Sale!

Emerson VE4005S2B1 8-Channel 4-20 mA HART AO Card

Parameter Specification
Manufacturer Emerson
Model / Part Number VE4005S2B1
System Family DeltaV Traditional I/O (M-Series)
Module Type Analog Output Card (Series 2)
Channel Density 8 Channels
Output Signal Range 4-20 mA DC (HART active)
Signal Resolution 16-bit D/A conversion
Categories: , , , , SKU: VE4005S2B1 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Emerson VE4005S2B1 is an 8-channel analog output card designed for the DeltaV distributed control system. Operating within the DeltaV Traditional I/O subsystem (M-Series form factor), this Series 2 module converts digital control commands from DeltaV controllers into continuous 4-20 mA analog signals to drive field actuators, positioners, variable speed drives, and control valves.

This card features 8 independent output channels equipped with HART protocol pass-through, enabling digital device diagnostics, configuration, and status tracking to superimpose over 4-20 mA control loops. Designed to mount on standard DeltaV 2-wide or 8-wide I/O interface carriers, the VE4005S2B1 receives internal logic power directly from the 12V DC LocalBus backplane and pairs with matching 8-channel analog output terminal blocks for field cable landing.

 

Key Technical Specifications

Parameter Specification
Manufacturer Emerson
Model / Part Number VE4005S2B1
System Family DeltaV Traditional I/O (M-Series)
Module Type Analog Output Card (Series 2)
Channel Density 8 Channels
Output Signal Range 4-20 mA DC (HART active)
Signal Resolution 16-bit D/A conversion
Output Accuracy 0.1% of span over operating temperature range
LocalBus Power Consumption 85 mA typical, 150 mA maximum (12V DC nominal)
Field Circuit Power Supply 300 mA maximum at 24V DC (±10%)
Operating Temperature Range -40°C to +70°C (-40°F to +158°F)
Storage Temperature Range -40°C to +85°C (-40°F to +185°F)
Relative Humidity 5% to 95% non-condensing
Shock / Vibration 10 g half-sine wave (11 ms); 1 mm peak-to-peak (5–16 Hz), 0.5 g (16–150 Hz)

 

Detailed Product Overview

The Emerson VE4005S2B1 analog output card acts as an executive interface between the DeltaV control network and field-actuated process hardware. By converting internal system control commands into isolated 4-20 mA current loops across 8 channels, the module provides high-resolution, low-drift signal driving required for modulating control valves, I/P converters, and speed controllers.

The module supports bi-directional HART pass-through. This functionality allows secondary parameters, valve position feedback, and field device diagnostics to transmit between HART-enabled smart positioners and DeltaV engineering software without interrupting the primary analog control output loop.

Logic power is supplied directly from the carrier backplane’s 12V DC LocalBus, while field output loops draw current from a 24V DC bulk field power supply landed at the terminal base. Integrated mechanical polarization keying prevents misinsertion into non-matching carrier slots, protecting central processing hardware and field wiring connections.

 

Engineering Selection Highlights

  • 8-Channel HART Signal Driving: Combines high-precision 4-20 mA current output generation with integrated HART digital communication on 8 independent channels.
  • 16-Bit Resolution: Employs 16-bit digital-to-analog conversion for accurate, fine-step valve positioning and smooth process control loops.
  • HART Device Pass-Through: Enables remote calibration, status monitoring, and asset management of connected smart field positioners from DeltaV Workstations.
  • Dual Power Architecture: Logic circuits utilize internal 12V DC LocalBus backplane power, separating system processing from external 24V DC field loop power.
  • Carrier Polarization Keying: Mechanical key slots restrict card insertion exclusively to designated, correctly configured terminal bases.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Automation System Emerson DeltaV DCS Integrated within DeltaV controller hardware trees
Subsystem Series Traditional I/O (M-Series) Plugs into M-Series Traditional I/O interface carriers
Carrier Mounting DeltaV 2-wide / 8-wide I/O Interface Carriers Snaps onto DIN-rail mounted interface carriers
Terminal Block 8-Channel Analog Output Terminal Block Requires a matching 8-channel terminal block for field cable landing
Backplane Power DeltaV LocalBus (12V DC) Draws up to 150 mA maximum from carrier bus
Field Power 24V DC Auxiliary Field Power Supply Auxiliary 24V DC landed at terminal block for output loop driving
Engineering Software DeltaV Explorer / Control Studio Configured via standard DeltaV hardware management software
 VE4005S2B1

VE4005S2B1

 VE4005S2B1

VE4005S2B1

Dimensions, Mounting & Connection Notes

  • Height: 10.7 cm (4.2 in.)
  • Width: 4.1 cm (1.6 in.)
  • Depth: 10.5 cm (4.1 in.)
  • Mounting Method: Direct snap-in mounting onto a DeltaV I/O interface carrier fixed to standard T-section DIN rail (EN 50022).
  • Clearance Requirements: Provide standard vertical ventilation spacing above and below the carrier assembly to maintain natural thermal convection inside enclosures.
  • Terminal Wiring: Output conductors connect to the associated 8-channel terminal block using screw or spring-clamp connections.
  • Shield Grounding: Cable shields should land on the carrier’s dedicated grounding bar to prevent high-frequency noise from affecting loop output accuracy.

 

FAQ

What is the primary function of the Emerson VE4005S2B1?

The Emerson VE4005S2B1 is an 8-channel 4-20 mA analog output card used in the DeltaV DCS to drive field actuators, valves, and positioners.

Does the VE4005S2B1 support HART communication?

Yes, all 8 output channels support HART pass-through communication for smart device diagnostics and remote asset management.

How many channels are available on this module?

The card provides 8 independent 4-20 mA analog output channels.

What power sources are required for operation?

The card uses 12V DC power from the LocalBus backplane for internal processing, plus external 24V DC field circuit power landed at the terminal block to drive output loops.

What terminal block is required for installation?

The module requires a matching DeltaV 8-channel analog output terminal block mounted on an I/O interface carrier.

 

Verification & Troubleshooting Notes

  • Status LED Inspection: Check the faceplate status LEDs. A steady green light confirms active LocalBus communication and health. Solid or flashing red states indicate communication loss, improper carrier seating, or internal module faults.
  • Output Loop Current Measurement: If a valve fails to respond, place a digital multimeter in series with the output loop terminal to verify if 4-20 mA current is flowing according to the control command.
  • External 24V DC Supply Check: Absence of output current across all channels often indicates a missing or disconnected bulk 24V DC field power supply at the terminal block.
  • Carrier Alignment Verification: If the card resists insertion, inspect the physical polarization keys on the carrier base to ensure they align with the slot keying of the VE4005S2B1. Do not force insertion.