Emerson SE4608T01 12-Channel IS Electronic Marshalling Baseplate

Item Specification
Manufacturer / model Emerson SE4608T01
Product type IS CHARM baseplate assembly
System family Emerson DeltaV IS Electronic Marshalling
Channels per baseplate 12
Included terminal blocks 12 standard IS CHARM terminal blocks
Included address terminal block IS CHARM address terminal block
Included separation hardware Baseplate separation wall
Terminal-block color Light blue
Field-wire size 0.32 to 2.5 mm² (22 to 14 AWG)
Wire strip length 7 to 9 mm (0.28 to 0.36 in)
Categories: , , , , SKU: SE4608T01 Brand:

Description

Core Product Summary

The Emerson SE4608T01 is an intrinsically safe (IS) CHARM baseplate assembly for DeltaV IS Electronic Marshalling. It provides mounting, power, communication, and field-terminal connections for 12 IS CHARMs and their removable IS terminal blocks.

The assembly includes an IS CHARM baseplate, an IS CHARM address terminal block, 12 standard IS CHARM terminal blocks, and a baseplate separation wall. It connects to a CHARM I/O Card (CIOC) carrier through baseplate separators and provides redundant power and communication buses to the installed IS CHARMs. The light-blue IS terminal blocks identify the field wiring as intrinsically safe and are mechanically keyed to prevent installation of a non-IS CHARM.

 

Key Technical Specifications

Item Specification
Manufacturer / model Emerson SE4608T01
Product type IS CHARM baseplate assembly
System family Emerson DeltaV IS Electronic Marshalling
Channels per baseplate 12
Included terminal blocks 12 standard IS CHARM terminal blocks
Included address terminal block IS CHARM address terminal block
Included separation hardware Baseplate separation wall
Terminal-block color Light blue
Field-wire size 0.32 to 2.5 mm² (22 to 14 AWG)
Wire strip length 7 to 9 mm (0.28 to 0.36 in)
Standard IS terminal-block connections 4 screw-cage terminals
Maximum terminal-block current 45 mA at 28 V DC maximum
Shield connections One screw-cage terminal per channel plus one for cable shield
Shield connector finish Gold-plated connectors for shield continuity
Addressing One address plug, positions 1 through 8
Communication bus Redundant RS-485 communication bus
Field power Redundant 24 V DC bus
Mounting T-type DIN rail with latch
Operating temperature -40 to 70 °C
Storage temperature -40 to 85 °C
Relative humidity 5 to 95%, non-condensing
Protection rating IP20
Contaminant rating ISA-S71.04-1985 Class G3 conformal coating
Shock rating 10 g half-sine wave for 11 ms
Vibration rating 1 mm peak-to-peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz

 

Detailed Product Overview

The Emerson SE4608T01 is the field-side mounting and termination platform for intrinsically safe channels in a DeltaV IS Electronic Marshalling system. Each baseplate supports 12 IS CHARMs, with each CHARM providing signal characterization, galvanic isolation, fault isolation, and basic analog-to-digital conversion for one field channel.

The assembly is supplied with 12 standard IS CHARM terminal blocks. These light-blue terminal blocks provide four screw-cage terminals each and support 2-wire and 4-wire field devices, including conventional analog and discrete instrumentation and 2-, 3-, and 4-wire RTD sensors. Each terminal block also includes a shield connection, with gold-plated connectors maintaining shield continuity.

The SE4608T01 includes an IS CHARM address terminal block and a baseplate separation wall. The separation wall is required at the beginning and end of an IS CHARM baseplate row, as well as between IS CHARM baseplates. It is also used when connecting IS baseplates to CIOC carriers, baseplate extenders, or baseplate terminators.

The baseplate connects to the CIOC carrier and receives redundant 24 V DC field power and redundant RS-485 communication. IS CHARMs inserted into the terminal blocks provide galvanically isolated field power through internal isolation transformers, eliminating the need for separate external barriers and associated inter-cabinet wiring. The IS CHARM keying system locks each terminal block to the installed CHARM type, preventing insertion of an incorrect IS CHARM during maintenance.

Up to eight IS CHARM baseplates can be connected to one CIOC. IS and non-IS CHARM baseplates can be combined on the same CIOC, subject to Emerson’s installation rules; however, an IS baseplate cannot be extended directly with a non-IS baseplate.

SE4608T01

SE4608T01

SE4608T01

SE4608T01

Dimensions, Mounting & Connection Notes

The SE4608T01 mounts on a T-type DIN rail using a DIN-rail latch. It is installed below the CHARM I/O Card carrier, with up to eight CHARM baseplates mounted beneath one carrier. The baseplates snap to the DIN rail and interconnect as they are installed.

Each of the 12 standard IS terminal blocks provides four screw-cage terminals for field wiring. Acceptable wire size is 0.32 to 2.5 mm² (22 to 14 AWG), with a wire strip length of 7 to 9 mm (0.28 to 0.36 in). The standard IS terminal block is rated for a maximum current of 45 mA at 28 V DC maximum.

Each channel includes a screw-cage shield terminal, and the baseplate provides an additional screw-cage terminal for the cable shield. Shield connections use gold-plated connectors to maintain shield continuity.

The baseplate includes a black address terminal block with no field-wire connections. It accepts an address plug that assigns the baseplate position, from address 1 through 8. The included baseplate separation wall must be installed at the beginning and end of an IS baseplate row and between IS baseplates.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Control system Emerson DeltaV IS Electronic Marshalling The SE4608T01 is an IS CHARM baseplate assembly
Carrier CHARM I/O Card (CIOC) carrier Connects to the carrier through baseplate separators
IS CHARMs IS AI 4–20 mA HART, IS AO 4–20 mA HART, IS RTD, IS Thermocouple/mV, IS DI NAMUR, and IS DO 45 mA Insert the appropriate IS CHARM into each terminal-block position
Terminal blocks Standard IS CHARM terminal blocks Included in the SE4608T01 assembly
Addressing SE4602 or SE4613 address plugs SE4602 includes address plugs 1 through 8; SE4613 includes address plugs 1 through 4
Baseplate separation Baseplate separation wall Required at both ends of an IS baseplate row and between IS baseplates
CIOC connection Special fuse in each of the two CIOC power-supply lines Required when connecting IS CHARM baseplates to a CIOC carrier
Controllers SD Plus, SX, and SQ with DeltaV v11.3.1 or later; MD Plus, MQ, MX, and PK with DeltaV v14.3 or later IS CHARM I/O hardware requires these controller/software combinations
CIOC2 DeltaV v13.3.1 or later CIOC2 requires this software version; hotfixes are documented for v13.3.1 and v13.3.2
Network DeltaV Smart Switches Required between controllers and CIOCs for Electronic Marshalling
DIN-rail retention VE4054DRS DIN-rail stop One DIN-rail stop is required for each vertical DIN rail to lock baseplates in position

 

 

FAQ

What is the Emerson SE4608T01?
It is an Emerson DeltaV IS Electronic Marshalling baseplate assembly for 12 intrinsically safe CHARMs and their IS terminal blocks.

How many channels does the SE4608T01 support?
It supports 12 IS CHARM channels.

What is included in the SE4608T01 assembly?
It includes an IS CHARM baseplate, an IS CHARM address terminal block, 12 standard IS CHARM terminal blocks, and a baseplate separation wall.

Which IS CHARM types can be installed?
The baseplate supports IS AI 4–20 mA HART, IS AO 4–20 mA HART, IS RTD, IS Thermocouple/mV, IS DI NAMUR, and IS DO 45 mA CHARMs.

What wire size and strip length are used?
Field wiring uses 0.32 to 2.5 mm² (22 to 14 AWG) wire, stripped 7 to 9 mm (0.28 to 0.36 in).

How is the baseplate addressed?
It uses an address plug in the IS CHARM address terminal block. Address plugs are available as positions 1 through 8 (SE4602) or 1 through 4 (SE4613).

Can IS and non-IS baseplates be mixed on one CIOC?
Yes, IS and non-IS CHARM baseplates can be combined on the same CIOC, provided Emerson’s installation rules are followed. An IS baseplate cannot be extended directly with a non-IS baseplate.

What software is required for DeltaV IS Electronic Marshalling?
SD Plus, SX, and SQ controllers require DeltaV v11.3.1 or later. MD Plus, MQ, MX, and PK controllers require DeltaV v14.3 or later. CIOC2 hardware requires DeltaV v13.3.1 or later.

 

Documented Performance Data

Metric Value / Range Operating Condition
Channels per baseplate 12 SE4608T01 IS CHARM baseplate assembly
Baseplates per CIOC 8 IS CHARM baseplates connected to one CIOC
Standard IS terminal-block current 45 mA maximum 28 V DC maximum
Terminal-block connections 4 screw-cage terminals Standard IS CHARM terminal block
Shield connections 1 per channel plus 1 cable-shield terminal IS CHARM baseplate
Operating temperature -40 to 70 °C Common environmental specification for IS Electronic Marshalling components
Vibration rating 1 mm peak-to-peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz Common environmental specification for IS Electronic Marshalling components