I/O modules support “plug-and-play” hot-swapping on active local bus carriers under proper maintenance guidelines. However, removing an active module will take all 8 connected analog input channels offline, which may affect active control loops or trip interlocks. Always verify safety procedures before removing a live card.
Can this module supply power to 2-wire field transmitters directly?
Yes. The provides integrated 24 VDC loop excitation power across its channels, allowing direct connection to passive 2-wire HART field transmitters through the mating terminal block base.
What warranty coverage comes with this New Surplus unit?
We back this New Surplus Emerson DeltaV analog input card with a full 1-year functional replacement warranty. Should any hardware defect occur under standard operational conditions within 12 months, we provide an immediate direct replacement or full refund to protect your plant maintenance schedule.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626