GE 8502-BI-DP PROFIBUS-DP Bus Interface Module

Parameter Specification
Manufacturer General Electric / GE Intelligent Platforms
Exact model 8502-BI-DP
Product type PROFIBUS-DP bus interface module (BIM)
I/O platform 8000 Series / PAC8000 I/O
PROFIBUS protocol PROFIBUS-DP V1, EN 50170
Physical interface RS-485
Transmission rates 9.6, 19.2, 93.75, 187.5, 500 kbaud, 1.5 Mbaud, and 6 Mbaud
Connected I/O modules Up to 24
Maximum input data 244 bytes
Maximum output data 244 bytes
Categories: , , , , Brand:

Description

Core Product Summary

The GE 8502-BI-DP is a PROFIBUS-DP bus interface module (BIM) that links a node of 8000 Series I/O modules to a PROFIBUS-DP host controller. It provides cyclic data exchange between the host and the connected I/O modules and supports process-variable and status transfer for HART devices.

The module supports up to 24 I/O modules, PROFIBUS-DP V1 communication to EN 50170, and transmission rates from 9.6 kbaud to 6 Mbaud. It is configured with a GSD file through PROFIBUS parameterization or with the 8455-SW-CF configuration software; its non-volatile memory retains configuration. The BIM mounts on an 8715-CA-BI carrier and requires 12 V DC system power.

 

Key Technical Specifications

Parameter Specification
Manufacturer General Electric / GE Intelligent Platforms
Exact model 8502-BI-DP
Product type PROFIBUS-DP bus interface module (BIM)
I/O platform 8000 Series / PAC8000 I/O
PROFIBUS protocol PROFIBUS-DP V1, EN 50170
Physical interface RS-485
Transmission rates 9.6, 19.2, 93.75, 187.5, 500 kbaud, 1.5 Mbaud, and 6 Mbaud
Connected I/O modules Up to 24
Maximum input data 244 bytes
Maximum output data 244 bytes
Message response time Less than 4 ms
HART support HART process variables and status
Bus isolation 500 V
System power 12 V DC; 420 mA typical, 520 mA maximum
Module width 63 mm
Module weight 350 g
Configuration GSD file / PROFIBUS configurator, or 8455-SW-CF software
Configuration storage Non-volatile memory
Carrier 8715-CA-BI BIM carrier
Manual INM8502, 8000 I/O PROFIBUS-DP BIM
Hazardous-area scope Group II Category 3 G equipment; ATEX assessment references EN 60079-11 and EN 60079-15
Ambient temperature range −40 to +70 °C

The 8502-BI-DP is listed in the PAC8000 traditional BIM range with a 24-module capacity, 244-byte input and output frames, and a message response time below 4 ms. The ATEX declaration identifies the exact model as a PROFIBUS-DP bus interface module and gives the −40 to +70 °C ambient range.

 

Engineering Selection Highlights

  • The 8502-BI-DP connects up to 24 I/O modules → it defines the maximum size of one PROFIBUS-DP I/O node.
  • It supports 9.6 kbaud through 6 Mbaud → the selected PROFIBUS baud rate determines the usable bus-length range, which is documented as 100 m to 1.2 km depending on baud rate.
  • Its input and output data frames are each limited to 244 bytes → cyclic data mapping must be planned within this boundary.
  • HART process variables and status are supported → HART-capable field devices can expose selected variables and diagnostic status through the BIM.
  • The module requires an 8715-CA-BI carrier → the BIM cannot be treated as a standalone DIN-rail device without the appropriate carrier and system-power arrangement.
  • PROFIBUS-based configuration provides a reduced parameter set, while 8455-SW-CF provides the fuller configuration range → the intended configuration method affects available module and channel options.
  • The BIM has 500 V bus isolation → it separates the PROFIBUS LAN, Railbus, and internal power-supply domains.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
I/O platform 8000 Series / PAC8000 I/O modules The BIM is the communications interface for a local node of these modules.
PROFIBUS host PROFIBUS-DP V1 master, EN 50170 The BIM operates as a PROFIBUS-DP interface to the host LAN.
Physical network RS-485 PROFIBUS-DP communication uses an RS-485 connection.
Carrier 8715-CA-BI BIM carrier The BIM must be mounted on the appropriate carrier.
System power 12 V DC, 420 mA typical / 520 mA maximum Power is supplied through the carrier/Railbus arrangement.
Configuration tool GSD file / PROFIBUS configurator, or 8455-SW-CF GSD-based PROFIBUS configuration offers a reduced parameter set; 8455-SW-CF provides more detailed configuration.
Configuration storage Non-volatile memory in the BIM Configuration can also be saved to an 8510-MO-NS Node Services Module for recovery.
HART maintenance 8512 HART Comms interface HART pass-through messaging is available through the local configuration port and 8512 interface.
IONet / SafetyNet Not supported on serial BIMs including 8502-BI-DP SafetyNet SOE functions are not supported on this serial BIM.

The carrier, power, configuration, and HART-maintenance dependencies are documented in the manufacturer BIM material and PAC8000 system documentation.

8502-BI-DP

8502-BI-DP

Dimensions, Mounting & Connection Notes

Item Verified information
Module width 63 mm
Module weight 350 g
Mounting requirement Must be installed on an appropriate BIM carrier
Required carrier 8715-CA-BI BIM carrier
Carrier mounting DIN rail
Carrier dimensions 93 × 170 × 35 mm
Carrier weight 420 g
Carrier connectors Two 9-pin D-sub female RS-485/422 connectors
Carrier system power 12.0 V DC ±5%
PROFIBUS connection RS-485
Configuration connection Local configuration port
Diagnostics Power, Fault, Comm, LAN A, Config, and Railbus indicators
Address setting Software address setting through the I/O Configurator

The 8502-BI-DP is mounted on the 8715-CA-BI carrier; the carrier supplies the physical mounting, RS-485/422 connectors, and 12 V DC system-power connection. The ATEX declaration identifies the module’s energy-limited PROFIBUS LAN, Railbus, and power-supply connections and specifies installation in accordance with EN 60079-14 and EN 60079-25.

 

Detailed Product Overview

The GE 8502-BI-DP is a PROFIBUS-DP bus interface module for the 8000 Series / PAC8000 distributed I/O platform. It provides the communications bridge between a PROFIBUS-DP host and a local node containing up to 24 I/O modules. In this role, it handles the cyclic exchange of input and output data between the host controller and the I/O modules, while also exposing module and channel diagnostic information.

The BIM uses an RS-485 PROFIBUS-DP interface and supports EN 50170-compliant PROFIBUS-DP V1 communication. Supported transmission rates span 9.6 kbaud to 6 Mbaud. The documented bus-length range is 100 m to 1.2 km, depending on the selected baud rate; therefore, the intended cable topology and baud rate must be evaluated together rather than treated as independent settings.

Data capacity is bounded by the 244-byte input and 244-byte output data frames. The mapping method differs by data type: analog channels use one word per channel, digital channels use one word per module, and HART variables use two words per variable. These distinctions matter when allocating cyclic PROFIBUS-DP data to a large mixed analog, digital, and HART-enabled I/O node.

Configuration can be performed through a PROFIBUS configurator using a GSD file, or through the 8455-SW-CF configuration software. The GSD-file approach configures modules on a per-module basis, meaning all channels of one module receive the same configuration. The 8455-SW-CF method instead supports individual channel and alarm configuration and stores the configuration in the BIM. A configuration can also be saved to an 8510-MO-NS Node Services Module for recovery if a BIM must be replaced.

HART integration is available through pass-through messaging. The local configuration port and an 8512 HART Comms interface allow multiple BIMs to be multi-dropped on an RS-485 link to a PC running instrument-management software. This makes the 8502-BI-DP relevant where HART device maintenance access is required in addition to routine PROFIBUS-DP process-data exchange.

The module requires an 8715-CA-BI BIM carrier and 12 V DC system power. Its 420 mA typical and 520 mA maximum system-power requirement must be considered alongside the power demand of the connected I/O modules. The module is 63 mm wide and weighs 350 g; its carrier is 93 × 170 × 35 mm and weighs 420 g.

 

Applications & System Role

The 8502-BI-DP sits between a PROFIBUS-DP host and a local node of 8000 Series I/O modules. It acquires input data from the I/O modules, transfers output data to them, and makes module and channel diagnostic status available to the host.

Its role is therefore that of a fieldbus interface rather than an I/O module itself. Analog channels are represented by one input word per input channel and one output word per output channel, while digital data uses one word per input module and one word per output module. HART variables use two words per variable.

The module is appropriate where a PAC8000/8000 Series I/O node must exchange cyclic process data with a PROFIBUS-DP master. It is also relevant where HART device variables and status need to be made available over the PROFIBUS-DP interface.

 

FAQ

 

What is the GE 8502-BI-DP?

It is a PROFIBUS-DP bus interface module that connects a node of 8000 Series / PAC8000 I/O modules to a PROFIBUS-DP host controller.

 

How many I/O modules can it support?

The 8502-BI-DP supports up to 24 I/O modules.

 

Which PROFIBUS-DP rates does it support?

It supports 9.6, 19.2, 93.75, 187.5, and 500 kbaud, as well as 1.5 and 6 Mbaud.

 

What are its data-frame limits?

The maximum input data frame is 244 bytes and the maximum output data frame is 244 bytes.

 

Does it support HART devices?

Yes. It supports HART process variables and status, with HART pass-through messaging available through the local configuration port and an 8512 HART Comms interface.

 

Which carrier does it require?

It must be mounted on an 8715-CA-BI BIM carrier.

 

How is it configured?

It can be parameterized from a PROFIBUS configurator using a GSD file, or configured with the 8455-SW-CF software. The configuration is stored in non-volatile memory.

 

What is its operating temperature range?

The ATEX declaration specifies an ambient temperature range of −40 to +70 °C.

 

Does it support SafetyNet SOE functions?

No. The 8502-BI-DP is a serial BIM, and SafetyNet SOE functions are not supported on serial BIMs.