Description
Core Product Summary
The GE IC694ALG222 is a high-density analog voltage input module for the PACSystems RX3i platform. It provides 16 single-ended or 8 differential input channels, with each channel independently configurable for 0 to +10 V (unipolar) or –10 to +10 V (bipolar) ranges.
Factory-calibrated resolution is 2.5 mV per count on the 0–10 V range and 5 mV per count on the bipolar range. The module supports configurable high and low alarm limits, optical isolation between field and backplane, and installs in any RX3i I/O slot. It draws power from the backplane +5 VDC bus and the isolated +24 VDC supply.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Product Type | Analog Voltage Input Module |
| Platform | PACSystems RX3i |
| Channels | 1–16 selectable single-ended or 1–8 selectable differential |
| Input Ranges | 0 to +10 V (unipolar, default) or –10 to +10 V (bipolar); per channel |
| Resolution | 2.5 mV (1 LSB) on 0–10 V; 5 mV (1 LSB) on ±10 V |
| Update Rate | 6 ms (all 16 single-ended channels); 3 ms (all 8 differential channels) |
| Absolute Accuracy | ±0.25 % of full scale at 25 °C; ±0.5 % over operating temperature range |
| Linearity | < 1 LSB |
| Isolation (Field to Backplane & Frame Ground) | 250 VAC continuous; 1500 VAC for 1 minute |
| Input Impedance | >500 kΩ (single-ended); higher in differential mode |
| Input Filter Response | 41 Hz (single-ended); 82 Hz (differential) |
| Power Consumption | 112 mA max from +5 VDC backplane; 41 mA max from isolated +24 VDC |
| Diagnostics | MODULE OK and MODULE P/S LEDs |
Detailed Product Overview
The IC694ALG222 converts analog voltage signals from field devices into digital values for the RX3i controller. Channel count and wiring mode are selected in configuration software: the module can operate as a full 16-channel single-ended bank or as an 8-channel differential bank. Each channel is independently set for either the unipolar or bipolar voltage range, and high/low alarm thresholds can be defined for both ranges.
Factory calibration ensures consistent scaling—2.5 mV per count on the 0–10 V range and 5 mV per count on the ±10 V range. Update performance is 6 ms across all 16 single-ended channels or 3 ms across all 8 differential channels. Optical isolation separates the field side from the backplane and frame ground, providing continuous 250 VAC isolation and 1500 VAC withstand for one minute.
Power is taken from the RX3i backplane +5 VDC bus and the isolated +24 VDC supply. When the module is installed in a Universal Backplane, an external isolated +24 VDC source must be connected via the TB1 terminal block on the left side of the rack. In an Expansion Backplane the power supply provides the isolated 24 V. Status is indicated by two front-panel LEDs: MODULE OK reports successful power-up diagnostics and normal operation; MODULE P/S confirms adequate +5 VDC supply voltage.
The module occupies a single I/O slot and is compatible with standard RX3i terminal blocks for field wiring. Configuration is performed through the PACSystems programming software, allowing selection of channel mode, range, and alarm limits without hardware jumpers.

IC694ALG222
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Controller Platform | PACSystems RX3i | Any I/O slot with serial connector |
| Series 90-30 | Compatible in slots with serial connector | Verify backplane type |
| Power – Universal Backplane | External isolated +24 VDC required | Connect via TB1 on left side of rack |
| Power – Expansion Backplane | Isolated +24 VDC supplied by power supply | No external 24 V needed |
| Field Wiring | Single-ended or differential | Selected in configuration software |
| Terminal Block | Standard RX3i analog terminal block | Supports the module’s channel density |
| Configuration Software | PACSystems programming environment | Sets channel count, range, and alarms |
Dimensions, Mounting & Connection Notes
The module occupies one standard RX3i I/O slot. Field connections are made through a removable terminal block on the front of the module. Wiring diagrams distinguish single-ended and differential configurations; proper shielding and grounding practices should follow the RX3i system manual recommendations. The front panel provides clear channel labeling (I1–I16) and the two status LEDs.
FAQ
What is the GE IC694ALG222?
It is a 16-channel analog voltage input module for the PACSystems RX3i platform that supports 16 single-ended or 8 differential inputs.
What voltage ranges does it accept?
Each channel can be configured for 0 to +10 V (unipolar) or –10 to +10 V (bipolar).
What is the resolution?
2.5 mV per count on the 0–10 V range and 5 mV per count on the ±10 V range.
How fast does the module update?
6 ms for all 16 single-ended channels or 3 ms for all 8 differential channels.
Does it require external power?
In a Universal Backplane an external isolated +24 VDC supply is required via TB1. In an Expansion Backplane the power supply provides the isolated 24 V.
What isolation is provided?
250 VAC continuous and 1500 VAC for one minute between field and backplane/frame ground.
Can high and low alarms be set?
Yes. High and low alarm limits are configurable for both input ranges.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626