Emerson VE4012S2B1 | DeltaV 8-Channel Intrinsically Safe 4–20 mA HART AI Interface

Parameter Specification
Manufacturer Emerson
Model / order number VE4012S2B1
Product type 8-channel intrinsically safe analog input I/O interface
Control system family Emerson DeltaV M-series Intrinsically Safe I/O
Number of input channels 8
Input signal 4–20 mA with HART
Nominal signal range 4 to 20 mA
Full signal range 2 to 22 mA
Resolution 16 bits
Calibration None required
Categories: , , , , SKU: VE4012S2B1 Brand:

Description

Core Product Summary

The Emerson VE4012S2B1 is a DeltaV M-series intrinsically safe analog input interface with eight 4–20 mA HART channels and an included I/O termination block. It connects intrinsically safe field circuits and transmitters to a DeltaV controller without requiring separate third-party barriers or interface mapping.

The interface accepts a nominal 4–20 mA signal with a full 2–22 mA range and supports HART communication. It provides 16-bit resolution, requires no calibration, and includes line-fault detection for short-circuit and open-circuit conditions. The VE4012S2B1 mounts in a DeltaV 8-wide intrinsically safe I/O carrier and is intended for I/O interfaces installed in Zone 2 / Class I, Division 2 locations, with intrinsically safe field circuits permitted in Zone 0, Zone 1, and Division 1 hazardous areas.

 

Key Technical Specifications

Parameter Specification
Manufacturer Emerson
Model / order number VE4012S2B1
Product type 8-channel intrinsically safe analog input I/O interface
Control system family Emerson DeltaV M-series Intrinsically Safe I/O
Number of input channels 8
Input signal 4–20 mA with HART
Nominal signal range 4 to 20 mA
Full signal range 2 to 22 mA
Resolution 16 bits
Calibration None required
Voltage to transmitter at 20 mA 15 V minimum
Temperature stability ±0.006% of span per °C
Line-fault detection, short circuit Greater than 21.5 mA
Line-fault detection, open circuit Less than 0.5 mA
LocalBus current 600 mA per card at 12 V DC nominal
Isolation, LocalBus to any channel 60 V AC
Isolation, I.S. channel to non-I.S. rail 250 V AC
Isolation between channels None
Optional loop disconnect Yes
Terminal block I/O termination block included
Carrier DeltaV 8-wide intrinsically safe I/O carrier
Operating temperature -40 to 60°C (-40 to 140°F)
Storage temperature -40 to 85°C (-40 to 185°F)
Relative humidity 5 to 95%, non-condensing
Protection rating IP20
I/O interface hazardous-area rating Zone 2, IIC T4; Class I, Division 2, Groups A–D, T4
Field-circuit hazardous-area rating Zone 0, IIC; Class I, Division 1, Groups A–D
Card dimensions 10.7 cm H × 4.1 cm W × 10.5 cm D
Conformal coating ISA-S71.04-1985 Class G3

 

Detailed Product Overview

The VE4012S2B1 is an Emerson DeltaV M-series intrinsically safe analog input interface for 4–20 mA HART transmitters. It combines the eight-channel I.S. AI card with its matching I/O termination block, providing a complete field-termination and signal-acquisition interface for hazardous-area measurement loops.

The interface accepts a nominal 4–20 mA input and recognizes a 2–22 mA full signal range. Its 16-bit converter digitizes each channel, while the card provides a temperature stability of ±0.006% of span per °C. No field calibration is required. For two-wire transmitters, the interface supplies at least 15 V to the transmitter at 20 mA.

The I.S. AI card includes line-fault detection. A short-circuit condition is indicated when loop current exceeds 21.5 mA, while an open-circuit condition is indicated when current falls below 0.5 mA. These diagnostics help identify wiring or transmitter-loop faults at the I/O interface.

The VE4012S2B1 is part of DeltaV’s native intrinsically safe I/O subsystem. It connects field circuits directly to the DeltaV controller I/O subsystem, eliminating the need for separate third-party barriers or interface mapping. The I.S. I/O subsystem is designed for I/O interfaces located in Zone 2 / Class I, Division 2 areas, while its intrinsically safe field circuits and connected devices may extend into Zone 0, Zone 1, and Class I, Division 1 areas.

The card plugs into a DeltaV 8-wide I.S. I/O carrier. Its I/O function keying ensures that the AI card is installed only in the matching terminal block. The terminal block can be mounted and pre-wired before the I/O card is installed, and I/O interfaces can be added online as the installation expands.

The LocalBus current requirement is 600 mA per card at 12 V DC nominal. An Emerson I.S. I/O power supply converts 24 V DC input power to 12 V DC for the I.S. I/O cards. When connecting intrinsically safe I/O to non-intrinsically safe I/O, a DeltaV LocalBus isolator is required.

VE4012S2B1

VE4012S2B1

VE4012S2B1

VE4012S2B1

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Control system Emerson DeltaV distributed control system The interface is a native DeltaV I/O card.
I/O architecture DeltaV M-series Intrinsically Safe I/O Designed for hazardous-area I/O installations.
Controllers DeltaV M-series controllers M-series I/O cards are not compatible with S-series controllers and carriers.
Carrier DeltaV 8-wide intrinsically safe I/O carrier Holds up to eight I/O cards and eight terminal blocks.
Terminal block Included I/O termination block The VE4012S2B1 is the standard I/O terminal-block configuration.
Loop disconnect Optional; use VE4012S2B2 for loop-disconnect termination The VE4012S2B1 includes the standard I/O termination block.
Field signal 4–20 mA HART transmitters Nominal range is 4–20 mA; full range is 2–22 mA.
Field circuits Intrinsically safe circuits Permitted in Zone 0, IIC; Class I, Division 1, Groups A–D.
I/O location Zone 2, IIC T4; Class I, Division 2, Groups A–D, T4 Applies to the I/O interface installation location.
Power DeltaV I.S. I/O power supply Converts 24 V DC input to 12 V DC for I.S. I/O cards.
Mixed I/O DeltaV LocalBus isolator required Needed to connect I.S. I/O with non-I.S. field wiring.
Installation sequence I.S. carriers must be mounted last in line Applies when standard I/O carriers and I.S. I/O carriers are connected.

 

Dimensions, Mounting & Connection Notes

  • Card size: 10.7 cm high × 4.1 cm wide × 10.5 cm deep.
  • Mounting method: Plugs into a DeltaV 8-wide intrinsically safe I/O carrier.
  • Carrier capacity: Eight I/O cards and eight terminal blocks.
  • Field connection: Uses the included I/O termination block.
  • Keying: I.S. I/O interfaces and terminal blocks use I/O function keys to ensure matching card and terminal-block installation.
  • Pre-wiring: The I/O terminal block plugs directly onto the carrier and can be installed before the I/O card.
  • Status indication: LEDs on the top of the card indicate power, error, and channel status.
  • Environmental installation limits: -40 to 60°C operating temperature, 5 to 95% non-condensing relative humidity, and IP20 protection.
  • Environmental protection: Conformal coating meeting ISA-S71.04-1985 Class G3 airborne-contaminant requirements.
  • Mechanical environment: 10 g half-sine shock for 11 ms; 1 mm peak-to-peak vibration from 5 to 16 Hz and 0.5 g from 16 to 150 Hz.
  • Hazardous-area installation: Refer to Emerson Zone 0 installation instructions, document 12P1990, for installations in hazardous areas.

 

FAQ

What is the Emerson VE4012S2B1?
It is an Emerson DeltaV M-series intrinsically safe analog input interface with eight 4–20 mA HART channels and an included I/O termination block.

How many analog inputs does the VE4012S2B1 provide?
It provides eight analog input channels.

What field signals does it accept?
It accepts 4–20 mA HART transmitter signals, with a nominal 4–20 mA span and a full signal range of 2–22 mA.

Does it support HART communication?
Yes. The interface supports 4–20 mA signals with HART communication.

Does it require external intrinsic-safety barriers?
No. It is part of DeltaV’s native intrinsically safe I/O subsystem and connects field circuits directly to the DeltaV controller I/O subsystem without third-party barriers or interface mapping.

What terminal block is included?
The VE4012S2B1 includes the standard I/O termination block. The VE4012S2B2 is the corresponding configuration with a loop-disconnect termination block.

Which carrier does it require?
It requires a DeltaV 8-wide intrinsically safe I/O carrier.

Can it be used with S-series controllers?
No. DeltaV M-series I/O cards are not compatible with S-series controllers and carriers.

What hazardous-area ratings apply?
The I/O interface is rated for Zone 2, IIC T4 and Class I, Division 2, Groups A–D, T4 locations. Its intrinsically safe field circuits may enter Zone 0, IIC and Class I, Division 1, Groups A–D locations.

 

Documented Performance Data

Metric Value / Range Test / operating condition
Input channels 8 I.S. AI, 4–20 mA with HART
Nominal input span 4 to 20 mA Analog input channel
Full signal range 2 to 22 mA Analog input channel
Resolution 16 bits Analog-to-digital conversion
Calibration None required Factory-configured interface
Voltage to transmitter 15 V minimum at 20 mA Two-wire transmitter loop
Temperature stability ±0.006% of span per °C Analog input measurement
Short-circuit detection Greater than 21.5 mA Line-fault detection
Open-circuit detection Less than 0.5 mA Line-fault detection
LocalBus current 600 mA per card 12 V DC nominal LocalBus supply
Isolation 60 V AC LocalBus to any channel; 250 V AC I.S. channel to non-I.S. rail Intrinsically safe analog input interface