Sale!

GE IS215UCVEM08 US2000 VME Controller

  • Model: IS215UCVEM08
  • Brand: General Electric
  • Series: Mark VI Speedtronic / US2000
  • Functional Acronym: UCVE
  • Core Function: Executes Mark VI turbine-control processing
  • Product Type: Single-slot VME controller / PC control module
  • Key Specs: Intel Celeron 300 MHz; 32 MB DRAM; QNX real-time operating system
  • Communication: 10BaseT/100BaseTX Ethernet; two RS-232C ports
  • Service Interfaces: SVGA monitor; keyboard and mouse
  • Alternate Reference: UCVE08A; verify interchangeability
  • ⚠️ Legacy Model: Limited stock available
  • Condition: Confirm before ordering: New Original / New Surplus / Refurbished
Categories: , , , , SKU: IS215UCVEM08 Brand:

Description

Key Technical Specifications

Parameter Value
Manufacturer General Electric
Model IS215UCVEM08
Functional Acronym UCVE
Alternate Reference UCVE08A; verify exact compatibility
System Family GE Mark VI Speedtronic
Platform US2000 controller architecture
Module Type Single-slot VME controller / PC control module
Processor Intel Celeron, 300 MHz; verify board revision
Operating System QNX real-time operating system
System Memory 32 MB DRAM; verify actual board configuration
Ethernet One 10BaseT/100BaseTX RJ-45 port
Serial Ports COM1 and COM2, RS-232C
Service Display SVGA monitor interface
Peripheral Interfaces Keyboard and mouse connections
Local Storage CompactFlash or other installed storage; verify actual unit
Controller Memory Battery-backed SRAM; verify battery condition
Status Indication Three front-panel status LEDs
Backplane VME bus
Installation Mark VI controller rack; verify intended slot
Typical Supply 125 V DC Mark VI rack supply; verify cabinet documentation
Operating Temperature 0 to 60 °C; confirm applicable system specification
Software Image Site-specific GE Mark VI application; verify before purchase
Configuration Site-specific controller and network settings; not automatically included

Supplier references identify the IS215UCVEM08 as a Mark VI UCVE controller with Ethernet, two RS-232C ports, and service interfaces. Processor, memory, storage, software image, and exact power requirements should be verified against the board revision and GE documentation.

 

Product Introduction

The GE IS215UCVEM08 is a single-slot VME UCVE controller for GE Mark VI Speedtronic turbine-control systems. It executes turbine-control software and communicates with the Mark VI control architecture through one 10BaseT/100BaseTX Ethernet port and two RS-232C serial ports.

The US2000-based controller also provides SVGA, keyboard, and mouse service connections. Verify the exact processor, memory, storage media, QNX software image, battery condition, rack slot, Ethernet configuration, and approved replacement status before commissioning.

IS215UCVEM08

IS215UCVEM08

IS215UCVEM08

IS215UCVEM08

Troubleshooting Quick Reference

Symptom Possible Cause Relevance to This Part Quick Check Method Recommendation
Controller does not power up Missing 125 V DC rack supply, blown fuse, poor VME seating, backplane fault ✅ High Verify rack power at the approved test points and inspect the board’s VME connectors Check rack supply and seating before replacing the controller
No normal startup sequence Failed processor, corrupted storage image, memory fault, incorrect board revision ✅ High Observe the three status LEDs and connect an approved service monitor if available Record the startup code and verify the installed software image
Mark VI system reports controller offline Ethernet cable, IONet/network fault, wrong address, failed controller interface ✅ High Test the cable and switch port; verify IP configuration and network diagnostics Correct the network path before condemning the UCVE board
Ethernet link LED remains off No link partner, incorrect cable, failed RJ-45 interface, switch disabled ⚠️ Medium Connect to a known-good switch port and check link status at both ends Replace cable or switch port first; test the board only after the physical link is proven
COM1 or COM2 does not communicate Incorrect pinout, baud rate, handshaking, cable, or failed serial port ⚠️ Medium Perform a controlled serial loopback test with the approved cable and port settings Verify the service device and cable before replacing the controller
Controller repeatedly reboots Unstable rack supply, overheating, failed memory, damaged storage media ✅ High Trend supply voltage and temperature; inspect boot logs and storage diagnostics Correct power and cooling issues before installing another controller
QNX fails to boot Corrupt CompactFlash or software image, storage failure, memory fault ✅ High Inspect boot messages and compare the storage media with a verified image Restore only the approved Mark VI image; do not use a generic QNX image
Application loads but turbine control remains unavailable Wrong configuration, missing network parameters, incompatible software revision ✅ High Compare controller configuration, IP settings, application version, and rack assignment with the original Restore the site-specific configuration and validate with the system owner
SVGA monitor shows no service output Monitor/cable issue, incorrect boot stage, failed video interface ⚠️ Medium Test with a known-good compatible monitor and verify controller startup indicators Treat video loss separately from controller failure
Keyboard or mouse is unresponsive Peripheral compatibility, connector fault, service-port configuration ❌ Low Test known-good peripherals during a controlled service session Use the Mark VI-approved service hardware; process control may still be operational
Several Mark VI functions fail simultaneously Controller failure, VME bus fault, common rack power loss ✅ High Check rack power, controller LEDs, VME diagnostics, and communication with adjacent cards Diagnose common infrastructure before replacing multiple I/O boards
Replacement controller will not assume control Wrong UCVE variant, incompatible software image, configuration mismatch, battery-backed data issue ✅ High Compare complete labels, revision, storage media, application, and network settings Confirm approved interchangeability before field installation

Support note: Contact technical support with photos of the complete controller label, board revision, LED pattern, VME rack slot, software/storage media, Ethernet configuration, boot messages, and Mark VI diagnostic logs.

 

Frequently Asked Questions (FAQ)

 

What is the GE IS215UCVEM08?

The IS215UCVEM08 is a GE Mark VI UCVE controller and PC control module used in Speedtronic turbine-control applications. It is a VME processor board, not a conventional analog or digital I/O module.

 

What processor and memory does it use?

Supplier documentation commonly identifies an Intel Celeron 300 MHz processor and 32 MB of DRAM. Because legacy UCVE assemblies can vary by revision or installed configuration, confirm the actual board markings and applicable GE manual before using those values as acceptance criteria.

 

What communication interfaces are available?

The listed interfaces are one 10BaseT/100BaseTX Ethernet port, two RS-232C ports labeled COM1 and COM2, an SVGA service-monitor connection, and keyboard/mouse service connections. Confirm the physical connector arrangement on the exact unit before purchase.

 

Is the IS215UCVEM08 interchangeable with UCVE08A?

Some suppliers list UCVE08A as an alternate reference, but that does not prove universal interchangeability. Compare hardware revision, processor and memory configuration, storage media, QNX image, Mark VI application, rack position, and network configuration before substitution.

 

Can I hot-swap the ?

Do not assume hot swapping is permitted. The controller executes turbine-control software, and removing it can cause loss of control, diagnostics, or redundancy. Follow the GE Mark VI maintenance procedure and the plant’s approved isolation and transfer process before removing the board.

 

Will a replacement include the turbine-control software?

Not necessarily. A surplus or refurbished board may include a blank, damaged, outdated, or site-specific storage image. Confirm whether the CompactFlash or other storage media is included, whether the correct QNX/Mark VI image is installed, and whether configuration backup and restoration are part of the supply.

 

Is this controller obsolete?

The belongs to the legacy GE Mark VI platform and is generally sourced through surplus, refurbished, repair, or exchange channels. Request the exact part-number photo, board revision, software status, battery condition, functional test report, warranty, and return terms before purchasing.