Description
Core Product Summary
The Honeywell R7247C1001 is a solid-state, plug-in dynamic self-check rectification flame amplifier for flame-safeguard systems using C7012E or C7012F ultraviolet flame detectors. It processes the detector signal, indicates flame presence, and provides a 2–4 second flame-failure response time.
The amplifier operates from a 102–132 V AC, 50/60 Hz supply and is intended for use with Honeywell BC7000, R4140, R4075C/D/E, R4138C/D, and FSP5075 flame-safeguard controls or amplifier modules. Its dynamic self-check circuit tests the flame-detection electronics during burner operation and shuts the burner down if the detection system fails.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Honeywell |
| Model | R7247C1001 |
| Product type | Dynamic self-check rectification flame amplifier |
| Detection principle | Ultraviolet (UV) flame detection |
| Compatible flame detectors | C7012E and C7012F ultraviolet flame detectors |
| Flame-failure response time | 2–4 seconds |
| Self-check function | Dynamic self-check |
| Self-check rate | 60–240 tests per minute |
| Supply voltage | 102–132 V AC |
| Supply frequency | 50/60 Hz |
| Construction | Solid-state, plug-in design |
| Color | Green |
| Weight | 0.20 kg |
Engineering Selection Highlights
- The R7247C1001 is a dynamic self-check amplifier, so it continuously tests the flame-detection circuit during burner operation and initiates burner shutdown if the detection system fails.
- It is specifically paired with C7012E or C7012F ultraviolet flame detectors; flame-detector type, sighting, and installation must match the amplifier’s UV detection principle.
- Its 2–4 second flame-failure response time is a safety-response characteristic that must be consistent with the requirements of the associated flame-safeguard control and burner application.
- The 102–132 V AC, 50/60 Hz supply range defines the electrical operating window; the amplifier must be installed in a control circuit that provides voltage within this range.
- The plug-in format is intended for use with compatible Honeywell flame-safeguard control platforms, including BC7000, R4140, R4075C/D/E, R4138C/D, and FSP5075 modules.
- The amplifier is listed by UL under File No. MP268, Guide No. MCCZ2, and certified by CSA under File No. LR1620,Guide 名列前茅40-A-2; it is also identified as acceptable under CSD-1.
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Flame detector | Honeywell C7012E or C7012F ultraviolet flame detector | The amplifier is designed for UV flame detection using these detector models. |
| Primary safety controls | BC7000, R4140, R4075C/D/E, R4138C/D | The amplifier is specified for use with these Honeywell flame-safeguard controls. |
| Amplifier modules | FSP5075A1 or FSP5075A3 | The R7247C1001 is listed for use with these flame-amplifier modules. |
| Fuel applications | Gas, oil, or coal | The C7012E/F UV detector and amplifier combination is specified for these fuel types. |
| Supply power | 102–132 V AC, 50/60 Hz | The control circuit must supply voltage within this range. |
| Installation | Plug-in amplifier | The unit is a plug-in module for the compatible flame-safeguard control architecture. |
Dimensions, Mounting & Connection Notes
| Item | Specification |
|---|---|
| Form factor | Solid-state plug-in amplifier |
| Weight | 0.20 kg |
| Supply connection | 102–132 V AC, 50/60 Hz |
| Detector connection | C7012E or C7012F ultraviolet flame detector |
| Mounting context | Installed in a compatible Honeywell flame-safeguard control or amplifier-module arrangement |
| Indicator color | Green |
Detailed Product Overview
The Honeywell R7247C1001 is a dynamic self-check rectification flame amplifier used with ultraviolet flame detectors in burner flame-safeguard applications. It is a solid-state, plug-in unit that responds to the signal from a C7012E or C7012F UV flame detector and indicates the presence of flame to the associated safety control.
The amplifier operates from 102–132 V AC at 50 or 60 Hz. Its flame-failure response time is 2–4 seconds, meaning that loss of the validated flame signal is processed within this response window under the amplifier’s specified operating conditions.
A defining feature is dynamic self-checking. The self-check circuit tests the electronic components of the flame-detection system 60 to 240 times per minute during burner operation. If the self-check identifies a detection-system failure, the amplifier supports burner shutdown through the associated flame-safeguard control.
The R7247C1001 is intended for use with Honeywell BC7000, R4140, R4075C/D/E, and R4138C/D flame-safeguard controls, as well as FSP5075A1 or FSP5075A3 flame-amplifier modules. The compatible detector is the C7012E or C7012F ultraviolet flame detector, which senses ultraviolet radiation generated by the flame.
The unit is UL Listed under File No. MP268, Guide No. MCCZ2, and CSA Certified under File No. LR1620,Guide Top 40- A-2. It is also identified as acceptable under CSD-1. These approval references apply to the amplifier’s documented flame-safety role and should be reviewed together with the complete burner-control installation requirements.

R7247C1001

R7247C1001
Applications & System Role
The R7247C1001 occupies the flame-signal processing position in a Honeywell burner-management or flame-safeguard system. It receives the ultraviolet signal from a C7012E or C7012F flame detector, determines flame presence, and communicates the flame status to the associated flame-safeguard control.
In gas, oil, or coal burner applications, the amplifier’s dynamic self-check function continuously exercises the flame-detection electronics while the burner operates. If the detection system fails, the associated control can shut down the burner, supporting the flame-safety function of the overall system.
FAQ
What is the Honeywell R7247C1001?
The Honeywell R7247C1001 is a solid-state, plug-in dynamic self-check rectification flame amplifier for ultraviolet flame-detection systems.
Which flame detectors work with the R7247C1001?
It is designed for use with Honeywell C7012E and C7012F ultraviolet flame detectors.
What is the flame-failure response time?
The flame-failure response time is 2–4 seconds.
What does dynamic self-check do?
The dynamic self-check circuit tests the flame-detection electronics 60–240 times per minute during burner operation and supports burner shutdown if the detection system fails.
Which Honeywell controls is it used with?
The R7247C1001 is specified for use with BC7000, R4140, R4075C/D/E, and R4138C/D flame-safeguard controls, as well as FSP5075A1 or FSP5075A3 flame-amplifier modules.
What power supply does it require?
It requires a 102–132 V AC, 50/60 Hz supply.
What approvals apply to the R7247C1001?
The amplifier is UL Listed under File No. MP268, Guide No. MCCZ2, and CSA Certified under File No. LR1620,Guide 名列前茅40-A-2. It is also identified as acceptable under CSD-1.
15 个来源

WhatsApp: +86 16626708626
Email: