Sale!

Emerson SE3007 DeltaV SX Controller Module

The Emerson SE3007 is a DeltaV SX Controller module designed to execute process control logic and manage system communications within Emerson DeltaV S-series distributed control system (DCS) architectures. Built to host control strategies, alarms, trends, and field I/O communications, the unit supports up to 1,500 Device Signal Tags (DSTs) and 3,200 SCADA tags, operating as a central processing node for continuous and batch process environments.

Categories: , , , , SKU: SE3007 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Emerson SE3007 is a DeltaV SX Controller module designed to execute process control logic and manage system communications within Emerson DeltaV S-series distributed control system (DCS) architectures. Built to host control strategies, alarms, trends, and field I/O communications, the unit supports up to 1,500 Device Signal Tags (DSTs) and 3,200 SCADA tags, operating as a central processing node for continuous and batch process environments.

Equipped with 96 MB of user memory, the Emerson SE3007 supports flexible module execution rates ranging from 100 ms up to 60 seconds. It is designed for mounting on S-series carrier backplanes without requiring mounting screws, simplifying cabinet assembly and maintenance. The controller features automatic I/O detection, self-addressing capabilities on the DeltaV Area Control Network, and internal power management operating off a 5 VDC backplane supply.

 

Key Technical Specifications

Specification Value / Detail
Product Type Process Controller Module
Control System Series Emerson DeltaV S-Series
Device Signal Tag (DST) Limit 1,500
SCADA Tag Capacity 3,200
User Memory 96 MB
Module Execution Rates 100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 30 s, 60 s
Max Data Throughput 4,000 values/sec sent, 500 values/sec received
Max Unsolicited Client Nodes 120
Input Voltage 5 VDC (1.4 A maximum)
Power Dissipation 5.0 W typical, 7.0 W maximum
Internal Protection 3.0 A non-replaceable internal fuse
Operating Temperature -40 °C to 60 °C (-40 °F to 140 °F)
Relative Humidity 5% to 95%, non-condensing
Physical Dimensions 13.0 cm × 1.9 cm × 19.1 cm (5.12 in × 0.75 in × 7.52 in)
Weight Approximately 0.2 kg (0.44 lbs)

 

Detailed Product Overview

The Emerson SE3007 DeltaV SX Controller acts as the real-time execution engine for DeltaV automation architectures. It decouples strategy execution from higher-level operator workstations by processing function blocks, managing I/O scan cycles, assigning timestamps, and managing local alarm conditions directly at the controller level. By executing logic locally and delivering process data across redundant control networks, the module provides deterministic processing performance needed for complex plant loops.

Hardware architecture in the SX series eliminates traditional mounting hardware, allowing the controller to latch directly onto dedicated DeltaV system carrier slots. The SE3007 manages communication across the I/O subsystem and supports pass-through capabilities for smart HART field device data. This HART data pass-through enables asset management software to perform remote instrument calibration, diagnostics, and status checks without interrupting process control strategies.

 

Engineering Selection Highlights

  • 1,500 DST Capacity: Provides sufficient capacity to execute control strategies for mid-sized process units and multi-loop control schemes.
  • 96 MB Configurable Memory: Supports allocation of complex control logic, sequence function charts, and trend data collections.
  • Fast Loop Execution: Offers configurable execution rates down to 100 ms for fast-responding control loops and emergency shutdown functions.
  • Screw-Free Installation: Designed for quick insertion onto S-series carrier assemblies, reducing installation time during system deployment or module replacement.
  • Extended Thermal Operating Envelope: Qualified to operate from -40 °C to 60 °C, supporting installation in severe industrial field enclosures.
SE3007

SE3007

SE3007

SE3007

Dimensions, Mounting & Connection Notes

  • Dimensions: Measures 13.0 cm in height, 1.9 cm in width, and 19.1 cm in depth.
  • Weight: Weighs approximately 0.2 kg.
  • Mounting: Snaps directly into a dedicated slot on the DeltaV S-series system carrier without requiring mounting screws.
  • Network & I/O Interfaces: Interconnects with the DeltaV control network and field I/O channels through multi-pin connectors integrated on the backplane carrier.
  • Environmental Limits: Requires a non-condensing relative humidity range between 5% and 95% and provides structural resistance against mechanical shock up to 10 g (11 ms half-sine).

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
System Architecture Emerson DeltaV S-Series DCS Integrates directly into DeltaV Area Control Networks
Hardware Carrier S-Series Controller Carrier Plugs directly into assigned controller slots on the carrier base
Field Device Interface HART & standard DeltaV I/O cards Passes HART diagnostic data transparently to management software
Power Supply S-Series System Power Supply Powered via 5 VDC backplane connection from carrier bus

 

FAQ

What is the Emerson SE3007?

The Emerson SE3007 is an SX controller module used in the DeltaV Distributed Control System (DCS) to manage process execution and network communication.

What is the Device Signal Tag (DST) capacity of the SE3007?

The SE3007 supports a maximum capacity of 1,500 Device Signal Tags (DSTs) and 3,200 SCADA tags.

How is the SE3007 mounted?

It mounts directly onto a DeltaV S-series controller carrier backplane using built-in latching mechanisms, eliminating the need for mounting screws.

What execution rates does the controller support?

The module supports multiple configurable execution rates: 100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 30 s, and 60 s.

Does the SE3007 support smart field instrument communications?

Yes, the controller supports HART pass-through, allowing asset management applications to communicate directly with connected HART devices.

 

Verification & Troubleshooting Notes

  • Power & Status Inspection: Verify the front panel diagnostic LEDs to confirm proper module power-up and operational status on the 5 VDC backplane bus.
  • Auto-Addressing: Upon insertion into an active carrier slot, the controller automatically assigns itself an address on the DeltaV control network.
  • Protection Circuitry: The module contains internal 3.0 A non-replaceable fuses; if the unit experiences severe overcurrent, it must be replaced rather than serviced in the field.