Description
Core Product Summary
The Emerson VE4003S2B1 is a DeltaV Series 2 analog input card from the M-Series Traditional I/O family. It provides eight channels of 4 to 20 mA input with HART communication support, and this orderable configuration pairs the card with the standard 8-channel I/O termination block on a DIN-rail I/O interface carrier. The card reads current signals from two-wire and four-wire transmitters and passes HART digital data — device variables, status, and configuration access — to the DeltaV system alongside the analog measurement.
Each channel is optically isolated from the system and factory tested to 1500 VDC. The card offers 0.1% of span accuracy over temperature, 16-bit resolution, and 0.05% of span repeatability, with a HART scan time of 600 to 800 ms typical per enabled channel. It supports simplex or redundant installation: two cards on a redundant standard I/O termination block are autosensed by the controller as a redundant pair.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Product type | Analog input card with HART, DeltaV Series 2 Traditional I/O |
| System family | Emerson DeltaV |
| Number of channels | 8 |
| Nominal signal range (span) | 4 to 20 mA |
| Full signal range | 1 to 22.5 mA, with over-range checking |
| Isolation | Each channel optically isolated from the system, factory tested to 1500 VDC |
| Accuracy over temperature range | 0.1% of span |
| Resolution | 16 bits |
| Repeatability | 0.05% of span |
| Roll-off frequency | ‘-3 dB at 2.7 Hz; -20.5 dB at half the sampling frequency |
| Calibration | None required |
| Optional fuse | 2.0 A |
| LocalBus current (12 VDC nominal) per card | 120 mA typical, 150 mA maximum |
| Field circuit power per card | 300 mA maximum at 24 VDC (+10%) |
| HART communications support | HART pass-through request/response, HART variable reporting, field device status reporting |
| HART scan time | 600–800 ms typical per enabled channel |
| Field wiring | 2-wire non-incendive; 4-wire non-arcing; 2-wire nL or ic; 4-wire nA |
| Operating temperature | ‘-40 to 70 °C (-40 to 158 °F) |
| Protection rating | IP20, NEMA 12 enclosure |
| Airborne contaminants | ISA-S71.04-1985 Class G3 (conformal coated) |
| Card dimensions (common I/O interface form factor) | H 10.7 cm × W 4.1 cm × D 10.5 cm (4.2 × 1.6 × 4.1 in.) |
Engineering Selection Highlights
- 8 HART-capable 4-20 mA channels — suited to smart transmitters where the analog loop measurement and HART digital data must both reach the DeltaV system; HART pass-through, variable reporting, and device status reporting are supported per channel.
- HART scan time of 600–800 ms typical per enabled channel — HART data is not real-time; control decisions must rely on the analog value, with HART data used for diagnostics, asset information, and configuration access.
- 0.1% of span accuracy and 16-bit resolution — sufficient for most process measurement loops; the 1 to 22.5 mA full signal range with over-range checking provides visibility into loop fault conditions beyond the normal span.
- 300 mA maximum field circuit power at 24 VDC per card — the card can power two-wire loops, and the aggregate loop power budget must respect this per-card limit when all eight channels supply transmitters.
- Standard 8-channel termination block on this configuration — fused, 4-wire, mass-termination, and redundant 8-channel blocks exist in the same family; the terminal block variant must match the existing field wiring scheme.
- Simplex or redundant installation — the same Series 2 card can be installed as a redundant pair on a redundant standard I/O termination block, with automatic switchover and no special channel configuration required.
- 1500 VDC channel-to-system optical isolation — isolates field loops from the system side; channels are not specified as isolated from each other.

VE4003S2B1

VE4003S2B1
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control system | DeltaV DCS, M-Series Traditional I/O subsystem | New I/O interfaces are acknowledged by the DeltaV engineering tools with basic configuration assigned automatically. |
| Software version | Series 2 analog input cards supported on DeltaV v10.3.1 and later | For earlier DeltaV versions, or where DNV marine certification is required, the manufacturer offers an alternate card revision. |
| Mounting | I/O interface carrier (DIN-rail mounted) | Card plugs into an assigned carrier slot; carriers can be installed before cards and termination blocks. |
| Termination block | Standard I/O termination block (8-channel) | The complete I/O interface is the card plus termination block; function and field wiring keys prevent incorrect card installation. |
| Redundancy | Redundant standard I/O termination block required for a redundant pair | The controller autosenses the pair, treats it as one card, and switches automatically on fault; switchover completes within two I/O bus scans. |
| Field power | 24 VDC bulk power, 300 mA maximum per card | Covers two-wire transmitter loops wired through the termination block. |
| Under-power replacement | Cards may be replaced under power in safe areas | In hazardous areas, applicable installation procedures must be followed. |
Dimensions, Mounting & Connection Notes
- Common I/O interface form factor: 10.7 cm high × 4.1 cm wide × 10.5 cm deep (4.2 × 1.6 × 4.1 in.).
- The card plugs directly into an assigned slot of the I/O interface carrier; the termination block can be pre-wired before card installation.
- Field wiring options for this card type: 2-wire non-incendive, 4-wire non-arcing, 2-wire nL or ic, and 4-wire nA configurations.
- An optional 2.0 A fuse supports field wiring protection on the termination block.
- Housing is labeled with the card type; cards carry power and internal error indicators with visible channel status LEDs.
- Environmental installation limits: -40 to 70 °C operating, 5–95% relative humidity non-condensing, IP20 protection requiring a NEMA 12 enclosure, ISA G3 corrosion resistance via conformal coating.
Detailed Product Overview
The VE4003S2B1 is the 8-channel, 4-20 mA HART analog input card within the DeltaV M-Series Traditional I/O range, ordered here with the standard 8-channel termination block. Its Series 2 designation matters for two reasons: these cards support both simplex and redundant installation using the same hardware, and their introduction is tied to specific DeltaV software versions, so version compatibility should be confirmed for the target system before specifying.
The measurement path is conservative and well-defined. The nominal span is 4 to 20 mA, but the card reads a full signal range of 1 to 22.5 mA with over-range checking — which is what allows the system to distinguish a healthy over-range reading from a loop fault and to detect conditions such as a saturated transmitter or a failing loop. Accuracy of 0.1% of span over the temperature range and 16-bit resolution place the card in the class needed for general process measurement. The input filter rolls off at -3 dB at 2.7 Hz, which suppresses noise on most process loops but means the card is intended for process-speed signals, not fast transient capture.
The HART capability is the card’s defining feature relative to non-HART input cards. HART pass-through request/response lets maintenance tools reach field devices through the system; HART variable reporting brings secondary digital variables into the system as configured values; and field device status reporting carries device-level fault flags into DeltaV alerts. The 600–800 ms typical HART scan time per enabled channel is the practical constraint to design around: HART communication is deliberately slow relative to the analog scan, so any use of HART variables should accommodate seconds-scale update rates, and enabling HART on all eight channels multiplies the polling load accordingly.
Power planning has two parts. The card itself draws 120 mA typical from the 12 VDC LocalBus, and the field side can deliver up to 300 mA at 24 VDC to power two-wire loops. When all eight channels feed two-wire transmitters, the aggregate transmitter load must stay within the per-card field power limit — a common oversight when upgrading from four to eight loops on one card.
Integration mechanics follow the Traditional I/O design. The card plugs into the DIN-rail carrier, and the termination block mounts independently, so field wiring can be completed before the card is installed. Keying posts on the termination block mechanically prevent the wrong card type from being inserted, which protects against the most common maintenance error. No calibration is required over the card’s life. For installations requiring input availability, a second card on a redundant termination block gives automatic, configuration-free failover managed entirely by the controller.
Applications & System Role
In a DeltaV architecture, the VE4003S2B1 occupies the analog input layer between field transmitters and the controller. It converts 4-20 mA loop signals into controller-readable values and simultaneously gives the system a path to HART data carried on the same pair of wires: device variables, configuration parameters, and status flags. This makes it the interface point where the primary measurement and the smart-device diagnostics of a modern transmitter both enter the DeltaV system.
Typical signal sources are two-wire pressure, flow, level, and temperature transmitters powered from the card’s 24 VDC field circuit, as well as four-wire transmitters with external power. The card’s role is measurement acquisition rather than control execution: control modules in the controller consume the channel values, while HART data feeds the system’s device management functions.
Installed as a redundant pair on a redundant standard termination block, the same hardware serves loops where measurement continuity matters enough to justify a standby card, with automatic switchover and hardware alerts covering both cards of the pair.
FAQ
What is the Emerson VE4003S2B1?
It is a DeltaV Series 2 analog input card providing eight 4-20 mA input channels with HART communication support, delivered with the standard 8-channel I/O termination block.
Which system does it belong to?
It belongs to the Emerson DeltaV M-Series Traditional I/O subsystem, mounted on DIN-rail I/O interface carriers.
What are its key specifications?
8 channels, 4-20 mA nominal span (1-22.5 mA full range with over-range checking), 0.1% of span accuracy, 16-bit resolution, 0.05% repeatability, 300 mA maximum field circuit power at 24 VDC, and per-channel optical isolation factory tested to 1500 VDC.
What does HART support include?
The card provides HART pass-through request/response, HART variable reporting, and field device status reporting, with a typical HART scan time of 600-800 ms per enabled channel.
Which termination block does it require?
This configuration uses the standard I/O termination block; fused, 4-wire, and mass-termination variants exist in the same family and must be matched to the field wiring scheme.
Can this card be used redundantly?
Yes. Series 2 cards support simplex or redundant installation; two cards on a redundant standard I/O termination block are autosensed as a redundant pair with automatic switchover.
Which DeltaV version is required?
Series 2 analog input cards of this type are supported on DeltaV v10.3.1 and later; an alternate card revision is available for earlier DeltaV versions or where DNV marine certification is required.
Does the card need calibration?
No calibration is required.