Description
Core Product Summary
The Emerson VS3202 is a DeltaV SLS 1508 Redundant Logic Solver supplied with a terminal block for use in the DeltaV Safety Instrumented System (SIS). It contains dual CPUs and provides 16 channels of flexible I/O, allowing each channel to be configured as an analog input with HART, HART two-state output, discrete input, or discrete output.
The module operates from 24 VDC ±20% and requires 1.0 A plus field power, with a total input-power limit of 5.0 A. It mounts in odd-numbered slots—1, 3, 5, or 7—on an 8-wide SIS carrier, and a redundant logic-solver configuration occupies four slots.
Key Technical Specifications
| Parameter | Emerson VS3202 |
|---|---|
| Manufacturer | Emerson |
| Product family | DeltaV SIS / SLS 1508 |
| Product type | Redundant Logic Solver with terminal block |
| Model number | VS3202 |
| Processor architecture | Dual CPUs |
| I/O channels | 16 flexible I/O channels |
| Configurable channel types | Analog input (HART), HART two-state output, discrete input, discrete output |
| Input power | 24 VDC ±20%, 1.0 A plus field power |
| Total input power | 5.0 A maximum |
| Field power | 4.0 A maximum |
| Isolation | Each channel optically isolated from the system; 1,500 VDC factory-tested |
| Channel-to-channel isolation | Not provided |
| Mounting | Odd-numbered slots (1, 3, 5, 7) on an 8-wide SIS carrier |
| Redundant configuration | Uses four slots |
| Weight, redundant logic solver | 1.20 kg |
| Heat dissipation, redundant logic solver | 24 W |
| Power consumption, redundant logic solver | 2 A at 24 VDC plus digital-output field loads |
| Operating temperature | -40 to 70°C |
| Storage temperature | -40 to 85°C |
| Relative humidity | 5% to 95%, noncondensing |
| Airborne contaminants | ISA-S71.04-1985 Class G3 |
| Conformal coating | Provided |
| Protection rating | IP 20 |
| Hazardous-location rating | FM Non-Arcing, Class I, Division 2, Groups A, B, C, D, T4 |
| EMC compliance | European EMC Directive per EN 61326-1, Criterion A; NAMUR NE 21 |
| Low-voltage compliance | IEC 61010-1 |
| Software prerequisite | DeltaV v8.3 software or later |
Engineering Selection Highlights
- The VS3202 is the DeltaV SLS 1508 Redundant Logic Solver, so it is intended for DeltaV SIS architectures rather than as a general-purpose PLC or standalone safety controller.
- Its dual-CPU architecture and 16 flexible I/O channels allow safety logic execution and configurable analog, HART, discrete-input, and discrete-output functions within one logic solver.
- The module mounts only in odd-numbered slots on an 8-wide SIS carrier; a redundant configuration requires four slots, which affects carrier and cabinet space planning.
- The 24 VDC input requirement includes both module power and field power, with a total limit of 5.0 A; field-power allocation must account for channel type and connected field devices.
- Each channel is optically isolated from the system and factory-tested at 1,500 VDC, but the module does not provide channel-to-channel isolation.
- The IP 20 enclosure rating means the module must be installed in an appropriate DeltaV SIS carrier and cabinet environment rather than exposed to dust, moisture, or mechanical contact.
- DeltaV v8.3 software or later is required, so the control-system software version should be confirmed before installation or upgrade planning.

VS3202

VS3202
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Safety system | Emerson DeltaV Safety Instrumented System (SIS) | The VS3202 is an SLS 1508 Logic Solver for DeltaV SIS. |
| Logic-solver family | DeltaV SLS 1508 | The module is a redundant SLS 1508 Logic Solver with terminal block. |
| Carrier | 8-wide SIS carrier | Mounts in odd-numbered slots 1, 3, 5, or 7. |
| Redundant configuration | Four slots per redundant logic solver | Reserve carrier capacity accordingly. |
| Software | DeltaV v8.3 or later | Earlier DeltaV software versions do not meet the stated prerequisite. |
| I/O configuration | Analog input with HART, HART two-state output, discrete input, or discrete output | Channel function is configurable; it is not a fixed 16-input or 16-output card. |
| Power supply | 24 VDC ±20% | Emerson recommends separate power supplies for the SLS and the DeltaV controller/I/O. |
| Field power | Up to 4 A maximum | Actual allocation depends on channel type and field-device type. |
| Hazardous-area installation | FM Non-Arcing, Class I, Division 2, Groups A, B, C, D, T4 | The applicable hazardous-area approval must be observed during cabinet and installation design. |
Dimensions, Mounting & Connection Notes
- The VS3202 is supplied as a DeltaV SLS 1508 Redundant Logic Solver with terminal block.
- It mounts in odd-numbered slots—1, 3, 5, or 7—on an 8-wide SIS carrier.
- A redundant logic-solver configuration occupies four slots on the carrier.
- The module weighs 1.20 kg in the redundant logic-solver configuration.
- It dissipates 24 W in the redundant configuration.
- Each I/O channel is optically isolated from the system and factory-tested to 1,500 VDC.
- The module provides no channel-to-channel isolation.
- The module has a conformal coating and an IP 20 protection rating.
Detailed Product Overview
The Emerson VS3202 is the DeltaV SLS 1508 Redundant Logic Solver with terminal block. It is a core module in the DeltaV Safety Instrumented System, where it executes configured safety logic and provides the interface between the SIS and field instrumentation and final elements.
The module contains dual CPUs and provides 16 channels of flexible I/O. Each channel can be configured as an analog input with HART, a HART two-state output, a discrete input, or a discrete output. This flexible channel architecture allows one logic solver to support a combination of safety-related measurement and output functions, subject to the configured system design.
The VS3202 operates from 24 VDC ±20%. Its input-power requirement is 1.0 A plus field power, with a total limit of 5.0 A. Field power is limited to 4.0 A, with the actual requirement depending on channel type and connected field-device type. Emerson recommends that the SLS and the DeltaV controller and I/O use separate power supplies.
Each channel is optically isolated from the system and factory-tested to 1,500 VDC. The module does not provide channel-to-channel isolation, so field wiring design must account for this boundary. The module includes conformal coating and has an IP 20 protection rating, meaning it is intended for installation inside an appropriate DeltaV SIS carrier and control-cabinet environment.
The VS3202 mounts in odd-numbered slots—1, 3, 5, or 7—on an 8-wide SIS carrier. A redundant logic-solver configuration occupies four slots. This mounting arrangement affects carrier selection, spare-slot planning, and cabinet layout.
The module is specified for operation from -40 to 70°C, storage from -40 to 85°C, and 5% to 95% relative humidity, noncondensing. It is rated for ISA-S71.04-1985 Class G3 airborne contaminants. Its hazardous-location scope includes Factory Mutual Non-Arcing approval for Class I, Division 2, Groups A, B, C, D, T4 locations. It also complies with the European EMC Directive per EN 61326-1, Criterion A; NAMUR NE 21; and the Low Voltage Directive per IEC 61010-1.
The VS3202 requires DeltaV v8.3 software or later. System configuration, logic development, diagnostics, and commissioning should therefore be performed using a compatible DeltaV software version and the applicable Emerson DeltaV SIS documentation.
Applications & System Role
The Emerson VS3202 functions as the logic-solving element in a DeltaV Safety Instrumented System. It executes the configured safety logic, interfaces with field devices through its 16 flexible I/O channels, and communicates within the DeltaV SIS architecture.
Because each channel can be configured as an analog input with HART, HART two-state output, discrete input, or discrete output, the module can support a mix of safety-related measurement, final-element control, and discrete interlock functions. Its dual-CPU design supports the redundant SLS 1508 architecture.
The module is intended for installation in an Emerson DeltaV SIS carrier within a suitably rated control cabinet. Its IP 20 rating, hazardous-location approval scope, EMC requirements, and separate-power-supply recommendation define the installation boundary for plant applications.
FAQ
What is the Emerson VS3202?
It is a DeltaV SLS 1508 Redundant Logic Solver with terminal block for the Emerson DeltaV Safety Instrumented System.
How many I/O channels does it provide?
It provides 16 channels of flexible I/O.
Which channel types can be configured?
Each channel can be configured as an analog input with HART, HART two-state output, discrete input, or discrete output.
What power does the VS3202 require?
It requires 24 VDC ±20%, 1.0 A plus field power, with a total input-power limit of 5.0 A.
How much field power does it support?
It supports up to 4.0 A of field power, depending on channel type and field-device type.
Where does it mount?
It mounts in odd-numbered slots—1, 3, 5, or 7—on an 8-wide SIS carrier.
How many slots does a redundant configuration use?
A redundant logic-solver configuration uses four slots.
What software version is required?
DeltaV v8.3 software or later is required.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626