Sale!

ICS Triplex T9802 AADvance 16-Channel Dual Digital Input TA

Parameter Specification
Manufacturer & Series ICS Triplex / Rockwell Automation AADvance System
Model Number T9802 (Conformal-coated version: T9802C)
Assembly Type AADvance 16-Channel Dual Isolated Digital Input Termination Assembly
System Format Dual / Redundant (interfaces with 2 digital input modules in parallel)
Safety Integrity Level Certified for IEC 61508 SIL 3 application loops
Channel Capacity 16 galvanically isolated discrete digital input channels
Categories: , , , , SKU: T9802 Brand:

Description

Core Product Summary (Brand / Model / Key Attributes)

The ICS Triplex T9802 is a 16-channel Dual Isolated Digital Input Termination Assembly (TA) for the Rockwell Automation AADvance safety and critical control system. Designed to mount directly behind or adjacent to I/O base units, this field termination assembly interfaces field switch contacts and discrete safety sensors with companion AADvance digital input modules (such as the T9401 and T9402). The dual-socket layout allows two digital input modules to plug into the same field wiring assembly in parallel, creating fault-tolerant 1oo2 or 2oo3 voting architectures.

Engineered for IEC 61508 SIL 3 safety application loops, the T9802 provides 16 galvanically isolated input channels that eliminate common-return ground loops and contain electrical noise. The assembly features screw terminals for secure field cable connection, onboard field power distribution, and optional conformal coating (T9802C variant) for deployment in corrosive or humid process environments. By supporting dual active input modules simultaneously, the T9802 enables live online hot-swapping and continuous signal monitoring without opening field loops or interrupting safety logic execution.

 

Key Technical Specifications

Parameter Specification
Manufacturer & Series ICS Triplex / Rockwell Automation AADvance System
Model Number T9802 (Conformal-coated version: T9802C)
Assembly Type AADvance 16-Channel Dual Isolated Digital Input Termination Assembly
System Format Dual / Redundant (interfaces with 2 digital input modules in parallel)
Safety Integrity Level Certified for IEC 61508 SIL 3 application loops
Channel Capacity 16 galvanically isolated discrete digital input channels
Operating Voltage Nominal 24 VDC (Operating field range: 18 VDC to 32 VDC)
Channel Isolation Channel-to-channel and channel-to-logic galvanic isolation
Host Card Compatibility Pairs with T9401 / T9402 Digital Input Modules
Field Termination Type Screw terminal blocks for field sensor and power connections
Operating Temperature -10 °C to 60 °C (Standard span; supports extended boundaries)
Storage Temperature -40 °C to 85 °C (-40 °F to 185 °F)
Relative Humidity 5% to 95%, non-condensing
Environmental Approvals CE, cULus, ATEX Zone 2 / IECEx, Class I Division 2 certified

 

Detailed Product Overview

The ICS Triplex T9802 Field Termination Assembly (TA) serves as the primary field-to-logic physical interface for discrete signal acquisition within the Rockwell Automation AADvance controller system. Applied across high-integrity process safety installations—such as Emergency Shutdown (ESD) pushbuttons, gas detector alarm contacts, burner management interlocks, and turbomachinery trip loops—the T9802 terminates field wiring cables and passes isolated discrete signals directly to processing modules.

Architecturally, the T9802 features a dual-module socket design that accepts two T9401 or T9402 digital input cards side-by-side. Signal lines from each of the 16 field channels are passively routed to both module connectors simultaneously. This layout allows the controller to perform hardware voting across paired input cards (1oo2D or 2oo3) while ensuring that removing one module for maintenance or replacement does not break the field loop or disturb signal continuity to the remaining card.

The T9802 incorporates galvanic isolation across all 16 channels, isolating field wiring from backplane logic power and preventing ground potential shifts from affecting adjacent channels. Onboard power distribution busbars simplify field wiring by distributing 24 VDC loop power to dry-contact field switches directly from the assembly terminals, reducing the need for external marshaling terminal strips.

T9802

T9802

T9802

T9802

Engineering Selection Highlights

  • Dual-Module Fault Tolerance: Connects two digital input modules in parallel to support 1oo2D fail-operational voting and hot-swappable maintenance.
  • 16 Isolated Channels: Complete channel-to-channel galvanic isolation eliminates common-ground noise and prevents fault propagation.
  • Direct Field Power Distribution: Integrated 24 VDC supply distribution simplifies field wiring for dry contacts and passive switches.
  • Online Hot-Swapping Support: Allows companion input cards to be extracted and replaced live without disturbing field terminal connections.
  • SIL 3 System Certification: Fully approved for deployment in safety-critical instrumented loops conforming to IEC 61508 SIL 3.
  • Conformal Coating Option: Available as variant T9802C with factory-applied conformal coating for harsh or high-humidity process environments.

 

System Compatibility & Integration Requirements

Item / Dependency Verified Compatibility or Requirement Practical Note
Companion I/O Modules T9401 / T9402 Isolated Digital Input Modules Plugs directly into the dual connectors of the T9802 assembly.
I/O Base Unit T9300 3-Way I/O Base Unit Mounts adjacent to or behind the I/O base unit assembly on standard DIN rail.
Field Power Source 24 VDC Regulated Field Power Supply Connects to power input terminals on the T9802 to energize field contact loops.
Configuration Toolset AADvance Workbench Software configures channel allocation, fault reporting, and line monitoring.

 

Dimensions, Mounting & Connection Notes

  • Mounting Method: Mounts on standard TS35 DIN rail directly alongside or beneath the associated T9300 I/O Base Unit.
  • Field Connection Terminals: Heavy-duty screw terminals accept stranded or solid field conductors for 16 digital input loops and power supply feeds.
  • Wiring Practice: Route field input cables in separate trunking away from high-voltage AC lines to preserve EMC noise immunity.
  • Thermal Range: Rated for industrial operating ambient temperatures between -10 °C and 60 °C under standard cabinet ventilation.

 

FAQ

What is the primary function of the ICS Triplex T9802?

The T9802 is a 16-channel dual isolated digital input termination assembly that routes discrete field signals to companion AADvance digital input modules.

Why does the T9802 feature a dual-module design?

The dual-module layout allows two input cards to connect to the same field wiring assembly simultaneously, enabling fault-tolerant voting (such as 1oo2D) and online hot-swapping.

How many channels does the T9802 termination assembly support?

The T9802 supports 16 independent, galvanically isolated digital input channels.

Which AADvance I/O modules are compatible with the T9802?

The T9802 pairs directly with T9401 and T9402 isolated digital input modules.

Does the T9802 provide channel isolation?

Yes, the T8902 features complete channel-to-channel and channel-to-logic galvanic isolation across all 16 input points.

What is the difference between the T9802 and T9802C variants?

The T9802C variant includes factory-applied conformal coating on the circuit board to protect against moisture, chemical vapors, and airborne contaminants in harsh industrial environments.

 

Verification & Troubleshooting Notes

  • Terminal Tightness: Check field terminal screw torque during commissioning to prevent intermittent contact faults caused by cabinet vibration.
  • Field Loop Power Checks: Verify that 24 VDC field supply voltage delivered to the T9802 terminals remains within 18 VDC to 32 VDC under full load.
  • Module Seating: Ensure both companion digital input cards are fully latched into the T9802 connectors to maintain reliable dual-bus communication.
  • Conformal Coating Inspection: For T9802C units installed in aggressive chemical environments, inspect terminal areas periodically for severe oxidation or corrosive buildup.