Description
Core Product Summary (Brand / Model / Key Attributes)
The Kongsberg RMP420 is an advanced remote multipurpose input/output module engineered for industrial alarm monitoring and integrated control systems. Designed as part of the Kongsberg system architecture, this interface unit handles a total of 32 software-configurable, solid-state field channels supporting a wide array of signal types including analog inputs and outputs, digital inputs and outputs, and temperature sensors.
The module interfaces with host control computers via a dual remote I/O process bus (RBUS) network, providing robust, galvanically isolated, and redundant communication. It features integrated high-side drivers with short-circuit protection for loop power output, comprehensive per-channel loop monitoring, dynamic A/D calibration, and broad operational compatibility across demanding industrial and hazardous environments certified for Ex Zone 2 applications.
Key Technical Specifications
| Technical Parameter | Specification Value |
| Product Type / Function | Remote Multipurpose I/O Module (32 Channels) |
| Input Supply Voltage | 24 VDC (18 to 31.2 V) |
| Power Consumption | 10 W typical (excluding loop power) |
| Communication Interface | Dual RS485 RBUS (2×9-pin male D-Sub, galvanically isolated) |
| Channel Configuration | 32 software-configurable multipurpose channels (AI, AO, DI, DO, RTD) |
| Analog Input (AI) Ranges | 0–4 V, 0–10 V, 0–20 mA (Accuracy: ±0.15% of full scale) |
| Analog Output (AO) Ranges | 0–10 V, 0–20 mA (Accuracy: ±0.35% of full scale) |
| Temperature Measurement | PT100 (2 or 3-wire), range -200°C to 600°C |
| Digital Output Drivers | Short-circuit proof high-side drivers (trip current approx. 1.4 A) |
| Pulse/Frequency Input | Up to 10 kHz pulse count, 2.5 kHz encoder count |
| Operating Temperature | -15°C to +70°C |
| Ingress Protection | IP 20 (IEC 60529) |
| Dimensions & Weight | 355 mm × 158 mm × 87 mm |
| Hazardous Area Certification | Ex Zone 2 approved |
Detailed Product Overview
The Kongsberg RMP420 serves as a critical data acquisition and control interface positioned between field instrumentation and host automation controllers. In complex industrial architectures, it acts as a decentralized node that reduces wiring complexity by multiplexing multiple signal types through a unified hardware footprint.
Each of the 32 channels can be independently configured via software to handle diverse signal topologies, eliminating the need for dedicated single-function input or output cards. This flexibility accommodates mixed instrumentation layouts involving standard voltage/current loops, binary status switches, and temperature monitoring elements like PT100 sensors.
System reliability is reinforced by redundant communication pathways through dual RBUS interfaces, ensuring uninterrupted data flow to the host control computer (RCU) even during a single-line communication fault. Built-in diagnostic features, automatic recovery protection for faulty channels, and embedded overvoltage protection mechanisms safeguard connected field devices against transient electrical disturbances.

RMP420

RMP420
System Compatibility & Integration Requirements
| Item / Dependency | Verified Compatibility or Requirement | Practical Note |
| Host Controller | Compatible with control systems utilizing RBUS communication protocol | Interfaces directly with remote control units (RCU) |
| Communication Bus | RS485 via dual 9-pin male D-Sub connectors | Galvanically isolated to protect internal circuitry |
| Power Supply | 24 VDC nominal (18 to 31.2 V range) | Requires external fuses to limit input current |
| Terminal Blocks | Screw terminals accepting up to 2.5 mm² wire cross-section | Tightening torque specified at 0.4 to 0.5 Nm |
Engineering Selection Highlights
- 32 Multipurpose Channels: Reduces hardware variant counts by allowing individual channels to be software-configured for AI, AO, DI, DO, or RTD measurements.
- Redundant Bus Integration: Dual RS485 RBUS connection ports support fault-tolerant communication architectures with host control computers.
- Integrated Loop Power: Features short-circuit protected high-side drivers supplying 24 VDC directly to field loops from the module supply.
- Specialized Pulse/Frequency Support: Channels support up to 10 kHz frequency inputs and encoder up/down counting for rotational or flow measurement requirements.
- Hazardous Area Suitability: Certified for deployment in Ex Zone 2 environments, expanding installation possibilities in industrial process zones.
Dimensions, Mounting & Connection Notes
- Physical Dimensions: Measures 355 mm in height, 158 mm in width, and 87 mm in depth.
- Mounting Standard: Designed for standard DIN rail mounting systems.
- Wiring Terminations: Utilizes screw terminal blocks supporting conductor cross-sections up to 2.5 mm² with recommended terminal screw torques of 0.4 to 0.5 Nm.
- Enclosure Protection: Offers IP 20 ingress protection, requiring installation within an appropriate protective cabinet or control housing for harsher environments.
- Environmental Limits: Rated for operational temperatures ranging from -15°C to +70°C and storage down to -25°C, with relative humidity tolerance up to 98% non-condensing.
FAQ
What is the Kongsberg RMP420?
The Kongsberg RMP420 is a remote multipurpose input/output module designed for industrial alarm monitoring and integrated control systems.
How many channels does the RMP420 support?
The module features 32 software-configurable solid-state channels capable of handling analog inputs/outputs, digital inputs/outputs, and temperature sensor loops.
What communication interface does the module use to connect to the host?
It communicates with host control computers via a dual remote I/O process bus (RBUS) utilizing galvanically isolated RS485 connections.
Can the RMP420 measure temperature directly?
Yes, it supports 2-wire and 3-wire Resistance Temperature Detectors (such as PT100) across a temperature range of -200°C to 600°C.
Is the module certified for hazardous areas?
Yes, the RMP420 is certified for deployment in Ex Zone 2 applications.
Verification & Troubleshooting Notes
- Status Indicators: Utilize front-panel status LEDs to check module operational health, power presence, and communication traffic state.
- Overload Behavior: High-side drivers include a software-based fuse function that automatically trips and switches off the output loop if current exceeds approximately 1 A due to a short circuit, preventing thermal overload.
- Communication Loss: In the event of host communication failure, outputs default to predefined soft or hard fail-safe states programmed via system configuration.