Sale!

Emerson VE3006 KJ2003X1-BB1 DeltaV DI 24V DC Dry Contact Card

Parameter Specification
Model Number VE3006
Assembly Part Number KJ2003X1-BB1
Manufacturer Emerson (DeltaV System)
Product Family DeltaV Traditional I/O Series
Module Type 12-Channel 24 V DC Discrete Input Card
Number of Channels 12 Discrete Inputs
Input Signal / Voltage 24 V DC (Dry Contact or Externally Powered)
Categories: , , , , SKU: VE3006 KJ2003X1-BB1 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Emerson VE3006 (Assembly Part Number: KJ2003X1-BB1) is a 12-channel 24 V DC discrete input card designed for the Emerson DeltaV Distributed Control System (DCS). Functioning within DeltaV I/O carrier assemblies, it senses binary field states from limit switches, pushbuttons, proximity sensors, pressure switches, and auxiliary relay contacts across industrial process automation systems.

Configured for 24 V DC dry contact or powered-input operation, the VE3006 interfaces directly with standard field instrumentation. Each of its 12 channels features optical isolation to protect the internal DeltaV I/O bus from external ground loops and electrical transients. The module supports hot-swapping under power and includes channel-level LED status indicators on the front panel for rapid visual diagnostic verification during system operation.

 

Key Technical Specifications

Parameter Specification
Model Number VE3006
Assembly Part Number KJ2003X1-BB1
Manufacturer Emerson (DeltaV System)
Product Family DeltaV Traditional I/O Series
Module Type 12-Channel 24 V DC Discrete Input Card
Number of Channels 12 Discrete Inputs
Input Signal / Voltage 24 V DC (Dry Contact or Externally Powered)
Isolation Optical isolation between field terminals and system backplane
Module Insertion Hot-swappable in energized DeltaV I/O carriers
Status Indicators Front panel LEDs for power, card health, and channel states (1–12)
Operating Temperature 0°C to 60°C (32°F to 140°F)

 

Detailed Product Overview

The Emerson VE3006 / KJ2003X1-BB1 discrete input module forms an essential physical input layer for the DeltaV automation system. Engineered for high availability in chemical plants, oil refineries, pharmaceutical facilities, and power stations, the card converts 24 V DC field contact states into digital logic signals processed by DeltaV controllers.

The card features 12 isolated channels designed to detect binary open/closed conditions. Channel circuitry includes hardware noise filtering to suppress mechanical switch contact chatter and induced industrial noise. Optocouplers provide galvanic isolation between the field wiring terminals and the internal system local bus, protecting sensitive system components against high-voltage surges and ground potential differences.

The VE3006 card plugs directly into a dedicated slot on a DeltaV 8-slot or 2-slot I/O carrier. Full hot-swapping capability allows plant technicians to replace a module under live system power without disrupting adjacent operational I/O cards or stopping controller execution. Dedicated channel LEDs on the front faceplate illuminate bright green when an input signal is active, allowing quick visual field inspection.

VE3006 KJ2003X1-BB1

VE3006 KJ2003X1-BB1

VE3006 KJ2003X1-BB1

VE3006 KJ2003X1-BB1

Engineering Selection Highlights

  • 12-Channel High Density → Consolidates 12 discrete 24 V DC input signals into a single DeltaV carrier slot to optimize cabinet footprint.
  • Galvanic Optical Isolation → Protects system electronics from field-side voltage spikes, noise, and ground loops up to nominal isolation ratings.
  • Hot-Swappable Design → Modules can be installed or removed under live system power, minimizing process downtime during maintenance.
  • Integrated Channel Diagnostics → Individual front-panel status LEDs provide immediate channel-by-channel confirmation of field signal states.
  • Native DeltaV Integration → Recognized automatically by DeltaV software, enabling rapid I/O auto-sensing and assignment within DeltaV Explorer.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Host Platform Emerson DeltaV Distributed Control System Plugs into standard DeltaV 8-slot or 2-slot Traditional I/O Carriers.
Required Terminal Block DeltaV 8-Channel / 12-Channel Terminal Block Connects to matching DeltaV field terminal blocks (such as 12-channel screw or mass termination blocks).
Power Supply 24 V DC Field Power Field contacts require a 24 V DC bulk power source routed through the terminal block.
Engineering Software DeltaV Configuration Software Auto-sensed by DeltaV Explorer; channel parameters configured via standard DeltaV software.

 

Dimensions, Mounting & Connection Notes

  • Mounting: Snaps securely into card slots on DeltaV I/O carriers mounted on standard DIN rails.
  • Carrier Insertion: Align internal card guides and push firmly until top and bottom carrier latches click into place.
  • Terminal Connections: Wiring terminates at the dedicated DeltaV field terminal block installed directly below the card slot.
  • Hot-Swap Procedure: To replace, depress top and bottom retention latches simultaneously and pull the card straight out from the carrier. Insert the replacement VE3006 card directly into the energized slot.

 

FAQ

What is the difference between VE3006 and KJ2003X1-BB1?

VE3006 is the model number for the DeltaV 12-channel 24 V DC discrete input card, while KJ2003X1-BB1 is the hardware assembly part number printed on the module board and label.

Does the VE3006 module support hot-swapping?

Yes, the VE3006 card is fully hot-swappable and can be removed or replaced without turning off system or carrier power.

How many channels are available on the VE3006 card?

The VE3006 provides 12 discrete input channels operating at 24 V DC logic levels.

What terminal block is required for the VE3006?

It requires a compatible DeltaV 12-channel field terminal block (such as a standard 12-channel screw terminal block or mass header terminal block) mounted on the carrier slot.

What signal type does the VE3006 discrete input card accept?

It accepts 24 V DC discrete signals, including dry contact closures powered by an external 24 V DC supply or active 24 V DC PNP output field devices.

 

Verification & Troubleshooting Notes

System Fusing & Field Wiring Notice

Ensure field contact power circuits are properly fused at the 24 V DC bulk distribution panel before energizing field loops. Incorrect wiring of high voltage AC lines to 24 V DC input terminals will permanently damage the input card and terminal assembly.

1

Verify Card Seating and Power LED

Physical check

1.Verify Card Seating and Power LED:Physical check.

Insert the VE3006 card firmly into the DeltaV carrier slot until retaining latches click. Check the top green POWER / CARD OK LED. Verification: The green Power LED illuminates steadily, confirming the card is receiving local bus power.

2

Check DeltaV Explorer Auto-Sensing

Software verification

2.Check DeltaV Explorer Auto-Sensing:Software verification.

Open DeltaV Explorer on the system engineering workstation and navigate to the assigned I/O subsystem slot. Verification: The VE3006 card appears online without diagnostic warning icons or configuration mismatch faults.

3

Verify Input Channel LED and Signal State

Field signal test

3.Verify Input Channel LED and Signal State:Field signal test.

Actuate a connected field switch (or jumper 24 V DC across the input terminals) for a specific channel. Verification: The corresponding front panel channel LED (1 through 12) lights up bright green, and the channel state toggles to ON in the DeltaV diagnostic software.