Description
Core Product Summary
The ICS Triplex T8830 is a Trusted 40-channel analog input Field Termination Assembly (FTA) for the Rockwell Automation (ICS Triplex) Trusted TMR safety platform, designed as the primary interface between field devices generating analog signals and the Trusted TMR analog input module T8431. It provides termination for up to 40 input channels using industry-standard 2-wire field device connections, with a 250 Ω resistor per channel converting the incoming loop current to the voltage measured by the input module.
Field power is derived from dual 24 Vdc feeds, diode-commoned on the FTA, and distributed to each channel through an individual 50 mA fuse, which effectively limits the current in each field loop. A green onboard LED indicates the presence of field power. The assembly mounts on a standard DIN rail, connects to the T8431 through the pre-assembled I/O cable at a 96-way connector, and carries the SmartSlot link that enables “one-to-many” online replacement of input modules. Rockwell’s Trusted product documentation lists the T8830 for ordinary and hazardous locations with ATEX and IECEx coverage.
Key Technical Specifications
| Parameter | Value |
|---|---|
| Product type | Trusted 40-channel analog input Field Termination Assembly (FTA) |
| Input channels | 40 input channels per FTA |
| Associated I/O module | Trusted TMR analog input module T8431 (system-powered two-wire devices) |
| Field device connections | Industry-standard 2-wire arrangements |
| Signal conversion | 250 Ω resistor per channel; voltage fed directly to the analog input module |
| Field supply | Dual 24 Vdc feeds, diode-commoned on the FTA |
| Voltage range | 18 to 32 Vdc |
| Channel signal range | 0 to 22 mA per channel |
| Power consumption | 5 W (field supply); 0.25 W for the LED power indicator |
| Loop protection | TR5, 50 mA fuse per channel (quantity 40); effectively limits field loop current |
| Power indication | Onboard green LED indicating field power supply presence |
| Module interface cable | Terminates at the 96-way socket SK1; SmartSlot version 1 signals carried on SK1, SmartSlot connector SK2 (also 96-way) |
| Field power terminals | 5-way terminal block (PWR TB) for the dual dc field supplies |
| Signal terminals | 2-wire arrangements terminated on 12-off 3-way terminal blocks and 2-off 2-way terminal blocks |
| Mounting | Standard DIN rail |
| Location ratings | Ordinary locations / hazardous locations, with ATEX and IECEx coverage in the Trusted product documentation |
Detailed Product Overview
The T8830 is not a signal-processing module — it is the engineered wiring layer between the field and the Trusted T8431 analog input module. Its value lies in what it standardizes: the dropping resistor, loop power distribution, fusing, and termination layout for 40 two-wire analog loops are fixed on the assembly, so channel-to-channel consistency is built in rather than depending on panel wiring practice.
Each channel follows one simple electrical path. The dual 24 Vdc field supplies are diode-commoned on the FTA, so the loss of one feed does not interrupt loop power; a green LED confirms supply presence. From there, power reaches each channel through its own 50 mA TR5 fuse, which caps the current a field loop can draw. The two-wire field device sits in the loop, and the current it generates develops a voltage across the channel’s 250 Ω resistor — the value the T8431 measures directly. This is the same 250 Ω conversion assumed by the T8431’s engineering-unit scaling (4-20 mA mapping to -1024 to 4096 counts at 1024 counts per volt), which is why the FTA and module must be specified as a pair.
Terminations are organized for practical loop wiring: field signals land on 3-way and 2-way terminal blocks (12 three-way blocks plus 2 two-way blocks across the 40 channels), and the dual dc supplies connect at a dedicated 5-way power terminal block. The connection to the T8431 is a single pre-assembled I/O cable terminating at the FTA’s 96-way connector SK1, which also carries the SmartSlot version 1 signals; a second 96-way SmartSlot connector (SK2) is not used where SmartSlot version 2 is deployed in the Trusted system. Because the FTA carries the SmartSlot link, a single spare slot arrangement can serve the online replacement of multiple input modules — the “one-to-many” hot-replacement topology supported by the Trusted I/O SmartSlot cables.
For hazardous-area installations, the Trusted product documentation lists the T8830 with ordinary-location, hazardous-location, ATEX, and IECEx coverage, and an IECEx Certificate of Conformity covers T8830 revisions A and B. Engineers planning such installations should verify the applicable certificate scope against the specific revision being installed.

T8830

T8830
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
|---|---|---|
| Associated input module | Trusted TMR analog input module T8431 (T8431/T8431C) | Allows connection of system-powered two-wire devices to the T8431; the 250 Ω channel resistor matches the module’s engineering-unit scaling |
| Module interface | 96-way socket SK1 for the pre-assembled I/O cable linking the FTA to the T8431 | Interface cable is pre-assembled and fitted with specialized hoods that secure the cable in a metal slot retainer |
| SmartSlot link | SmartSlot version 1 signals carried on SK1; SK2 connector unused where SmartSlot version 2 is employed in the Trusted system | Enables one-to-many online replacement of input modules |
| I/O cable types | Trusted I/O Companion Slot cables (ICSTT-RM311, e.g. TC-201/TC-203) and Trusted TMR I/O SmartSlot cables (ICSTT-RM313, e.g. TC-503) | Cable selection publications list the T8830/T8831 among the supported FTAs |
| Field power | Dual 24 Vdc feeds (18-32 Vdc operating range), diode-commoned at the FTA | Connected via the 5-way terminal block PWR TB |
| Channel protection | TR5, 50 mA fuse per channel, 40 fuses per FTA | Limits fault current in each individual field loop |
| Mounting | Standard DIN rail | Field wiring lands on 3-way and 2-way terminal blocks |
| Location approvals | Ordinary and hazardous locations, ATEX and IECEx coverage per the Trusted product documentation; IECEx Certificate of Conformity covers revisions A and B | Verify certificate scope against the installed revision |
Dimensions, Mounting & Connection Notes
The T8830 mounts on a standard DIN rail, and its physical installation is built around the pre-assembled interface cable that links the FTA to its I/O module. This cable arrives pre-assembled and fitted with a pair of specialized hoods used to secure it in place; the FTA hood fits into a metal slot retainer, which reduces integration time and prevents strain on the 96-way connector SK1.
Field wiring divides into two groups. The 40 field input signals connect as 2-wire arrangements, terminated on twelve 3-way terminal blocks and two 2-way terminal blocks. The dual dc field power supplies land on the dedicated 5-way terminal block PWR TB; the two feeds are diode-commoned on the assembly, and the green LED adjacent to the power section confirms supply presence before loops are commissioned. Each channel is individually fused at 50 mA, so a wiring fault during commissioning is contained to one loop rather than affecting the shared supply.
Before power-up, verify that the SmartSlot connector configuration matches the system: with SmartSlot version 1, module SmartSlot signals route through SK1; the second 96-way SmartSlot connector (SK2) is not used where the Trusted system employs SmartSlot version 2.
FAQ
What is the ICS Triplex T8830?
The T8830 is a Trusted 40-channel analog input Field Termination Assembly that serves as the primary interface between analog field devices and the Trusted TMR analog input module T8431.
Is the T8830 an I/O module?
No. It is a field termination accessory — it provides loop power distribution, per-channel fusing, the 250 Ω signal conversion resistors, and the terminal blocks and connectors for field wiring, while the T8431 module performs the signal acquisition.
Which module does the T8830 work with?
It is designed for the Trusted TMR analog input module T8431, allowing connection of system-powered two-wire devices.
How are 4-20 mA signals handled?
The field loop current develops a voltage across the 250 Ω resistor on each FTA channel, which is fed directly to the T8431 for measurement — matching the module’s 1024-counts-per-volt scaling.
How is field power supplied on the T8830?
From dual 24 Vdc feeds (18-32 Vdc range) that are diode-commoned on the FTA, distributed to each channel through an individual 50 mA fuse; a green LED indicates power presence.
Does the T8830 support online module replacement?
Yes. The FTA carries the SmartSlot connection, enabling the “one-to-many” hot replacement of Trusted input modules under the SmartSlot cabling arrangement.
Can the T8830 be used in hazardous areas?
The Trusted product documentation lists the T8830 for ordinary and hazardous locations with ATEX and IECEx coverage, and an IECEx Certificate of Conformity covers revisions A and B; installations should verify certificate scope against the installed revision.
How is the T8830 mounted and wired?
It mounts on a standard DIN rail; the 40 field signals terminate as 2-wire arrangements on 3-way and 2-way terminal blocks, dual field supplies land on a 5-way power terminal block, and the module connection is a pre-assembled cable terminating at the 96-way connector SK1.
Documented Performance Data
| Metric | Value | Condition |
|---|---|---|
| Field supply voltage range | 18 to 32 Vdc | Dual 24 Vdc feeds, diode-commoned |
| Power consumption | 5 W from field supply | Per FTA; 0.25 W attributable to the LED power indicator |
| Channel signal range | 0 to 22 mA per channel | Per Trusted product documentation |
| Loop protection | 50 mA fused per loop (TR5, quantity 40) | Effectively limits current in each field loop |
| Signal conversion element | 250 Ω resistor per channel | Voltage fed directly to the T8431 analog input module |
| Module interface connector | 96-way socket SK1 (plus 96-way SmartSlot connector SK2, unused with SmartSlot version 2) | Pre-assembled I/O cable with securing hoods |

WhatsApp: +86 16626708626
Email:
Phone: +86 16626708626