Sale!

ICS Triplex T9432 AADvance 16-Channel Isolated Analogue Input Module

The ICS Triplex T9432 is a 16-channel isolated analogue input module for the AADvance safety controller platform. It measures current signals in the range of 0 to 24 mA DC (nominal 4 to 20 mA) and supplies both digital state and analogue data to the processor for process monitoring and safety applications.

Description

Core Product Summary

The ICS Triplex T9432 is a 16-channel isolated analogue input module for the AADvance safety controller platform. It measures current signals in the range of 0 to 24 mA DC (nominal 4 to 20 mA) and supplies both digital state and analogue data to the processor for process monitoring and safety applications.

The module supports simplex, dual, or triple modular redundant (TMR) arrangements when paired with matching termination assemblies (T9831, T9832, or T9833). It mounts on the T9300 I/O base, operates from a redundant nominal 24 V DC supply, dissipates 4.0 W, and provides channel isolation of ±1.5 kV DC. Configurable monitoring bands support field-device diagnostics and line monitoring, with HART Command 03 pass-through capability.

Key Technical Specifications

Parameter Value
Product type 16-channel isolated analogue input module
System / series AADvance
Input channels 16
Nominal input current 4 to 20 mA DC
Maximum measurement range 0 to 24 mA DC
Resolution 0.98 µA, 15-bit
Sample update interval (no filter) 6 ms
Calibrated accuracy at 25 °C ±0.05 mA
Module supply Redundant +24 V DC nominal (18–32 V DC range)
Module power dissipation 4.0 W (13.6 BTU/hr)
Channel isolation (maximum withstanding) ±1.5 kV DC for 1 minute
Safety integrity level IEC 61508 SIL 3 (configuration dependent)
Safety level degradation 1oo1D, 1oo2D, 2oo3D
Typical module scan times Simplex: 1.170 ms; Dual: 1.965 ms; Triple: 2.656 ms
Dimensions (H × W × D) 166 mm × 42 mm × 118 mm
Weight 340 g (12 oz)
Compatible terminations T9831 (simplex), T9832 (dual), T9833 (TMR)
Mounting base T9300 I/O base

Detailed Product Overview

The ICS Triplex T9432 functions as a high-density isolated analogue input module within the AADvance controller architecture. It accepts field current signals, converts them to digital values, and delivers both the analogue measurement and discrete state information to the system processors. Configurable voltage bands on each channel enable line monitoring and basic field-device diagnostics without additional hardware.

In safety instrumented systems the module participates in simplex, dual, or TMR voting schemes. The selected redundancy level is determined by the associated termination assembly and the number of modules installed on the T9300 I/O base. This flexibility allows system designers to match integrity requirements while controlling channel density and cabinet space.

Isolation of ±1.5 kV DC between channels and between field and backplane protects the controller from field-side faults. The 15-bit resolution and 6 ms sample update interval (unfiltered) support accurate process measurement for continuous monitoring and safety logic. HART Command 03 support permits the application to retrieve additional device information alongside the primary process variable.

Power is drawn from the system’s redundant 24 V DC supply. At 4.0 W dissipation the module contributes modestly to overall heat load, simplifying thermal design in multi-module assemblies. Local channel and module status indicators assist commissioning and maintenance.

The T9432 is intended for integration into AADvance systems only; it is not interchangeable with Trusted series modules. Correct pairing with the appropriate termination assembly and adherence to the documented installation and configuration procedures are required for proper operation and for maintaining the intended safety integrity level.

 T9432

T9432

 T9432

T9432

Dimensions, Mounting & Connection Notes

  • Dimensions: 166 mm height × 42 mm width × 118 mm depth
  • Weight: 340 g (12 oz)
  • Housing: Plastic, non-flammable
  • Mounting: Plugs into a T9300 I/O base unit; the base mounts on DIN rail or panel
  • Termination: Field connections are made on the companion T9831, T9832, or T9833 termination assembly, which attaches to the T9300 base
  • Conductor size on termination assembly: maximum 1.31 mm² (16 AWG), strip length 6 mm
  • Terminal screw tightening torque on termination assembly: minimum 0.5 Nm (follow full manufacturer procedure)

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
System / controller family AADvance Not compatible with Trusted series chassis or modules
I/O base T9300 Required mounting base
Termination assemblies T9831 (simplex), T9832 (dual), T9833 (TMR) Must match the intended redundancy arrangement
Module population One (simplex), two (dual), or three (TMR) T9431/T9432 modules Determined by selected termination assembly
Power supply Redundant nominal 24 V DC (18–32 V DC) Supplied via the backplane
Configuration software AADvance Workbench Required for channel monitoring levels and HART settings
Field wiring Conductor cross-section max. 1.31 mm² (16 AWG), 6 mm strip length Per termination assembly specification
Channel fuses (on TA) 50 mA, 125 V, Type T Replaceable without removing modules

FAQ

What is the ICS Triplex T9432?
It is a 16-channel isolated analogue input module for the AADvance safety controller platform that measures 0–24 mA current signals.

Which system does the T9432 belong to?
It belongs to the AADvance controller family and mounts on the T9300 I/O base.

What input range does the T9432 support?
Nominal 4–20 mA DC with a maximum measurement range of 0–24 mA DC.

What termination assemblies are required?
T9831 for simplex, T9832 for dual, or T9833 for TMR arrangements. The termination must match the number of modules installed.

Does the T9432 support HART?
Yes, it supports HART Command 03 pass-through for retrieval of field-device information.

What is the module power dissipation?
4.0 W (13.6 BTU/hr) from the redundant 24 V DC system supply.

What isolation is provided?
Channel-to-channel and channel-to-chassis isolation of ±1.5 kV DC for one minute.

What are the typical scan times?