Sale!

Emerson VE4001S2T2B4 DeltaV 8-Channel Analog Input HART Card

Parameter Specification
Model Number VE4001S2T2B4
Manufacturer Emerson (DeltaV System)
Product Family DeltaV Traditional I/O Series
Module Type 8-Channel 4–20 mA Analog Input Card with HART
Number of Channels 8 Analog Inputs
Signal Range 4 to 20 mA DC (Supports 1–5 V DC input conversion)
Protocol Support HART Pass-Through (HART transparent)
Isolation Optical isolation between field terminals and system local bus
Redundancy Simplex card configuration
Module Insertion Hot-swappable in energized DeltaV I/O carriers
Operating Temperature 0°C to 60°C (32°F to 140°F)
Operating Humidity 5% to 95% RH (non-condensing)
Categories: , , , , SKU: VE4001S2T2B4 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Emerson VE4001S2T2B4 is an 8-channel 4–20 mA analog input card with HART communication support, designed for the Emerson DeltaV Distributed Control System (DCS). Functioning within DeltaV Traditional I/O carrier architectures, it interfaces continuous field instrumentation—including pressure transmitters, flowmeters, temperature transmitters, and level gauges—with DeltaV controllers.

Model configuration code VE4001S2T2B4 designates an 8-channel isolated analog input hardware assembly featuring HART pass-through capabilities. Each channel converts analog current signals into digital process variables for system control logic while allowing bidirectional HART data pass-through to Emerson AMS Device Manager software. The module supports hot-swapping under live system power and installs directly into standard DeltaV 8-slot or 2-slot I/O carriers.

 

Key Technical Specifications

Parameter Specification
Model Number VE4001S2T2B4
Manufacturer Emerson (DeltaV System)
Product Family DeltaV Traditional I/O Series
Module Type 8-Channel 4–20 mA Analog Input Card with HART
Number of Channels 8 Analog Inputs
Signal Range 4 to 20 mA DC (Supports 1–5 V DC input conversion)
Protocol Support HART Pass-Through (HART transparent)
Isolation Optical isolation between field terminals and system local bus
Redundancy Simplex card configuration
Module Insertion Hot-swappable in energized DeltaV I/O carriers
Operating Temperature 0°C to 60°C (32°F to 140°F)
Operating Humidity 5% to 95% RH (non-condensing)

 

Detailed Product Overview

The Emerson VE4001S2T2B4 analog input module serves as a primary measurement acquisition interface within the DeltaV automation platform. Built for continuous operation in oil and gas production, chemical refining, power generation, and pharmaceutical processing, the card processes 4–20 mA current loop signals using high-resolution analog-to-digital converters (ADCs).

The card features eight independent channels, each equipped with dedicated hardware filtering to suppress high-frequency line noise and 50/60 Hz power frequency interference. Galvanic optical isolation separates the field wiring terminals from the internal DeltaV backplane, protecting controller microprocessors against ground potential shifts, field voltage surges, and lightning transients.

Integrated HART pass-through circuitry enables the module to superimpose digital device management signals onto the standard 4–20 mA analog loop. This allows maintenance technicians to perform remote sensor calibration, view secondary process variables, and run device diagnostics using AMS Device Manager without interrupting primary loop control signals. The module plugs into standard DeltaV carrier slots and supports hot-swapping for rapid field replacement without turning off system power.

 

Engineering Selection Highlights

  • 8-Channel High Density → Consolidates eight independent 4–20 mA current loops into a single DeltaV carrier slot to optimize control cabinet layout.
  • HART Digital Pass-Through → Superimposes digital HART signals over analog loops to support asset management and predictive diagnostic software.
  • Galvanic Optical Isolation → Protects system backplane electronics from field-side voltage spikes, industrial noise, and ground loops.
  • Hot-Swappable Module Architecture → Can be installed or removed under live system power to minimize process downtime during loop maintenance or card replacement.
  • Native DeltaV Sensing → Automatically detected and configured within DeltaV Explorer, simplifying I/O loop commissioning and channel parameter assignment.
VE4001S2T2B4

VE4001S2T2B4

VE4001S2T2B4

VE4001S2T2B4

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Host Platform Emerson DeltaV Distributed Control System Plugs into standard DeltaV 8-slot or 2-slot Traditional I/O Carriers.
Required Terminal Block DeltaV 8-Channel Field Terminal Block Connects to matching DeltaV 8-channel terminal blocks (screw or mass termination versions).
Loop Power Supply 24 V DC Transmitter Power Field loops require 24 V DC bulk power routed through the carrier terminal block for 2-wire transmitters.
Configuration Tool DeltaV Engineering & AMS Device Manager Auto-sensed by DeltaV Explorer; HART parameters managed via AMS Device Manager.

 

Dimensions, Mounting & Connection Notes

  • Mounting: Snaps into card slots on DeltaV I/O carriers mounted on standard 35 mm DIN rails.
  • Carrier Insertion: Align internal card guides and push firmly until top and bottom retention latches engage into place.
  • Terminal Connections: Field instrumentation wires connect to the dedicated DeltaV 8-channel terminal block positioned directly below the card slot.
  • Hot-Swap Procedure: Depress top and bottom retention latches simultaneously and pull the card straight out from the carrier. Insert the replacement VE4001S2T2B4 card directly into the energized slot.

 

FAQ

What is the Emerson VE4001S2T2B4?

The VE4001S2T2B4 is an 8-channel 4–20 mA analog input card with HART communication pass-through for the Emerson DeltaV Distributed Control System.

Does the VE4001S2T2B4 support HART field instruments?

Yes, the module features built-in HART pass-through functionality, allowing AMS Device Manager software to communicate with smart field transmitters over the 4–20 mA loop.

How many channels does the VE4001S2T2B4 card provide?

The module features eight independent 4–20 mA DC analog input channels.

Can the VE4001S2T2B4 card be hot-swapped during operation?

Yes, the card is fully hot-swappable and can be inserted or removed without switching off system power or stopping adjacent I/O modules.

What terminal block is required for the VE4001S2T2B4?

It requires a compatible DeltaV 8-channel field terminal block (such as a standard 8-channel screw terminal block or mass header terminal block) mounted on the carrier slot.

 

Verification & Troubleshooting Notes

Field Loop Power & Polarity Hazard

Verify 24 V DC auxiliary loop power polarity and loop fuses before energizing field loops. Reverse power connections or direct short circuits across input channels can damage field transmitters or channel input circuitry.

1

Verify Card Seating and Power LED

Physical & power check

1.Verify Card Seating and Power LED:Physical & power check.

Push the VE4001S2T2B4 card firmly into the DeltaV carrier slot until both retaining latches click closed. Observe the green POWER / CARD OK LED on the faceplate. Verification: The green Power LED illuminates steadily, confirming proper internal backplane power connection.

2

Verify Auto-Sensing in DeltaV Explorer

Software & diagnostics check

2.Verify Auto-Sensing in DeltaV Explorer:Software & diagnostics check.

Open DeltaV Explorer on the system workstation and navigate to the corresponding carrier slot address. Verification: The VE4001S2T2B4 card displays an online status without diagnostic error icons or hardware mismatch warnings.

3

Test 4–20 mA Analog Loop Signal

Signal verification

3.Test 4–20 mA Analog Loop Signal:Signal verification.

Inject a known 4–20 mA test current (e.g., 4 mA, 12 mA, 20 mA) into a specific input channel using a calibrated loop calibrator while observing the live value in DeltaV Control Studio. Verification: The measured digital value in the software matches the injected test current within standard accuracy tolerances.