Honeywell FS-SDI-1624 SIL 3 Safe Digital Input Module

The Honeywell SDI-1624 (available as conformal-coated model FC-SDI-1624 and non-conformal-coated model FS-SDI-1624) is a 16-channel safe digital input module engineered for use in Honeywell Safety Manager and Fail Safe Control (FSC) systems. The module provides sixteen independent 24 VDC fail-safe input channels designed to monitor process field states—such as pushbuttons, limit switches, and pressure switch contact outputs—in safety-instrumented applications.

Categories: , , , , SKU: FS-SDI-1624 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The Honeywell SDI-1624 (available as conformal-coated model FC-SDI-1624 and non-conformal-coated model FS-SDI-1624) is a 16-channel safe digital input module engineered for use in Honeywell Safety Manager and Fail Safe Control (FSC) systems. The module provides sixteen independent 24 VDC fail-safe input channels designed to monitor process field states—such as pushbuttons, limit switches, and pressure switch contact outputs—in safety-instrumented applications.

Certified for functional safety up to SIL 3 according to IEC 61508, the SDI-1624 module incorporates continuous self-diagnostics and internal testing to ensure fast fault detection and high system availability. The module operates on 24 VDC field voltage, featuring a HIGH threshold above 15 VDC and a LOW threshold below 9 VDC, with a typical input response delay of 10 ms. It occupies a standard 4 TE (4 HP) rack width in the chassis and communicates directly with the controller backplane for execution of emergency shutdown (ESD) and safety interlock logic.

 

Key Technical Specifications

Specification Value / Detail
Product Type 16-Channel Safe Digital Input Module
Model Variants FC-SDI-1624 (Conformal Coated) / FS-SDI-1624 (Non-Coated)
System Platform Honeywell Safety Manager / FSC Architecture
Number of Channels 16 fail-safe digital input channels
Nominal Field Voltage 24 VDC
Maximum Input Voltage 36 VDC
Input Current 7 mA typical at 24 VDC
Voltage Thresholds Input HIGH: > 15 VDC; Input LOW: < 9 VDC (I < 2 mA)
Input Delay Typically 10 ms
Logic Power Requirements 5 VDC, 8 mA (from backplane)
Module Width / Size 4 TE (4 HP), 3 HE (3U) slot footprint
Functional Safety Rating Certified IEC 61508 SIL 3
Standard Approvals CE, TÜV, UL, CSA, FM

 

Detailed Product Overview

The Honeywell SDI-1624 safe digital input module functions as a critical field interface card within Honeywell Safety Manager systems. In safety-critical industrial processes—including burner management systems (BMS), emergency shutdown (ESD), and fire and gas monitoring—the module continuously reads discrete field signals and passes verified process states to the central safety controller.

Each of the 16 digital input channels monitors field contacts powered by a 24 VDC loop. The internal hardware architecture includes extensive diagnostic routines that test channel integrity without disturbing active process monitoring. In the event of an internal hardware fault or out-of-spec voltage condition, the module drives the affected channel to a defined fail-safe state to prevent unmonitored hazards.

The module is produced in two ordering versions: the FS-SDI-1624 for standard operating environments and the FC-SDI-1624, which features conformal coating (indicated by “CC” in revision codes) to protect internal surface-mount components from corrosive gases, moisture, and airborne contaminants found in harsh chemical or offshore installations.

FC-SDI-1624

FC-SDI-1624

FC-SDI-1624

FC-SDI-1624

Engineering Selection Highlights

  • SIL 3 Functional Safety: Certified to IEC 61508 SIL 3 standards for use in high-integrity safety-instrumented functions (SIF).
  • 16-Channel Density: Provides 16 discrete input channels in a compact 4 TE (4 HP) module footprint to optimize cabinet rack space.
  • Conformal Coating Option: Available as FC-SDI-1624 with conformal coating to resist corrosive atmospheric conditions.
  • Defined Switching Thresholds: Operates with a clear 15 VDC HIGH threshold and 9 VDC LOW threshold, preventing noise-induced false trips.
  • Integrated Key Coding: Features mechanical key coding on connectors to prevent accidental insertion of incorrect module types into the rack slot.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
System Controller Honeywell Safety Manager / FSC Chassis Must be installed in a designated I/O slot on the Safety Manager backplane.
Field Termination Compatible Field Termination Assembly (FTA) Connects to field wiring via system cables linked to dedicated digital input FTAs.
Logic Power 5 VDC system backplane power Draws 8 mA from the 5 VDC chassis supply.
Field Loop Power 24 VDC field power supply Field contacts must be powered from a clean 24 VDC supply (\pm 10\%).

 

Dimensions, Mounting & Connection Notes

  • Physical Dimensions: Standard 3U height (3 HE), 4 HP width (4 TE) form factor.
  • Mounting Style: Direct card-edge insertion into Honeywell Safety Manager I/O rack slots.
  • Connector Keying: Utilizes pin key coding (Module connector holes A5/C5 matching chassis pins A5/C5) to ensure correct slot alignment.
  • Environmental Limits: Operating temperature range within standard Safety Manager chassis limits; conformal-coated variants (FC prefix) recommended for harsh chemical exposure.

 

FAQ

What is the difference between FC-SDI-1624 and FS-SDI-1624?

The FC-SDI-1624 is conformal-coated to protect components against moisture and corrosive atmospheres, whereas the FS-SDI-1624 is the standard non-conformal-coated version.

What system platform does the SDI-1624 belong to?

It belongs to the Honeywell Safety Manager and Fail Safe Control (FSC) system architecture.

How many input channels does the module provide?

The module provides 16 discrete safe digital input channels.

What is the input voltage rating for the SDI-1624?

It operates on nominal 24 VDC signals, with an input HIGH threshold above 15 VDC, an input LOW threshold below 9 VDC, and a maximum withstand voltage of 36 VDC.

What safety certifications apply to this module?

The SDI-1624 is TÜV certified for IEC 61508 SIL 3 safety applications and holds CE, UL, CSA, and FM approvals.

 

Verification & Troubleshooting Notes

  • Status LED Monitoring: Observe front panel LEDs to verify logic power presence, channel state (ON/OFF), and module fault conditions.
  • Field Voltage Verification: If input channels remain OFF when contacts are closed, check field loop supply to ensure incoming voltage exceeds the 15 VDC HIGH threshold.
  • Keying Alignment: If the card does not slide smoothly into the chassis, check connector pin coding (A5/C5) to ensure the slot is keyed correctly for an SDI-1624 card.