Description
Core Product Summary
The ICS Triplex T8310 is a Trusted TMR Expander Processor module for the ICS Triplex Trusted automation platform. It resides in the processor slots of a Trusted Expander Chassis and provides the slave interface between the triplicated Expander Bus and the Expander Chassis backplane.
The module enables multiple Trusted chassis systems to be connected through the Expander Bus while retaining the fault-tolerant, high-bandwidth Inter-Module Bus (IMB) used by I/O modules. Its HIFT TMR architecture provides fault containment for the Expander Bus, the module itself, and the Expander Chassis. The T8310 operates from dual redundant +24 Vdc power supplied through the Trusted Expander Chassis backplane and supports hot replacement, hot-standby configurations, and module-spare repair strategies.
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | ICS Triplex |
| Exact model | T8310 |
| Product type | Trusted TMR Expander Processor module |
| Product family | ICS Triplex Trusted |
| Architecture | Triple Modular Redundant (TMR), Hardware Implemented Fault Tolerant (HIFT) |
| Operating mode | Fault-tolerant 3-2-0 operation |
| System role | Slave interface between Expander Bus and Expander Chassis backplane |
| Module location | Processor slots of a Trusted Expander Chassis |
| Backplane supply | Dual redundant +24 Vdc via the Expander Chassis backplane |
| Backplane supply range | 20–32 Vdc |
| Power dissipation | 45 W backplane supply |
| Expansion media | Unshielded twisted-pair (UTP) Expander Bus connections |
| Copper expansion distance | Up to 30 m using TC-301 copper cable |
| Fiber expansion distance | Up to 10 km using T8314 Fiber TX/RX Units |
| Isolation | 50 V basic insulation, module to backplane supply |
| Fusing | Not user-serviceable |
| Operating temperature | 0 to +60 °C (+32 to +140 °F) |
| Storage temperature | -25 to +70 °C (-13 to +158 °F) |
| Relative humidity | 10% to 95%, non-condensing |
| Dimensions | 266 mm H × 31 mm W × 303 mm D |
| Weight | 1.33 kg |
| Front-panel indication | Module health and status indicators |
Engineering Selection Highlights
- The T8310 is specifically a Trusted TMR Expander Processor, so it should be selected for Trusted Expander Chassis applications rather than as a general-purpose controller or I/O module.
- Its role as the slave interface between the Expander Bus and the Expander Chassis backplane makes it a required system element when extending a Trusted system across multiple chassis.
- The HIFT TMR architecture and 3-2-0 fault-tolerant operation support fault containment within the Expander Bus, module, and Expander Chassis.
- The triplicated, point-to-point Expander Bus uses separate command and response media, with voting at the Expander Bus interface to tolerate cable faults.
- Copper expansion using TC-301 cable supports distances up to 30 m; fiber expansion using T8314 Fiber TX/RX Units supports distances up to 10 km, allowing the appropriate media to be selected for the physical layout.
- The module receives dual redundant +24 Vdc power from the Trusted Expander Chassis backplane, so chassis power distribution must be designed for the module’s 45 W backplane power dissipation.
- Hot replacement and hot-standby or module-spare configurations support maintenance strategies without requiring a complete system shutdown, subject to the configured Trusted system architecture.

T8310

T8310
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Trusted system family | ICS Triplex Trusted | The T8310 is part of the Trusted TMR expansion architecture. |
| Chassis location | Trusted Expander Chassis processor slots | The module is installed in the processor slots of the Expander Chassis. |
| Main processor connection | TMR Expander Interface Module and triplicated Expander Bus | Communication with the TMR Processor uses this interface arrangement. |
| I/O communication | Inter-Module Bus (IMB) on the Expander Chassis backplane | The IMB connects the module to I/O modules in the Expander Chassis. |
| Expansion cable | TC-301 copper cable or T8314 Fiber TX/RX Units | Copper supports up to 30 m; fiber supports up to 10 km. |
| Backplane power | Dual redundant +24 Vdc, 20–32 Vdc | Power is supplied through the Expander Chassis backplane. |
| Maintenance configuration | Hot replacement, hot standby, and module spare configurations | The applicable strategy depends on the configured Trusted system. |
Dimensions, Mounting & Connection Notes
The ICS Triplex T8310 measures 266 mm high, 31 mm wide, and 303 mm deep, and weighs 1.33 kg. It is installed in a processor slot of a Trusted Expander Chassis.
The module connects to the triplicated Expander Bus through the TMR Expander Interface Module and communicates with Expander Chassis I/O modules through the backplane IMB. It receives dual redundant +24 Vdc power through the backplane connector; no separate field power supply is used. Fusing is not user-serviceable.
The module is rated for 0 to +60 °C operation, -25 to +70 °C storage, and 10% to 95% non-condensing relative humidity. Front-panel indicators display module health and status.
Detailed Product Overview
The ICS Triplex T8310 is the Trusted TMR Expander Processor used in ICS Triplex Trusted systems that require expansion beyond a single controller chassis. Installed in the processor slots of a Trusted Expander Chassis, it acts as the slave-side interface between the triplicated Expander Bus and the Expander Chassis backplane.
The Expander Bus allows multiple chassis systems to be implemented using unshielded twisted-pair cable connections. At the same time, the Expander Chassis retains the Inter-Module Bus used for fault-tolerant, high-bandwidth communication between interface modules and the TMR Processor. The T8310 therefore provides the bridge that makes distributed Trusted I/O expansion possible without changing the fundamental IMB communication model within the Expander Chassis.
The module uses Hardware Implemented Fault Tolerant TMR architecture arranged in a lock-step configuration. It contains three principal fault containment regions, each with interfaces to the Expander Bus and IMB, an active/standby interface to the other TMR Expander Processor in the chassis, control logic, communications transceivers, and power supplies. A fourth fault containment region handles non-critical monitoring and display functions.
Communication between the T8310 and the TMR Processor is handled through the TMR Expander Interface Module and the triplicated Expander Bus. Each Expander Bus channel uses separate command and response media, and voting occurs at the Expander Bus interface. This arrangement is intended to tolerate cable faults while maintaining triplicated operation in the remainder of the Expander Processor.
For expansion distances up to 30 m, the system can use TC-301 copper cable. For longer distances, T8314 Fiber TX/RX Units support expansion distances up to 10 km. The selected medium should match the physical separation, cabinet layout, and Trusted system expansion design.
The T8310 receives dual redundant +24 Vdc power through the Expander Chassis backplane, with each fault containment region deriving its supplies independently. It dissipates up to 45 W from the backplane supply. Hot replacement, hot-standby operation, and module-spare configurations are supported, and front-panel indicators provide module health and status information for maintenance and diagnostics.
Applications & System Role
In a Trusted automation architecture, the ICS Triplex T8310 extends the Trusted controller system to one or more Expander Chassis locations. It provides the processing and bus-interface function that allows I/O modules in an Expander Chassis to communicate with the Trusted TMR Processor across the triplicated Expander Bus.
The module is relevant where a Trusted system requires additional chassis capacity or physical separation between the controller chassis and I/O chassis. Its copper and fiber expansion options support different distance requirements, while its TMR architecture is intended to contain faults within the Expander Bus, module, or Expander Chassis.
FAQ
What is the ICS Triplex T8310?
The ICS Triplex T8310 is a Trusted TMR Expander Processor module for the ICS Triplex Trusted automation platform.
What does the T8310 do?
It provides the slave interface between the triplicated Expander Bus and the backplane of a Trusted Expander Chassis, enabling communication between the Trusted TMR Processor and Expander Chassis I/O modules.
Where is the T8310 installed?
It is installed in the processor slots of a Trusted Expander Chassis.
What redundancy architecture does it use?
It uses Hardware Implemented Fault Tolerant Triple Modular Redundant (HIFT TMR) architecture with 3-2-0 fault-tolerant operation.
How does the T8310 connect to the Trusted TMR Processor?
It communicates through the TMR Expander Interface Module and the triplicated, point-to-point Expander Bus.
What expansion media and distances are supported?
TC-301 copper cable supports expansion distances up to 30 m, while T8314 Fiber TX/RX Units support distances up to 10 km.
How is the module powered?
It is powered by dual redundant +24 Vdc supplies from the Trusted Expander Chassis backplane, with an operating range of 20–32 Vdc.
Does the T8310 support hot replacement?
Yes. The module supports hot replacement, as well as hot-standby and module-spare configurations within the supported Trusted system architecture.

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626