Core Product Summary
The Honeywell SDOL-0424 (type numbers FS-SDOL-0424 and FC-SDOL-0424) is a safe loop-monitored digital output module designed for Honeywell Safety Manager systems. It provides four 24 V DC solid-state source output channels, each rated 1 A, for driving resistive or inductive loads in safety-critical applications.
Each channel includes loop monitoring for lead breakage and short-circuit detection, plus an integrated suppression diode for inductive loads. The outputs, monitoring circuits, and suppression diodes are fully tested for use in safe applications. The module occupies 4 TE / 3 HE (4 HP / 3U) and requires an IO backplane together with a BSDOL-04UNI range-setting module. Approvals include CE, TÜV, UL, CSA, and FM.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Product type | Safe loop-monitored digital output module |
| Type numbers | FS-SDOL-0424, FC-SDOL-0424 |
| Number of channels | 4 |
| Output type | 24 V DC solid-state source, short-circuit proof |
| Maximum channel current | 1 A |
| Maximum total module load | 3.6 A (module dissipation limit) |
| Maximum load inductance | 0.5 H |
| Maximum load capacitance | 1 μF |
| Voltage drop | < 1.3 V at 1 A |
| Off current | < 0.1 mA |
| Current-sense voltage drop | < 1 V at 1 A |
| Overload detection threshold | > 10 Ω |
| Cold-resistance lamp threshold | > 20 Ω |
| Power requirements | 5 V DC 15 mA; 24 V DC internal 50 mA; 24 V DC external 15 mA (no load) |
| Space requirements | 4 TE, 3 HE (= 4 HP, 3U) |
| Approvals | CE, TÜV, UL, CSA, FM |
| Key coding | Module holes A13, C9; chassis large pins A13, C9 |
Engineering Selection Highlights
- Four independent 24 V DC / 1 A solid-state channels with full loop monitoring support selection for safety-instrumented digital outputs where lead-breakage and short-circuit detection are required.
- Integrated suppression diodes on every channel allow direct connection of inductive loads up to the stated inductance and current limits without external freewheeling components.
- Secondary means of de-energizing (SMOD) enables the watchdog or processor to force outputs off independently of the application logic, supporting higher-integrity de-energize-to-trip designs.
- Requires an IO backplane and a BSDOL-04UNI module with appropriate range-setting sub-modules (S/L/M/H) matched to expected load power; incorrect range selection affects monitoring thresholds.
- Compact 4 TE / 3 HE footprint and defined key coding (A13/C9) ensure correct physical placement and prevent insertion into incompatible slots.
- Power draw on the 5 V and dual 24 V supplies must be accounted for in system power budgeting, especially when multiple modules share the same backplane supplies.

SDOL-0424

SDOL-0424
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| System family | Honeywell Safety Manager | Module is part of the Safety Manager I/O portfolio |
| Backplane | IO backplane required | Module cannot be used without the appropriate IO backplane |
| Range-setting companion | BSDOL-04UNI with S/L/M/H sub-modules | Sub-module selection sets lead-breakage current thresholds according to load power |
| Power supplies | 5 V DC logic + 24 V DC internal + 24 V DC external | Internal 24 V must be present for self-tests; external 24 V supplies the loads |
| Field termination | Compatible FTAs (e.g., TSDOL-0424C or TSDO-04UNI families) | Connection examples show use with corresponding FTAs for redundant or non-redundant I/O |
| Key coding | Holes A13/C9 on module; large pins A13/C9 on chassis | Prevents insertion into incorrect slots |
Dimensions, Mounting & Connection Notes
The module occupies 4 TE width by 3 HE height (equivalent to 4 HP by 3U). It mounts in a standard Safety Manager chassis/IO backplane. Key coding uses module holes A13 and C9 with corresponding large pins on the chassis.
Connector pin allocation includes dedicated pins for each output (OUT1+ to OUT4+ and associated 0 V), 24 V DC internal and external supplies, watchdog input, and logic supply. Connection examples in the hardware reference show wiring to field termination assemblies for both non-redundant and redundant configurations. Dummy loads or actual field loads must be present on all channels during lead-breakage testing to avoid false fault detection. The internal 24 V supply connection is required to prevent self-test faults.
Detailed Product Overview
The Honeywell SDOL-0424 is a specialized output module engineered for safety-instrumented applications inside the Safety Manager platform. It converts application logic commands into four independent 24 V DC solid-state source outputs, each capable of supplying up to 1 A while continuously supervising the external circuit for open-wire and short-circuit conditions.
Because the outputs are solid-state, switching is fast and free of mechanical wear. Each channel incorporates a suppression diode so that inductive loads can be driven directly within the stated inductance and current limits. The complete output path—including the switching element, the diode, and the current-sensing circuitry—is subjected to automatic diagnostic tests that verify the ability to de-energize, the absence of crosstalk, correct diode function, and the integrity of the field wiring. A secondary de-energize path (SMOD) allows the system watchdog or processor to force the outputs off regardless of the state of the application program, providing an independent shutdown mechanism.
Physical integration requires an IO backplane and a BSDOL-04UNI companion module that carries the range-setting sub-modules. These sub-modules (S, L, M, or H) select the appropriate lead-breakage current threshold according to the expected load power, ensuring that the monitoring remains effective across a wide range of field devices. Power is drawn from three rails: a low-current 5 V logic supply, an internal 24 V rail used for module functions and testing, and an external 24 V rail that supplies the actual load current. Both internal and external 24 V connections, together with loads (or dummy loads) on every channel, must be present for the diagnostic tests to complete without spurious faults.
The module’s 4 TE / 3 HE form factor and fixed key coding simplify chassis layout and prevent incorrect insertion. Status LEDs on each channel provide local indication of output state and ongoing diagnostic activity. Taken together, these features make the SDOL-0424 a purpose-built component for safety systems that demand continuous verification of both the module’s own output capability and the integrity of the field wiring connected to critical actuators.
Applications & System Role
The SDOL-0424 functions as a safe digital output stage within Honeywell Safety Manager architectures. It drives field devices such as solenoids, valves, or indicators that must be de-energized under defined safety conditions.
Its primary role is to provide four independently monitored, short-circuit-proof 24 V DC outputs that continuously verify wiring integrity and output capability. The secondary de-energize path and full diagnostic coverage of the switching elements, diodes, and monitoring circuits allow the module to participate in safety functions that require proven ability to remove energy from the process. Range-setting sub-modules on the companion BSDOL-04UNI adapt the monitoring thresholds to the actual load power, ensuring reliable detection across light- and heavier-load applications.
FAQ
What is the Honeywell SDOL-0424?
It is a safe loop-monitored digital output module that provides four 24 V DC, 1 A solid-state channels with continuous lead-breakage and short-circuit detection for Honeywell Safety Manager systems.
Which systems is the SDOL-0424 designed for?
It belongs to the Honeywell Safety Manager I/O family and requires an IO backplane plus a BSDOL-04UNI range-setting module.
What load types can the module drive?
It supports both resistive and inductive loads. Each channel includes a suppression diode, with maximum ratings of 1 A per channel, 0.5 H inductance, and 1 μF capacitance.
What monitoring functions does it provide?
Every output is continuously monitored for lead breakage in the external wiring and for short-circuit conditions. The monitoring thresholds are set by the companion BSDOL-04UNI range-setting sub-modules.
What power supplies does the module need?
It requires 5 V DC at 15 mA for logic, 24 V DC internal at 50 mA, and 24 V DC external at 15 mA (plus load current). The internal 24 V connection is required for correct self-test operation.
What is the maximum total load the module can handle?
The maximum combined load across all four channels is 3.6 A, limited by module dissipation.
What approvals does the SDOL-0424 carry?
The module is approved to CE, TÜV, UL, CSA, and FM standards.