Description
Core Product Summary
The Emerson VE4012S2B1 is a DeltaV M-series intrinsically safe analog input interface with eight 4–20 mA HART channels and an included I/O termination block. It connects intrinsically safe field circuits and transmitters to a DeltaV controller without requiring separate third-party barriers or interface mapping.
The interface accepts a nominal 4–20 mA signal with a full 2–22 mA range and supports HART communication. It provides 16-bit resolution, requires no calibration, and includes line-fault detection for short-circuit and open-circuit conditions. The VE4012S2B1 mounts in a DeltaV 8-wide intrinsically safe I/O carrier and is intended for I/O interfaces installed in Zone 2 / Class I, Division 2 locations, with intrinsically safe field circuits permitted in Zone 0, Zone 1, and Division 1 hazardous areas.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Emerson |
| Model / order number | VE4012S2B1 |
| Product type | 8-channel intrinsically safe analog input I/O interface |
| Control system family | Emerson DeltaV M-series Intrinsically Safe I/O |
| Number of input channels | 8 |
| Input signal | 4–20 mA with HART |
| Nominal signal range | 4 to 20 mA |
| Full signal range | 2 to 22 mA |
| Resolution | 16 bits |
| Calibration | None required |
| Voltage to transmitter at 20 mA | 15 V minimum |
| Temperature stability | ±0.006% of span per °C |
| Line-fault detection, short circuit | Greater than 21.5 mA |
| Line-fault detection, open circuit | Less than 0.5 mA |
| LocalBus current | 600 mA per card at 12 V DC nominal |
| Isolation, LocalBus to any channel | 60 V AC |
| Isolation, I.S. channel to non-I.S. rail | 250 V AC |
| Isolation between channels | None |
| Optional loop disconnect | Yes |
| Terminal block | I/O termination block included |
| Carrier | DeltaV 8-wide intrinsically safe I/O carrier |
| Operating temperature | -40 to 60°C (-40 to 140°F) |
| Storage temperature | -40 to 85°C (-40 to 185°F) |
| Relative humidity | 5 to 95%, non-condensing |
| Protection rating | IP20 |
| I/O interface hazardous-area rating | Zone 2, IIC T4; Class I, Division 2, Groups A–D, T4 |
| Field-circuit hazardous-area rating | Zone 0, IIC; Class I, Division 1, Groups A–D |
| Card dimensions | 10.7 cm H × 4.1 cm W × 10.5 cm D |
| Conformal coating | ISA-S71.04-1985 Class G3 |
Detailed Product Overview
The VE4012S2B1 is an Emerson DeltaV M-series intrinsically safe analog input interface for 4–20 mA HART transmitters. It combines the eight-channel I.S. AI card with its matching I/O termination block, providing a complete field-termination and signal-acquisition interface for hazardous-area measurement loops.
The interface accepts a nominal 4–20 mA input and recognizes a 2–22 mA full signal range. Its 16-bit converter digitizes each channel, while the card provides a temperature stability of ±0.006% of span per °C. No field calibration is required. For two-wire transmitters, the interface supplies at least 15 V to the transmitter at 20 mA.
The I.S. AI card includes line-fault detection. A short-circuit condition is indicated when loop current exceeds 21.5 mA, while an open-circuit condition is indicated when current falls below 0.5 mA. These diagnostics help identify wiring or transmitter-loop faults at the I/O interface.
The VE4012S2B1 is part of DeltaV’s native intrinsically safe I/O subsystem. It connects field circuits directly to the DeltaV controller I/O subsystem, eliminating the need for separate third-party barriers or interface mapping. The I.S. I/O subsystem is designed for I/O interfaces located in Zone 2 / Class I, Division 2 areas, while its intrinsically safe field circuits and connected devices may extend into Zone 0, Zone 1, and Class I, Division 1 areas.
The card plugs into a DeltaV 8-wide I.S. I/O carrier. Its I/O function keying ensures that the AI card is installed only in the matching terminal block. The terminal block can be mounted and pre-wired before the I/O card is installed, and I/O interfaces can be added online as the installation expands.
The LocalBus current requirement is 600 mA per card at 12 V DC nominal. An Emerson I.S. I/O power supply converts 24 V DC input power to 12 V DC for the I.S. I/O cards. When connecting intrinsically safe I/O to non-intrinsically safe I/O, a DeltaV LocalBus isolator is required.

VE4012S2B1

VE4012S2B1
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Control system | Emerson DeltaV distributed control system | The interface is a native DeltaV I/O card. |
| I/O architecture | DeltaV M-series Intrinsically Safe I/O | Designed for hazardous-area I/O installations. |
| Controllers | DeltaV M-series controllers | M-series I/O cards are not compatible with S-series controllers and carriers. |
| Carrier | DeltaV 8-wide intrinsically safe I/O carrier | Holds up to eight I/O cards and eight terminal blocks. |
| Terminal block | Included I/O termination block | The VE4012S2B1 is the standard I/O terminal-block configuration. |
| Loop disconnect | Optional; use VE4012S2B2 for loop-disconnect termination | The VE4012S2B1 includes the standard I/O termination block. |
| Field signal | 4–20 mA HART transmitters | Nominal range is 4–20 mA; full range is 2–22 mA. |
| Field circuits | Intrinsically safe circuits | Permitted in Zone 0, IIC; Class I, Division 1, Groups A–D. |
| I/O location | Zone 2, IIC T4; Class I, Division 2, Groups A–D, T4 | Applies to the I/O interface installation location. |
| Power | DeltaV I.S. I/O power supply | Converts 24 V DC input to 12 V DC for I.S. I/O cards. |
| Mixed I/O | DeltaV LocalBus isolator required | Needed to connect I.S. I/O with non-I.S. field wiring. |
| Installation sequence | I.S. carriers must be mounted last in line | Applies when standard I/O carriers and I.S. I/O carriers are connected. |
Dimensions, Mounting & Connection Notes
- Card size: 10.7 cm high × 4.1 cm wide × 10.5 cm deep.
- Mounting method: Plugs into a DeltaV 8-wide intrinsically safe I/O carrier.
- Carrier capacity: Eight I/O cards and eight terminal blocks.
- Field connection: Uses the included I/O termination block.
- Keying: I.S. I/O interfaces and terminal blocks use I/O function keys to ensure matching card and terminal-block installation.
- Pre-wiring: The I/O terminal block plugs directly onto the carrier and can be installed before the I/O card.
- Status indication: LEDs on the top of the card indicate power, error, and channel status.
- Environmental installation limits: -40 to 60°C operating temperature, 5 to 95% non-condensing relative humidity, and IP20 protection.
- Environmental protection: Conformal coating meeting ISA-S71.04-1985 Class G3 airborne-contaminant requirements.
- Mechanical environment: 10 g half-sine shock for 11 ms; 1 mm peak-to-peak vibration from 5 to 16 Hz and 0.5 g from 16 to 150 Hz.
- Hazardous-area installation: Refer to Emerson Zone 0 installation instructions, document 12P1990, for installations in hazardous areas.
FAQ
What is the Emerson VE4012S2B1?
It is an Emerson DeltaV M-series intrinsically safe analog input interface with eight 4–20 mA HART channels and an included I/O termination block.
How many analog inputs does the VE4012S2B1 provide?
It provides eight analog input channels.
What field signals does it accept?
It accepts 4–20 mA HART transmitter signals, with a nominal 4–20 mA span and a full signal range of 2–22 mA.
Does it support HART communication?
Yes. The interface supports 4–20 mA signals with HART communication.
Does it require external intrinsic-safety barriers?
No. It is part of DeltaV’s native intrinsically safe I/O subsystem and connects field circuits directly to the DeltaV controller I/O subsystem without third-party barriers or interface mapping.
What terminal block is included?
The VE4012S2B1 includes the standard I/O termination block. The VE4012S2B2 is the corresponding configuration with a loop-disconnect termination block.
Which carrier does it require?
It requires a DeltaV 8-wide intrinsically safe I/O carrier.
Can it be used with S-series controllers?
No. DeltaV M-series I/O cards are not compatible with S-series controllers and carriers.
What hazardous-area ratings apply?
The I/O interface is rated for Zone 2, IIC T4 and Class I, Division 2, Groups A–D, T4 locations. Its intrinsically safe field circuits may enter Zone 0, IIC and Class I, Division 1, Groups A–D locations.
Documented Performance Data
| Metric | Value / Range | Test / operating condition |
|---|---|---|
| Input channels | 8 | I.S. AI, 4–20 mA with HART |
| Nominal input span | 4 to 20 mA | Analog input channel |
| Full signal range | 2 to 22 mA | Analog input channel |
| Resolution | 16 bits | Analog-to-digital conversion |
| Calibration | None required | Factory-configured interface |
| Voltage to transmitter | 15 V minimum at 20 mA | Two-wire transmitter loop |
| Temperature stability | ±0.006% of span per °C | Analog input measurement |
| Short-circuit detection | Greater than 21.5 mA | Line-fault detection |
| Open-circuit detection | Less than 0.5 mA | Line-fault detection |
| LocalBus current | 600 mA per card | 12 V DC nominal LocalBus supply |
| Isolation | 60 V AC LocalBus to any channel; 250 V AC I.S. channel to non-I.S. rail | Intrinsically safe analog input interface |